VV32 /Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable

China VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable, Find details about China Electric Cable, Eletrical Cable from VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable

Model NO.
VV
Wire Core Material
Aluminum
Certification
ISO, CCC, CE, RoHS, UL, VDE
Model
VV
Brand
Yunfeng
Trademark
YUNFENG
Transport Package
Drum
Specification
4X25
Origin
China
HS Code
8544492100
Model NO.
VV
Wire Core Material
Aluminum
Certification
ISO, CCC, CE, RoHS, UL, VDE
Model
VV
Brand
Yunfeng
Trademark
YUNFENG
Transport Package
Drum
Specification
4X25
Origin
China
HS Code
8544492100
Standard
The product is manufactured according to the standard of GB12706 or IEC, BS, DIN and ICEA upon request.
Applications
The product is suitable for use in power distribution lines or fixed installations with rated power-frequncy voltage up to and including 0.6/1kV.
Operating Characteristics
Rated power-frequency voltage U0/U: 0.6/1kV
Max. permissible continuous operating temperature of conductor: 70°C
Max. Short -circuit temperature of the conductor shall not exceed:
(5s maximum duration) Cross-section of conductor ≤ 300mm2--160°C
                   Cross-section of conductor >300m2--160°C
The ambient temperature under installation should not below 0°C
The bending radius of a cable should not be less than 10 times of the cable diameter.

Production Rage of Cable
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableThe Current Carry Capacity of Cable
In Air
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable
The Current Carrying Capacity of Cable
Direct in the ground
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable
In air
  1. The single-core cables are paralle laid, the distance between the cable center is 2 times of the cable diameter for cross-section area of conductor ≤185mm2 and 90mm for cross-section area of conductor ≥240mm2
  2. Ambient air temperature: 40°C
  3. Max. Continous operating temperature of conductor: 70°C

Currentrating factors for variation in ambient air temperature
Ambient air temperature20°C25°C30°C35°C40°C45°C
Rating factor1.291.221.151.081.000.91
Direct in the ground
  1. The single-core cables are installed separtely, the distance between the cable center is 2 time of thecable diameter.
  2. Soil temperature: 25°C
  3. Max. Continous operating temperature of conductor: 70°C
  4. Thermal resistivity of soil: 1.0°C.m/W.
  5. Deoth of laying: 0.7m

Current rating for variation in soil temperature
Ambient air temperature20°C25°C30°C35°C40°C45°C
Rating factor1.041.000.960.960.920.87


Packing
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableOur Workshop
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableOur workshop
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableVV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableVV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableVV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable
Our Projects
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical CableVV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable
Our Partners
VV32/Vlv32 PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable Electrical Cable