China Oil Immersed Pole Mounted Power Distribution Transformer with Onan Cooling, Find details about China Distribution Transformer, Oil Immersed Transformer from Oil Immersed Pole Mounted Power Distribution Transformer with Onan Cooling
Rated capacity (KVA) | Voltage group(KV) | Vector group | Impedance voltage(%) | (KW) Loss | No-load current(%) | |
No-load | Load | |||||
10 | (HV) 11 10.5 10 6.3 6 (LV) 0.4 0.69 | Yyno Dyn11 | 4 | 0.065 | 0.4 | 3.5 |
20 | 0.08 | 0.52 | 3.0 | |||
30 | 0.1 | 0.63/0.6 | 2.3 | |||
50 | 0.13 | 0.91/0.87 | 2.0 | |||
63 | 0.15 | 1.09/1.04 | 1.9 | |||
80 | 0.18 | 1.31/1.25 | 1.9 | |||
100 | 0.2 | 1.58/1.5 | 1.8 | |||
125 | 0.24 | 1.89/1.8 | 1.7 | |||
160 | 0.28 | 2.31/2.2 | 1.6 | |||
200 | 0.34 | 2.73/2.6 | 1.5 | |||
250 | 0.4 | 3.2/3.05 | 1.4 | |||
315 | 0.48 | 3.83/3.65 | 1.4 | |||
400 | 0.57 | 4.52/4.3 | 1.3 | |||
500 | 0.68 | 5.41/5.15 | 1.2 | |||
630 | 4.5 | 0.81 | 6.2 | 1.1 | ||
800 | 0.96 | 7.5 | 1.0 | |||
1000 | 1.15 | 10.3 | 1.0 | |||
1250 | 1.36 | 12.0 | 0.9 | |||
1600 | 1.64 | 14.5 | 0.8 | |||
2000 | 1.96 | 19.8 | 0.8 | |||
2500 | 2.31 | 23.0 | 0.7 |