Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)

China Addressable Fire Alarm and Gas Fire Control Panel (Linkage type), Find details about China Fire Extinguisher, Alarm from Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)

Model NO.
JB-QB-LD128EN(M)-AI/JB-QB-LD5502ENI
Trademark
GQ
Transport Package
Standard Export Packing
Specification
GB
Origin
China
Model NO.
JB-QB-LD128EN(M)-AI/JB-QB-LD5502ENI
Trademark
GQ
Transport Package
Standard Export Packing
Specification
GB
Origin
China
Gas Fire Extinguishing Controller/Fire Alarm Panel
Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)
Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)
Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)
Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)
Addressable Fire Alarm and Gas Fire Control Panel (Linkage type)





Features:
Control and indicating equipment
★One detection loop with 64 maximum addressable points.
★Control function for 4 loops addressable passive normal open connectors.
★128*64 LCD for displaying in Chinese and English.
★Convertible between Chinese and English , comform to internationalization.
★Print out in Chinese.
★Black-box function, data storage up to 1000 fire alarm records, 500gas extinguishing records and 500 pieces of relevant information.
★Short circuit protection in the loop an power supply.
★CAN Bus communication interface, work with LD6900 series communication module, as zone CIE to network with other equipment.
★Addressing of field devices randomly.
 
Gas-extinguishing control and indicating equipment
★Multi-line output controlled directly on-scene equipments.
★Delay start(the delay time can be set randomly between 0 and 30 seconds)
★Auto start.
★On-scene emergence start/stop.
★Manual start.
★To stop the start function by manual in the delay start.
★Convert between manual and auto.
★Line fault detection function.
★One group passive normal open output control.
★Digital tube to display the count down in the process of delay time.

Main technology specifications:
ContentTechnical Data
Power supply voltageAC 220V(187V-242V)50Hz
Unload power≤ 4W
Operating temperature0ºC~45ºC
Relative humidity≤ 95%RH(40±2ºC)
Mounting methodWall-mounted
Battery2*12V/7Ah
Max. External dimension428(W)mm×145(D)MM×560(H)mm
Weight11.10kg ± 0.2kg
Control and indicating equipment
Output level to the loopDC14V~24V
Number of loop1
Max. Number of addressable codes64
Max. Output current to the loop200mA
Max. Protection current for short-circuit400mA
Number of output connector4 loops addressable passive normally open connectors
 Gas-extinguishing control and indicating equipment
Quantity of the controlling protective area1
Output voltageDC24V
Max. Output current 1A