HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China

HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China, Find details about China Damper Actuator, Electric Control Damper Actuator from HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China

Trademark
SOLOON
Transport Package
Cartons
Origin
China
Trademark
SOLOON
Transport Package
Cartons
Origin
China

Features of S6061SF-05Fire Smoke Fire Smoke Damper Actuator

 

  • ON/OFF or 0-10V

  • Shaft size up to 12* 12mm

  • Two fixed auxiliary switches

  • With IP54 standard

  • Without Manuel Override

  • 72ºC thermal sensor are optional

 

Technical datasheet of S6061SF-05Fire Smoke Fire Smoke Damper Actuator

 

Item

S6061SF05DF(S)/24V

S6061SF05DF(S)/220V

S6061SF-05AF/24V

Torque

5Nm

Damper area

1m2

Power supply

24VAC/DC

50/60Hz

AC90~250V

50/60Hz

24VAC/DC 50/60Hz

Operating Power Consumption

5W

At end stops Power Consumption

2.5W

Running time

Motor 75S;Spring return 20S

Wire size

10VA

7VA

Weight

1.6Kg

Control signal

On/off

0~10V

Rotation angle

0~90°(max 93º)

Auxiliary switch rating

3(1.5)Amp 250V

Life cycle

70000

Noise level

50dB(A) and 62dB(A)

IP protection

IP54

Ambient Temperature

-20~+50ºC

Ambient Humidity

5~95%RH

Storage temperature

-40~+70ºC

Certificate

CE & UL

72ºC thermal sensor

S6061SF-05DF(S)/24V(yes)

S6061SF-05DF(S)/220V(yes)

S6061SF-05DF/24V  (no)

S6061SF-05DF/220V  (no)

 

Wiring diagram of S6061SF-05Fire Smoke Fire Smoke Damper Actuator

HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper ChinaHVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China

 

 

 

 

Dimension of S6061SF-05Fire Smoke Fire Smoke Damper Actuator

HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China

 

 

72ºC thermal sensor

Including:environment( TS1 )and damper thermal sensor( TS2 );
when the temperature over 72ºC, TS1 will be cut;
when the pipe temperature over 72ºC, TS2 will be cut.

HVAC System Air Regulation Damper Actuators Electric Actuator Frd Fire Resisting Damper China