China Acurate Current Measurement Signal Conditioner D1 Rogowski Coils′ Secondary Signal Signal Conditioner, Find details about China Rogowski Coil Transducer Multiscale Converter, Flexible CT Integrator Current Clamp from Acurate Current Measurement Signal Conditioner D1 Rogowski Coils′ Secondary Signal Signal Conditioner
Advantage • High read accuracy 0.5% • Easy to install with DIN-RAIL • High bandwidth for measurement 5 to 20kHz • Lower zero drift down to 2mV Related Products Y-FCT,FCT,NRC,MRC | Applications Measuring devices • Power monitoring & analysis • Harmonics and transients monitoring • Welding machine control • High current measurement • PLC control |
Model | D1.1 | D1.2 | D1.3 |
Rated output | 5V AC rms | 4V DC(true-rms) | 4-20mA |
Maximum Output(overload) | 10V AC rms | 4.8V DC | 25mA |
Output Ripple factor | 0.5% | Default 5% (relay to Response time) | |
Response time | ≤1us | Default 100ms(adjustable) | |
Power consumption | 150mW | 200mW | |
Bandwidth | 10Hz to 20kHz | 20-2kHz | |
Rated Input | 100A 600A 1000A 3000A 6000A | ||
Read Accuracy | 0.5% typical at 1%(≥10A) to 200% of rated Current @25ºC | ||
Phase error | ≤0.5° | ||
Linearity | ±0.2% of reading(1% to 200% of range) | ||
Minimum Current measurement | 1A (Ripple 100mA) | ||
Output on 0A (zero drift) | ≤2mV | ||
Temperature drift | 200ppm/ºC | ||
Weight | 60g | ||
Dimension | 90*61*18mm | ||
Power supply | 12V or 24V(best performance on 24V default) | ||
Operating temperature | -20ºC to 70ºC | ||
Storage temperature | -30ºC to 90ºC | ||
Relative humidity: | 80% max.without condensation | ||
Protection degree: | IP20 | ||
Other requirements,please contact us to OEM. |
Coil Model | Coil diameter (mm) | Output ratio and tolerance | Signal cable length |
Code:Y-FCT | Code:200(Typical rated 500A) Code:350(Typical rated 1500A) Code:510(Typical rated 3kA) Code:800(Typical rated 10kA) Y-FCT code is length. | Code:110 110mV/kA@50Hz±5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | Code:-2m Code:-5m Code:-10m Code:-20m |
Code:NRC | Code:100(Typical rated 1kA) Code:150(Typical rated 3kA) Code:200(Typical rated 6kA) | ||
Code:MRC | Code:16(Typical rated 100A) Code:24(Typical rated 300A) Code:36(Typical rated 600A) | Code:60 60mV/kA@50Hz±5% Code:50 50mV/kA@50Hz±0.5% | |
Code:SRC | Code:50 Code:100 Code:150 | Code:360 360mV/kA@50Hz±5% Code:333 333mV/kA@50Hz±0.5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | |
Other requirement could be OEM |
Integrator | Output form | Output value | Rated current | Power supply |
Code:D1 (DIN-RAIL integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -5(5V) | Code: -600A Code: -1kA Code: -3kA Code: -6kA | Code: -12(12V DC) Code: -24(24V DC) |
Code: .3(4-20mA output) | N/A | |||
Code:S9 (mini integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -3(3V) | Code: -12(6-12V DC) Code: -24(24V DC) | |
Code:S1 (high accuracy integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -5(5V) Code: -10(10V) | Code: -12(4-12V DC) Code: -24(24V DC) | |
Code: .3(4-20mA output) | N/A | |||
Code:ATP-01 (1A output three phase integrator) | N/A(0-1A) | N/A | Code: -12(12V DC) Code: -24(24V DC) | |
Code:A01 (1A output integrator) | N/A(0-1A) | N/A | N/A(85-265V AC DC) | |
Code:A05 (5A output integrator) | N/A(0-5A) | N/A | N/A(85-265V AC DC) | |
Code:HF (high frequency integrator) | N/A(0-10VAC peak) | N/A | Code: -1kA(1kA/1V) Code: -10kA(10kA/1V) | N/A(4-12V DC) |
Other requirement could be OEM |