China Jsm Scb10 315kVA Dry Type Transformers Distribution Transformer, Find details about China Dry Type Power Transformer, Electric Transformer from Jsm Scb10 315kVA Dry Type Transformers Distribution Transformer
Technical Data of 35kV SC(B)10 Cast Resin F Insulation Class Dry Type Power Transformer | ||||||||||||||
Loss(kW) | Insulation Level | Weight (kg) | Outline Dimension (mm) | Outline dimension with protective casing | ||||||||||
Rated Capacity | Voltage Group(kV) | Connection Method | (120) | No-load current | (L) | (W) | (H) | (L) | (W) | (H) | ||||
(kVA) | HV | LV | No-load | Load | % | |||||||||
50 | 0.5 | 1.5 | 2.8 | 610 | 1000 | 870 | 1160 | 1700 | 1400 | 1330 | ||||
100 | 0.7 | 2.2 | 2.4 | 915 | 1100 | 870 | 1350 | 1800 | 1400 | 1500 | ||||
160 | 0.88 | 2.96 | 1.8 | 1200 | 1500 | 870 | 1380 | 2200 | 1500 | 1600 | ||||
200 | 0.98 | 3.5 | 1.8 | 1400 | 1530 | 870 | 1420 | 2250 | 1500 | 1650 | ||||
250 | 1.1 | 4 | 1.6 | 1600 | 1550 | 870 | 1450 | 2300 | 1500 | 1700 | ||||
315 | 1.31 | 4.75 | 1.6 | F/F | 1800 | 1580 | 870 | 1550 | 2300 | 1600 | 1800 | |||
400 | Dyn11 | 1.53 | 5.7 | 1.4 | 2200 | 1740 | 870 | 1710 | 2450 | 1600 | 1950 | |||
500 | 35~38.5 | 0.4 | 1.8 | 7 | 1.4 | 2500 | 1740 | 870 | 1900 | 2450 | 1600 | 2100 | ||
630 | Yyn0 | 2.07 | 8.1 | 1.2 | 2900 | 1860 | 870 | 1980 | 2550 | 1700 | 2250 | |||
800 | 2.4 | 9.6 | 1.2 | 3500 | 1860 | 870 | 2180 | 2550 | 1700 | 2400 | ||||
1000 | 2.7 | 11 | 1 | 4200 | 1900 | 1120 | 2265 | 2600 | 1800 | 2500 | ||||
1250 | 3.15 | 13.4 | 0.9 | 4900 | 1950 | 1120 | 2355 | 2650 | 1800 | 2600 | ||||
1600 | 3.6 | 16.3 | 0.9 | 5800 | 2000 | 1120 | 2380 | 2700 | 1800 | 2650 | ||||
2000 | 4.25 | 19.2 | 0.9 | 6600 | 2100 | 1120 | 2480 | 2800 | 1800 | 2700 | ||||
2500 | 4.95 | 23 | 0.9 | 7500 | 2200 | 1120 | 2550 | 2900 | 1800 | 2800 | ||||
(Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz. |