China 12kv Indoor High Voltage Vacuum Switch (ZN63 VS1), Find details about China Vacuum Switch, Indoor Vacuum Switch from 12kv Indoor High Voltage Vacuum Switch (ZN63 VS1)
Item | Unit | Date | |||||||||
Rated voltage | kV | 12 | |||||||||
Rated frequency | Hz | 50 | |||||||||
Rated insulation level | 1min power frequency withstand voltage | pole to earth | kV | 42 | |||||||
phase | kV | 48 | |||||||||
lightning impulse withstand voltage | pole to earth | kV | 75 | ||||||||
phase | kV | 85 | |||||||||
Power frequency withstand voltage of secondary circuit | V | 2000 | |||||||||
Rated current(1) | A | 630 | 630 | 630 | 2000 | 1250 | 2500 | 1600 | 3150 | ||
1250 | 1250 | 1250 | 2500 | 1600 | 3150 | 2000 | 4000 | ||||
1600 | 3150 | 2000 | 4000 | 2500 | 5000 | ||||||
Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 | 50 | |||||
Rated short-time withstand current | kA | 20 | 25 | 31.5 | 40 | 50 | |||||
Rated short circuit duration | s | 4 | |||||||||
Rated peak withstand current | kA | 50 | 63 | 80 | 100 | 125 | |||||
Rated short-circuit making current | kA | 50 | 63 | 80 | 100 | 125 | |||||
Rated short-circuit current breaking time (class E2) | times | 30 | |||||||||
Rated single/back to back capacitor bank breaking current | A | 630/400 | 800/400 | ||||||||
Clearance between open contacts | mm | 11±1 | |||||||||
Contact stroke | mm | 3~4 | |||||||||
Allowable wear thickness of contact | mm | 3 | |||||||||
Average opening speed | m/s | 0.9~1.4 | |||||||||
Average closing speed | m/s | 0.5~1.0 | |||||||||
Contact closing bounce time | ms | ≤2 | |||||||||
Different phase of contact closing and opening | ms | ≤2 | |||||||||
Rebound amplitude of opening contact | mm | ≤2 | |||||||||
Opening time (rated voltage) | ms | 20~50 | |||||||||
Closing time (rated voltage) | ms | 30~70 | |||||||||
Mechanical life (M2) | times | 10,000(20,000) | |||||||||
Rated operating voltage | V | AC110/220 DC110/220 | |||||||||
Rated operation sequence | 0-0.3s-CO-180s-CO |