33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer

China 33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer, Find details about China on Load Tap Changer, Tap Changer from 33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer

Model NO.
SYTZZ, SYJZZ
Trademark
HEMG
Specification
11kv 100A, 125A 200A 250A
Origin
China
Model NO.
SYTZZ, SYJZZ
Trademark
HEMG
Specification
11kv 100A, 125A 200A 250A
Origin
China
33KV 250A 50HZ/60HZ AUTO VOLTAGE  REGULATOR FOR POWER AND DISTRIBUTION TRANSFORMER 

33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer


33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer
33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer
33kv 17steps 250A Auto Voltage Regulator for Power and Distribution Transformer


Technical Specification
SYTZZ-33/200-17 is designed and produced according to IEC-60214-1(2003), the main specifications is shown by Table 1.

Table 1 SYTZZ-33/200-17 series OLTC Technical Specification
ModelSYTZZ-33/200-17
 max. through current240
Phase number3
Wiring methodEnd part voltage regulation
Max working position number17
Rated grade voltage600
Insulation
Level
(KA)
Insulation grade33
Max working voltage36
Industrial
test voltage 1min
To earth85
Between phase85
Between max. and min.36
Between neighboring contact36
Shocking test (1.2/50us)200
Shout circuit testThermal stability(3S)4
Dynamic stability10
Mechanical life(10000 times)Not less than 50
Electrical lifeNot less than 5
Tight testWorking pressure3×104 Pa
Test pressure6×104 Pa     24h without leakage
Switch weight (without oil)(kg)130
Oil weight filledAccording to switch height
Drying105+ 5ºC
Controller fittedYK-2










4. The wiring diagram

      
               (a )                                      (b)         
                              
 SYTZZ-33/200-17  

5. Operation Condition
5.1 Service ambient air temperature range of tap changer is -25ºC ~ +40ºC,Relative humidity is less then 85%.
5.2 Service temperature range of the tap changer in oil is -25ºC ~ +100ºC.

5.3 Vertical inclination of OLTC should not be over 2% when it is mounted onto the transformer.

5.4 OLTC should be operated in the place without heavy dusty and any corrosive or explosive gas.

6. Automatic Voltage Regulator
SYTZZ-33/200-17 OLTC is equipped with automatic voltage regulator YK-2. please refer to appendix for YK-2 automatic voltage regulator circuit diagram.



7. Special Design.
Special design will be provided according to the requirements of the customer. The OLTC can be equipped with temperature sensor for cold region application and a manual operation mechanism with DC power supply to YK-2 AVR for position display during installation.