High Voltage Overhead Line Aluminum Conductor Steel Core ACSR Conductor

China High Voltage Overhead Line Aluminum Conductor Steel Core ACSR Conductor, Find details about China Aluminum Alloy Stranded Conductor Aaac, Aaac Conductor from High Voltage Overhead Line Aluminum Conductor Steel Core ACSR Conductor

Model NO.
overhead cable
Trademark
Jin Shui
Transport Package
Iron-Wooden Drum. Iron Drum
Specification
ASTM, DIN. IEC or as request
Origin
Zhengzhou, Hean, China
Model NO.
overhead cable
Trademark
Jin Shui
Transport Package
Iron-Wooden Drum. Iron Drum
Specification
ASTM, DIN. IEC or as request
Origin
Zhengzhou, Hean, China
Bare conductor-----AAC/AAAC/ACSR conductor
AAC, AAAC, ACSR, AACSR&ACAR conductor widely used in power transmission lines with various voltage levels. Since they have such good characteristics as simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity and are also suitable for laying across rivers and valleys where special geographical teatures exist.

1. Specification:
(1) all aluminium conductor (AAC)
(2) all aluminimum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminimum conductor aluminimum clad steel reinforced(ACSR/AW)
(6)rear earth aluminimum conductor steel reinforced(ACSR/RE)
(7)aluminimum conductor aluminimum alloy reinforced(ACAR)

2. Elative manufacturing standards:
1). Standard: IEC61089, BS215 part2, ASTM B232, DIN48204, BS EN50182.
2). Specification: ACSR is composed by bare concentric-lay-stranded galvanized steel wire(s) with aluminum wires surrounded by one or more layers of helically. Greased ACSR can also be supplied.
3). Application: ACSR is widely used in overhead electric power transmission and distribution lines with
Various voltage levels.

All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM
(AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228
(AAAC) Conductor as per ASTM-B-399-1992
(AAAC) Conductor as per BS-3242-1970
(AAAC) Conductor IS: 398-IV-1994
(ACSR) as per ASTM-B-233-1992
(AAC) as per BS-215-1-1970
(AAC) as per IS-398-1: 1976
(AAC) as per ASTM-B-231-1990
(ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992
(ACSR) BS-215-II-1970
(AACSR) as per IEC-1089-1191
AAC(All aluminum conductor) are suited for overhead power line.

We can supply this conductor according to different recognized standards, distribution and transmission lines for distributing power.

Applications:
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

Construction:
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B, or C galvanizing; ""aluminized"" aluminum coated (AZ); Or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the corrosion or infusion of the complete cable with grease.

Specifications:
ACSR bare conductor meets or exceeds the following ASTM specifications:
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341 Aluminum-clad Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AW)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)

Notes:
Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 61.2% IACS for EC (1350) and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer constructions.
Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq. Ft sun, 0.5 coefficients of emissivity and absorption.

Nominal
Alum
mm 2
Number/Diameter
mm
Calculation Area  
mm 2
Approx.
Overall Diameter
mm
 
Max. D. C.
Resistance
At 20  degrees Celsius
≤ Ω /km
 
Nominal breaking load
KN
 
Weight
kg/km
 
Al
 
Steel
 
Al
 
Steel
 
Total
106/1.501/1.5010.621.7712.394.502.7064.1443
206/2.111/2.1120.943.4924.436.331.3687.8885
256/2.361/2.3626.254.3730.627.081.0939.61106
306/2.591/2.5931.615.2736.887.770.907711.45128
356/2.791/2.7936.666.1142.708.370.782213.20149
406/3.001/3.0042.417.0749.489.000.676615.20172
506/3.351/3.3552.888.8261.7010.050.542618.35214
606/3.661/3.6663.1810.5373.7110.980.454521.80255
6012/2.597/2.5963.2736.93100.3012.950.456753.00465
706/3.991/3.9974.8212.4787.2911.970.382525.70302
7012/2.797/2.7973.3742.80116.1713.950.393661.20538
756/4.101/4.1079.2013.2092.4012.300.362227.20320
806/4.221/4.2283.8813.9897.8612.660.341928.80339
906/4.501/4.5095.4015.90111.3013.500.300732.70386
1006/4.721/4.72105.0017.50122.5014.160.273336.00425
1006/4.727/1.57105.0013.50118.5014.150.273332.70394
1007/4.397/1.93105.8020.44126.2014.570.271240.90450
1256/5.287/1.75131.3016.80148.1015.810.218440.70492
12526/2.547/1.91132.1020.10152.2015.890.218746.40522
12518/3.051/3.05130.307.25137.5015.250.218929.80419
12530/2.367/2.36131.1030.60161.7016.520.220258.00602
15030/2.597/2.59158.0036.90194.9018.130.182869.20726
15018/3.351/3.35158.708.80167.5016.570.181535.70506
17530/2.797/2.79183.4042.80226.2019.530.157679.80842
17518/3.611/3.61184.2010.30194.5018.050.156341.10587
20030/3.007/3.00212.0049.50261.5021.000.136392.25974
22530/3.187/3.18238.5055.60294.2022.260.1212109.601095
25030/3.357/3.35264.0061.60325.6023.450.1093111.101213
30030/3.717/3.71324.3075.70400.0025.970.0891135.701489
35030/3.997/3.99374.1087.30461.4027.930.07704155.901718
35054/2.977/2.97373.1048.40421.5026.730.07727118.201411
35054/3.007/3.00381.8049.50431.3027.000.07573120.901444
20018/3.861/3.86210.6011.70222.3019.300.01367046.55671
40030/4.277/4.27429.30100.20529.5029.890.06726178.501971
40054/3.187/3.18428.9055.30484.5028.620.06740131.901621
45030/4.507/4.50477.00111.30588.3031.500.06056198.202190
45054/3.357/3.35475.2061.60536.8030.150.06073145.701797
50054/3.537/3.53528.7068.50597.2031.770.05470161.101999