Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S- 105 -692)

China Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692), Find details about China XLPE Cable, Power Cable from Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)

Model NO.
Triplex 600 V Secondary URD
Range of Application
Distribution
Certification
ISO9001, CCC
Brand
Boan
Manufacture Standard
ANSI/Icea S-105-692
Rated Voltage
600 V
Size
6-500 AWG or Kcmil
Number of Cores
3
Number of Wires
7-37
Trademark
DingAn or OEM
Transport Package
Fumigated Wooden/Steel-Wooden Drum
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544492100
Model NO.
Triplex 600 V Secondary URD
Range of Application
Distribution
Certification
ISO9001, CCC
Brand
Boan
Manufacture Standard
ANSI/Icea S-105-692
Rated Voltage
600 V
Size
6-500 AWG or Kcmil
Number of Cores
3
Number of Wires
7-37
Trademark
DingAn or OEM
Transport Package
Fumigated Wooden/Steel-Wooden Drum
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544492100
Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)
TRIPLEX 6OOV SECONDARY URD

INSULATION: CROSS-LINKED POLYETHYLENE XLP
CONDUCTORS: ALUMINUM

APPLICATION:
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts, in areas with soft soils where rodents are not present.

CONSTRUCTION:
Secondary power distribution up to 600V in areas with soft soils where rodents are not present.

SPECIFICATIONS:
Conductors are stranded, compressed 1350-H16/H26 aluminum insulated with vulcanized interlinked polyethylene. Neutrals are triple yellow extruded stripe. Neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two phase conductors and one neutral or three phase conductors are cabled together to produce the triplex configuration.

Triplex or paralleled 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications.
B-231 Aluminum 1350 Conductors. Concentric-Lay-Stranded
B-609 Aluminum 1350 Round Wire. Annealed and Intermediate Tempers, for Electrical Purposes.
B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation.

Triplex 600 volt secondary UD cable meets or exceeds all applicable requirements of ICEA S-105-692
for cross-linked polyethylene insulated conductors and UL Standard 854 for Type USE-2.
 
Code WordPhase ConductorNeutralDiameterWeight Per 1000 feetAllowable Ampacities+
(mils)
SizeStrand-ingInsul.Thick.SizeStrand-ingInsul.Thick.Single Phase Cond.Complete CableDirect BurialIn Ducts
(AWG)(mils)(AWG)(mils)(lbs.)
TRIPLEXED WITH YELLOW EXTRUDED STRIPE NEUTRAL.
Erskine676067602986441349570
Vassar4760476034574519112590
Stephens27604760403870249165120
Ramapo27602760403870278165120
Brenau1/098027605121106387215160
Bergen1/09801/09805121106441215160
Converse2/0118019805551199478245180
Hunter2/011802/011805551199535245180
Hollins3/017801/09806031302581280205
Rockland3/017803/017806031302651280205
Sweetbriar4/018802/011806581421709315240
Monmouth4/018804/018806581421796315240
Pratt25026953/017807321581853345265
Wesleyan35037954/0188083117951118415320
Holyoke5003795300379598021171545495395
Rider5003795350379598021171598495395