OEM UPS Series

China OEM UPS Series, Find details about China UPS, True on Line UPS from OEM UPS Series

Model NO.
HP9116C Series 6-20KVA
Standby UPS
Sine Wave Output UPS
Output Capacity
Medium Type
Equipment Mode
Centralized Model
Brand
Sorotec
Transfer Time
0ms
Rated Voltage
380VAC 3phase with Ground
Rated Frequency
50/60Hz
Voltagerange
304~478VAC(± 3VAC)
Frequencyrange
50Hz: (46~54Hz); 60Hz: (56Hz~64Hz)
Power Factor
0.98
Voltage Regulation
208/220/230/240X(1± 2%)VAC
Frequency Regulation
50/60Hz± 0.05 Hz
Current Crest Ratio
3"1
Battery DC Voltage
240VDC
Trademark
SOROTEC
Transport Package
Standard Exported Carton and Pallets
Specification
CE; RoHS; ISO9001
Origin
China
HS Code
8504402000
Model NO.
HP9116C Series 6-20KVA
Standby UPS
Sine Wave Output UPS
Output Capacity
Medium Type
Equipment Mode
Centralized Model
Brand
Sorotec
Transfer Time
0ms
Rated Voltage
380VAC 3phase with Ground
Rated Frequency
50/60Hz
Voltagerange
304~478VAC(± 3VAC)
Frequencyrange
50Hz: (46~54Hz); 60Hz: (56Hz~64Hz)
Power Factor
0.98
Voltage Regulation
208/220/230/240X(1± 2%)VAC
Frequency Regulation
50/60Hz± 0.05 Hz
Current Crest Ratio
3"1
Battery DC Voltage
240VDC
Trademark
SOROTEC
Transport Package
Standard Exported Carton and Pallets
Specification
CE; RoHS; ISO9001
Origin
China
HS Code
8504402000
Three Phase UPS Power Supply HP9316C series (10kVA~20kVA)

Key Features:
1)Large Blue Back Light LCD for Detailed Real-Time UPS Status Display
2)High frequency Online UPS and double conversion on-line technology
3)Fully digitized microprocessor control
4)Microprocessor control guarantees high reliability
5)Comprehensive Self-Protection Design
6)Audible Alarm Mute
7)Cold Start Funcition
8)Auto Self-Testing System whileTurning on UPS
9)Wide Input Voltage Range
10)Automatic start & inspect
12)Zero transfer time
13)Advanced battery management
14)Automatic battery charge in UPS off mode
15)Lightning and surge protection
16)Short circuit and overload protection
17)Fan speed auto control when loads varies
18)Optional extension battery pack
19)Maintenance Bypass Switch For 6-20K
20)N+X Parallel Redundancy and Capaacity Expansion For 6-20K

Applications:
Servers, Data-center, critical network devices, Sensitive electronic equipment, Telecom^

Technical Specifications of High Frequency Online UPS HP9316C (10-20K (1pH in/1pH out)
ModelHP9316C 10-20KVA
10KT-XL15KT-XL20KT-XL
Rated Power10KVA/7000W15KVA/10500W20KVA/14000W
Rated Voltage380VAC 3phase with ground
Rated Frequency50/60HZ
Input
VoltageRange304~478VAC(± 3VAC)
FrequencyRange50HZ: (46~54HZ); 60HZ: (56HZ~64HZ)
Power Factor0.98
Output
Voltage Regulation208/220/230/240X(1± 2%)VAC
Frequency Regulation50/60HZ± 0.05 Hz
Power factor0.7
Voltage distortionLinear load< 3%      Non-Linear load< 6%
Overload
Capability
110%~150% for 30s change to bypass model, Recover after load normal
Current Crest Ratio3: 1
Transfer time0ms(AC mode→ Battery mode)
Battery
DC Voltage240VDC
Recharge Current4.2A
Display
LCDDisplay input/output Voltage, Frequency, Battery voltage, Battery capacity, Loading rate.
Communication
InterfaceSmart RS232, SNMP(optional), USB(optional)
Environment
Operation Temperature0~40 º C
Humidity0~95%non-condensing
Storage Temperature-25º C~55º C
Sea level elevation< 1500m
Noise Level(1m)< 55dB
Physical Characteristic
Weight(KG)N. W.475454
G. W.536060
Dimension(D x W x H)mm570X260 X717