Water Cooled Scroll Chiller for Spraying

China Water Cooled Scroll Chiller for Spraying, Find details about China Water Chiller, Screw Chillers from Water Cooled Scroll Chiller for Spraying

Model NO.
RHP-060WS
Application Fields
Chemical
Application Machine
CNC Machine Tools
Certification
CSA, RoHS, UR, ISO, UL, CE, CCC
Condition
New
Refrigerant
R22/R3047c/R134A
Input Power
45kw
Frequency
50/60Hz
Size
2900X1100X1500mm
Weight
1860kg
Warranty
12months
Refrigerant Capacity
186.5kw
Trademark
Ruihai
Transport Package
Plywood Case
Specification
Standard quality. SGS, CE
Origin
Shenzhen
HS Code
8418699090
Model NO.
RHP-060WS
Application Fields
Chemical
Application Machine
CNC Machine Tools
Certification
CSA, RoHS, UR, ISO, UL, CE, CCC
Condition
New
Refrigerant
R22/R3047c/R134A
Input Power
45kw
Frequency
50/60Hz
Size
2900X1100X1500mm
Weight
1860kg
Warranty
12months
Refrigerant Capacity
186.5kw
Trademark
Ruihai
Transport Package
Plywood Case
Specification
Standard quality. SGS, CE
Origin
Shenzhen
HS Code
8418699090
Water Cooled Scroll Chiller for Spraying


Water Cooled Scroll Chiller for Spraying

Main Features

1. Equipped with imported compressor and high efficiency condeser and evaporator, excellent cooling capacity, quite and low electricity consumption.
2. 304S.S or 316 S.S tanks are equipped, easy to clean and maintain.
3. Use electronic thermostat to keep temperature within 3-5 ºC.
4. Installed with current overload protector, high and low pressure switch, electronic timer delay, fault display system.
5. Have LCD Screen to display the outlet and inlet and temperatures setting of chill water.
6. Single or double or four compressors combination unit are available for your chillers to meet your refrigeration requirement, have English and China human-machine interface.

Technical Parameters:
 
Model No.RHP
-025W
RHP
-030W
RHP
-035W
RHP
-040W
RHP
-045W
RHP
-050W
RHP
-060W
Power Supply3N - 50HZ - 380V
Refrigeration Capacity
(50HZ)
KW78.295.2108.3125.1139.8155.3186.5
Kcal/h672508187093130107580120230133560160390
Power Consumptionkw20.224.628.332.236.540.348.5
Freezing Water Flowm3/h13.616.018.821.224.126.531.8
Cooling Water Flowm3/h17.220.524.027.330.834.240.8
CompressorTypeScroll Type / Piston Type
StartingScroll Type / Piston Type
Output(kw)18.822.526.330.033.837.545.0
RefrigerantTypeStandard R-22 / Eco-friendly R134a or R407c
ControlThermostatic Expansion Valve
Vol (kg)12.515.017.520.222.525.030.0
EvaporatorTypeShell and Tube Type
Pipe Dia.PT2-1/2"PT3"
CondenserTypeShell and Tube Type
Pipe Dia.PT2-1/2"PT3"
Built-in TankVol (L)180220220220280280280
Built-in Pumpkw1.52.22.22.23.03.03.0
Protection Deviceshigh/low pressure switch, freeze protection device, safety valve, overload protection device, coil overheat protector, temperature automatic protective switch and etc
SizeL(mm)1700170022002200220024002400
W(mm)850850900900900900900
H(mm)1300130013501350135014501400
WeightKG63082010001090120014301600
Work Condition:
1. The above data is based on freezing water inlet temp 12ºC, outlet temp 7ºC, cooling water inlet temp 30ºC, outlet temp 35ºC.
2. The above specification may be modified due to product improvement without any prior notice, please confirm with our salesman before you place the order.

Work Principle:

Water Cooled Scroll Chiller for Spraying


Applications:
Be widely used in plastics, electroplating, electronics manufacturing, pharmaceutical chemicals, food processing, refrigeration and other industrial establishments and guesthouses, hotels, shopping malls, office buildings and other types of civil air-conditioning system.Water Cooled Scroll Chiller for Spraying

Package & Shipping
Use standard export plywood case with forklift truck feet, easy to load and unload
5-7 days to finish the production after receiving the deposit
Shipping by LCL or FCL


After-sales service:

12 months quality warranty since the date of delivery.
Free of charge to replace new chillersif quality problems.
Cost price to buy extra parts with Chillers from Ruihai if needed.
24 hours online service by e-mail, WhatsApp, Skype or Telephone Calling.
Installation Video to help installation even send engineer to customer's jobsite if needed.


Necessary info to Quote
1.What is your cooling capacity?_____    Kcal/hr  or   _____KW?
2. What's your power supply?  For example: 220V-50Hz-1N (N=Phase )
3.What refrigerant type do you require? R22 or R134a or R407c?
4. What's your ambient temperature? And what is your chiller inlet and outlet water temperature?
5. Which industry do you use the chiller in?