China Double Conversion Online UPS DSP Topology for School, Find details about China Double-Conversion UPS, DSP UPS from Double Conversion Online UPS DSP Topology for School
Technical Specification: | |||||||
Index | 33Q 10KL | 33Q 20KL | 33Q 30KL | 33Q 40KL | 33Q 60KL | 33Q 80KL | Comments |
Input | |||||||
Input voltage | |||||||
Rated voltage | 380VAC/220VAC | 380VAC | |||||
Phase | three phase with ground | ||||||
Turn on voltage range | (120±5~274±5)VAC | (207±9~475±9) VAC | |||||
Bypass voltage range | (60±5~300±5)VAC | (105±9~518±9) VAC | Could be adjusted by software. | ||||
Bypass low loss | 60VAC~220VAC(default 60VAC) | 105VAC~380VAC (default 105VAC) | |||||
Bypass low comeback | Low loss +5VAC | Low loss +17VAC | |||||
Bypass high loss | 220VAC~300VAC(default 300VAC) | 380VAC~475VAC (default 475VAC) | |||||
Bypass high comeback | High loss -5VAC | High loss -17VAC | |||||
Line low loss comeback | (120±5) VAC /(140±5) VAC | (207±9) VAC (242±9) VAC | load≤50% | ||||
(140±5) VAC /(160±5) VAC | (242±9) VAC (276±9) VAC | 50%≤90% | |||||
(160±5) VAC /(175±5) VAC | (276±9) VAC (302±9) VAC | load>90% | |||||
Line high loss comeback | (275±5)VAC/(260±5)VAC | (475±9)VAC (449±9)VAC | |||||
Input frequency | |||||||
Rated frequency | 50Hz | ||||||
Frequency low loss | (40~49) ±0.2Hz(default:46Hz) | Could be adjusted by software. | |||||
Frequency low comeback | Frequency low loss +0.5Hz | ||||||
Frequency high loss | (51~60)±0.2Hz(default:54Hz) | ||||||
Frequency high comeback | Frequency high loss -0.5Hz | ||||||
Input power factor | |||||||
Could be adjusted by software. | > 0.99 | 33Q 10-40KL: 220VAC,full R load 33Q 60-80KL: 380VAC,full R load | |||||
Generator | Support generator input | Generator rating ≥2*UPS rating | |||||
Input current | |||||||
Rated current | 14A | 28A | 42A | 67A | 80A | 105A | |
Input THDI | <= 10% | ||||||
Output protection | |||||||
Rating protection | 32A Breaker | 50A Breaker | 60A Breaker | 80A Breaker | 100A Breaker | 125A Breaker | |
Output power | |||||||
VA/watt | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/ 48KW | 80KVA/ 64KW | |
Rated voltage | 220VAC | 380VAC | Sine wave | ||||
Voltage range | 200/208/220 /230/240VAC | 345/359/380 /397/415 VAC | 33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC /200VAC. 33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC /359VAC. | ||||
Voltage regulation | ±1% | ||||||
Voltage distortion | ≤5% | ≤10% | Full RCD load | ||||
≤3% | Full R load | ||||||
DC offset | ≤200mV | ||||||
Transient response | ≤9% | R load 0%~100%~0% | |||||
≤6% | R load 20% ~100%~20% | ||||||
Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | |||||
Bypass output before turn-on | YES | ||||||
Crest ration | 3:1 | ||||||
Output frequency range | |||||||
Normal mode | 1,Same as input frequency(46Hz~54Hz) 2,50Hz(Input frequency>54Hz or Input frequency<46Hz) | ||||||
Battery mode | (50±0.1) Hz | ||||||
Slew rate | 1 Hz/Sec | ||||||
Efficiency | |||||||
Normal mode | > 93% | > 90% | |||||
Battery mode | > 90% | > 90% | |||||
Overload | |||||||
Normal mode battery mode | Overload warning only | 105%±5%≤load | |||||
1min,then transfer to bypass and alarm. | 105%±5%< load≤125%±5% | ||||||
30S,then transfer to bypass and alarm. | 125%±5%< load≤150%±5% | ||||||
300mS, then transfer to bypass and alarm. | load>150%±5% | ||||||
Automatically retransfer | YES | ||||||
Short protection | |||||||
Normal battery mode | YES | ||||||
Transfer time | |||||||
Normal to battery mode | 0mS | ||||||
Battery to normal mode | 0mS | ||||||
Normal to bypass mode | <4mS | 0mS | |||||
Bypass to normal mode | <4mS | 0mS | |||||
Battery and charger | |||||||
Battery | |||||||
Rated voltage | 192VDC | 240VDC | 192VDC*2 | 192VDC*2 | 480VDC | ||
Type/Rating | |||||||
Battery quantity | 16 | 20 | 16*2 | 16*2 | 40 | ||
Backup time | |||||||
Protection | |||||||
Low alarm voltage comeback voltage | (180.8V±4V)/ (188.8V±4V) | (226V±4V)/ (236V±4V) | (180.8V±4V) (188.8V±4V) | (226V±4V)/ (236V±4V) | (452V±4V) (472V±4V) | 33Q 30KL use two | |
Shutdown voltage comeback voltage | 160V±4V/ 168V±4V | (200V±4V)/ (210V±4V) | 160V±4V/ 168V±4V | (200V±4V)/ (210V±4V) | (400V±4V) (420V±4V) | ||
DC protection | |||||||
Overcharge protection comeback voltage | (249.6V±4V) (216V±4V) | (312V±4V) (270V±4V) | (249.6V±4V) (216V±4V) | (312V±4V) (270V±4V) | (624V±4V) (540V±4V) | ||
Leakage current | < 500uA | ||||||
Over discharge protection | 14.5h | Could be set by software | |||||
Battery test | |||||||
Battery weak | YES | ||||||
Battery fault | YES | ||||||
Charger | |||||||
Output voltage | (219.2±3)VDC | (277±3)VDC | (219.2±3)VDC | (277±3)VDC | (554±3)VDC | ||
Charge time | Depends on the external battery capacity | ||||||
Charge current | 7.5A | 6A | 5A | 4A | 10A | ||
Interface | |||||||
Alarm silence | YES | ||||||
DC power turn-on | YES | ||||||
Automatically retransfer | YES | ||||||
Audio alarm | |||||||
Battery mode | Beep/4s | ||||||
Battery low charger fault | Beep/1s | ||||||
UPS fault | Continue beep | ||||||
Overload | Beep/1s | ||||||
Bypass mode | Beep/2Min | ||||||
L/N inverse | Beep/2Min | ||||||
Communication | |||||||
RS232 interface | YES | ||||||
Intelligent slot | YES | ||||||
Monitor software | Appending with UPS | ||||||
Cooling | |||||||
Force air cooling | |||||||
Display | |||||||
LCD/LED displays UPS status | |||||||
Environment | |||||||
Work temperature | 0ºC~40ºC | ||||||
Altitude | <1000m | ||||||
Audible noise | ≤60dB | ||||||
Storage temperature | -15ºC~45ºC | ||||||
Work humidity | 20%~95% | ||||||
Standard | |||||||
EMS | |||||||
ESD | IEC61000-4-2 | Level4 | |||||
RS | IEC61000-4-3 | Level3 | |||||
EFT | IEC61000-4-4 | Level4 | |||||
Surge | IEC61000-4-5 | Level4 | |||||
EMI | |||||||
Conducted | EN55022 | Class A | |||||
Radiated | EN55022 | Class A | |||||
Safety | |||||||
Safety | GB4943-2001/IEC62040-1 | ||||||
Machinery features | |||||||
Size | |||||||
Outline dimension and net weight | |||||||
L*W*H (mm) | 710*260*717 | 840*515*1135 | |||||
Net weight(Kg) | 45/93 | 50/98 | 195 | 208 | |||
Optional functions | |||||||
60Hz | Optional | Set by software | |||||
Converter mode | Optional | Set by software | |||||
ECO | Optional | Optional | Available and set by software | ||||
EPO | Optional | Optional | |||||
LCD display | Optional |