M00 72.5KV/145KV PASS PLUG AND SWITCH SYSEM | |||||||||
ITEM | DESCRIPTION | UNIT | 72.5KV | 145KV | |||||
1 | GENERAL SERVICE CONDITIONS | ||||||||
1.01 | Installation type | Indoor/Outdoor | Indoor/Outdoor | ||||||
1.02 | Altitude above sea level | ≤1000M ,Adjuatable to 5000m | ≤1000M,adjustable to 5000m | ||||||
1.03 | Standard | IEC 62271 | IEC62271 | ||||||
1.04 | Extinction medium | SF6 | SF6 | ||||||
1.05 | Maximum ambient air temperature | °C | (+40ºC) | (+40ºC) | |||||
1.06 | Minimum ambient air temperature | °C | (-30ºC) | (-30ºC) | |||||
1.07 | Relative humidity | % | ≤100% day average ,≤95% month average | ≤100% day average ,≤95% month average | |||||
1.08 | Wind pressure (wind speed not more than 34m/s) | Pa | 700 | 700 | |||||
1.09 | Solar radiation according to IEC 894 | W/m2 | <1000 | <1000 | |||||
1.10 | Seismic acceleration according to IEC 1166 | g | >0.5 horizontal,>0.25 vertical | >0.5 horizontal,>0.25 vertical | |||||
1.11 | Degree of protection according to IEC 60529 | IP class | 44 | 44 | |||||
1.12 | Pollution level according to IEC 60815 | IV | IV | ||||||
1.13 | Anti-corrosion of tank | Yes | Yes | ||||||
1.14 | Ice Thickness | mm | 10 | 10 | |||||
2 | Weight of Equipment | ||||||||
2.01 | SBB Module | Kg | 2330 | 2620 | |||||
2.02 | SBB Support frame | Kg | 150 | 150 | |||||
2.03 | SBB Conntrol Panel | Kg | 80 | 80 | |||||
2.04 | SBB SF6 Gas | Kg | 40 | 50 | |||||
2.05 | Total weight of SBB PASS | Kg | 2600 | 2900 | |||||
3 | Surface Finishing | ||||||||
3.01 | Support structure(Hot-dip galvanised according to DIN50976) | um | 85 | 85 | |||||
3.02 | Surface painting | NO | NO | ||||||
4 | Electrical Data | ||||||||
4.01 | Number of poles | 2 | 2 | ||||||
4.02 | Number of phases | 3 | 3 | ||||||
4.03 | Type of execution | Outdoor | Outdoor | ||||||
4.04 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
4.05 | Voltage Characteristics | ||||||||
Nominal voltage of the system | kV | 66 | 132 | ||||||
Maximum equipment voltage | kV | 72.5 | 145 | ||||||
4.06 | Level of insulation | ||||||||
Rated voltage supported at industrial frequency (Ud)(1min) | kV | ||||||||
To ground | kV | 140 | 275 | ||||||
Across the isolating distance | kV | 160 | 315 | ||||||
Assigned voltage supported to the lightning impulse (peak) | |||||||||
to ground | kV | 325 | 650 | ||||||
across the isolating distance | kV | 375 | 750 | ||||||
5 | Bushing | ||||||||
5.01 | BIL exterior of Bushing | kV | 375 | 750 | |||||
5.02 | Interior BIL of Bushing | kV | 325 | 650 | |||||
5.03 | Bushing Materual | Porcelain/Composite | Porcelain/Composite | ||||||
5.04 | Rated voltage | kV | 72.5 | 145 | |||||
5.05 | Rated Current | A | 3150 | 3150 | |||||
5.06 | Rated power frequency withstadn voltage | kV | 140 | 275 | |||||
5.07 | Rated light impulse withstand voltage | kV | 325 | 650 | |||||
5.08 | Maximum dynamic current | kAp | 100 | 100 | |||||
5.09 | Duration of the short-circuit assigned (tk) | s | 4 | 4 | |||||
5.10 | Patial discharge level 46kV | pC | at 46kv ≤5 | at 58kv≤5 | |||||
5.11 | Radi inerference Voltage level | Uv | ≤2500 | ≤2500 | |||||
5.12 | Power frequency withstand voltage (15min) at 100Kpa /20ºC | 46 | 58 | ||||||
5.13 | Arcing distance | mm | 800 | 1452 | |||||
5.14 | Creepage distance | mm | 2250 | 4500 | |||||
5.15 | Forces that act on the concrete bases during the operation | ||||||||
5.16 | a) Vertical | N | 1250 | 1250 | |||||
5.17 | b) Horizontal | N | 750 | 750 | |||||
5.18 | c) transversal | N | 1000 | 1000 | |||||
6 | DIMENSIONS | ||||||||
6.01 | A) hIGH | mm | 3700 | 4500 | |||||
6.02 | b) Wide | mm | 2400 | 4100 | |||||
6.03 | c) Length | mm | 2700 | 2700 | |||||
7 | CIRCUIT BREAKER | ||||||||
7.01 | Standard | IEC 52271-100 | IEC 52271-100 | ||||||
7.02 | Type | three-phase | three-phase | ||||||
7.03 | Extinction medium | Gas | SF6 | SF6 | |||||
7.04 | Number of poles | 3 | 3 | ||||||
7.05 | Number of cameras per pole | 1 | 1 | ||||||
7.06 | Type of installation | Outdoor Hybrid bay | Outdoor Hybrid bay | ||||||
7.07 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
7.08 | Tension characteristics | ||||||||
7.09 | System Voltage | kV | 66 | 132 | |||||
7.10 | Nominal voltage of the equipment | kV | 72.5 | 145 | |||||
7.11 | Rated voltage supported at industrial frequency (Ud) phase-phase, phase-earth and through open switch | kV | 140 | 315 | |||||
7.12 | Assigned voltage supported to the impulse type ray (Up) phase-ground, between phases and through open switch | 325 | 650 | ||||||
7.13 | BIL interior (inner) | kV | 325 | 650 | |||||
7.14 | Current characteristics | ||||||||
7.15 | Rated current in continuous service (Ir) | A | 3150 | 3150 | |||||
7.16 | Rated short-circuit current (Ics) | kA | 40 | 40 | |||||
7.17 | Short circuit current assigned (Ip) | kAp | 100 | 100 | |||||
7.18 | First pole factor | 1.5 | 1.5 | ||||||
7.19 | Rated short-circuit duration (tk) | s | 3 | 3 | |||||
7.20 | Assigned sequence of maneuvers O-0, 3s-CO-3min-CO | yes | yes | ||||||
7.21 | Number of mechanical operations | TIMES | 6000 | 6000 | |||||
7.22 | Pole discrepancy logic | yes | yes | ||||||
7.23 | Anti-pumping device | yes | yes | ||||||
7.24 | CHARACTERISIC FOR TERMINAL FAULT (ACCORD TO IEC62271-100) | ||||||||
7.25 | Short circuit breaking current | KA | 40 | 40 | |||||
7.26 | Short circuit making current | KA | 100 | 100 | |||||
7.27 | Recovery voltage | KV | 63 | 86 | |||||
7.28 | TRV Peak value | KV | 124 | 171 | |||||
7.29 | Rate of rise of recovery voltage (RRRV) | KV/US | 1.47 | 2 | |||||
7.30 | OPENING TIME (AT RATED VOLTAGE) | 32 | 32 | ||||||
7.31 | CLOSING TIME(AT RATED VOLTAGE) | 85 | 85 | ||||||
7.32 | MINIMUM ARCING TIME | MS | 7 | 7 | |||||
7.33 | MINIMUM CLEARING ARCING TIME | MS | 50 | 50 | |||||
7.34 | MAXIMUM BREAK TIME | 60 | 60 | ||||||
7.35 | PEAK CURRENT VALUE RATED TO PEAK VALUE FOR SYMMETRICAL SHORT CIRCUIT CURRENT | PU | 1.21 | 1.21 | |||||
7.36 | DURATION OF MAJOR LOOP | MS | 11.5 | 11.5 | |||||
7.37 | CHARACTERISTIC FOR SHORT LINE FUALT (L90 DUTY CYCLS TO IEC62271-100) | ||||||||
7.38 | Short line fault current | 36 | 36 | ||||||
7.39 | TIME DELAY | 2 | 2 | ||||||
7.40 | TRV SIURCE CHARACTERISTICS | ||||||||
7.41 | TRV PEAK VALUE Uc | 144 | 144 | ||||||
7.42 | Time to reach peak t3 | ||||||||
7.43 | Rated of rise of recovery voltage (RRRV) | 2 | 2 | ||||||
7.44 | CHARACTERITIC FOR OUR OF PHASE MAKING AND BREAKING ACCORDING TO IEC62271-100 | ||||||||
7.45 | Out of phase breaking current | 10 | 10 | ||||||
7.46 | out of phase voltage factor | 2.5 | 2.5 | ||||||
7.47 | CHARACTERISTIC FOR CAPACITIVE CURRENT SWITCHING (LC1 LC2 ACCORDING TO 62271-100) | ||||||||
7.48 | RATED LINE CHARGING BREAKING CURRENT | A | 50 | 50 | |||||
7.49 | RATED CABLE CHARGING BREAKING CURRENT | A | 160 | 160 | |||||
7.50 | VOLTAGE FACTOR K | PU | 2 | 2 | |||||
7.51 | Auxiliary voltage for heating and lighting | V | 220 | 220 | |||||
7.52 | Number of reserve auxiliary contacts | ||||||||
7.53 | a) Opening | 10 | 10 | ||||||
7.54 | b) Closing | 10 | 10 | ||||||
7.55 | Closing and opening devices | ||||||||
7.56 | a) Supply DC voltage assigned (Ua) | Vcc | 110 | 110 | |||||
7.57 | b) Number of opening coils per mechanism | 2 | 2 | ||||||
7.58 | c) Number of closing coils per mechanism | 1 | 1 | ||||||
7.59 | d) Consumption of the closing coil | W | 253 | 253 | |||||
7.60 | e) Consumption of the opening coil | W | 297 | 297 | |||||
7.61 | f) Opening coil voltage range | % | 60-120 | 60-120 | |||||
7.62 | g) Voltage margin of closing coil | % | 85-110 | 85-110 | |||||
7.63 | Operation counter by mechanism | yes | yes | ||||||
7.64 | Data of the operation mechanism | ||||||||
7.65 | a) Type | SPRING | SPRING | ||||||
7.66 | b) Consumption for closing | W | 3000 | 3000 | |||||
7.67 | c) Consumption for opening | W | 1700 | 1700 | |||||
7.68 | d) Voltage margin for normal operation of the mechanism | V | 26.4 | 26.4 | |||||
7.69 | e) Degree of protection in accordance with IEC 60947 - 1 | yes | yes | ||||||
7.70 | f) REMOTE-DISCONNECTED-LOCAL switch | yes | yes | ||||||
7.71 | Alarms and indicators | ||||||||
7.72 | a) Low gas pressure (two states) | yes | yes | ||||||
7.73 | b) Fault in the control device | yes | yes | ||||||
7.74 | c) Pole discordance | yes | yes | ||||||
7.75 | d) Position local / remote status control box | yes | yes | ||||||
7.76 | e) Spring distension | yes | yes | ||||||
7.77 | f) Terminal monitoring trip coils | yes | yes | ||||||
7.78 | Mechanism engine data | ||||||||
7.79 | a) Type | Electric | Electric | ||||||
7.80 | b) Tension | Vcc | 110 | 110 | |||||
7.81 | c) Power | W | 400 | 400 | |||||
7.82 | d) Operation counter yes / no | yes | yes | ||||||
7.83 | e) Excessive operation indication yes / no | no | no | ||||||
7.84 | f) Operating voltage margin | % | 10 | 10 | |||||
7.85 | Nominal motor current | A | 3,5 +/- 1,5 | 3,5 +/- 1,5 | |||||
7.86 | Inrush current | A | 10 +/- 1,5 | 10 +/- 1,5 | |||||
8 | DISCONNECTOR | ||||||||
8.01 | Model | yes | yes | ||||||
8.02 | Standarda | IEC 62271-102 | IEC 62271-102 | ||||||
8.03 | Type of installation | Outdoor | Outdoor | ||||||
8.04 | Type of operation | three phase | three phase | ||||||
8.05 | Number of combined switches | 1 | 1 | ||||||
8.06 | Type of connection disconnector construction | Compressed air | Compressed air | ||||||
8.07 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
8.08 | Tension characteristics | Single pressure | Single pressure | ||||||
8.09 | System Voltage | kV | 66 | 132 | |||||
8.10 | Rated voltage of the equipment | kV | 72.5 | 145 | |||||
8.11 | Assigned voltage supported to the lightning impulse (Up), inside the Hybrid Bay | ||||||||
8.12 | a) On land and between poles | kV | 325 | 650 | |||||
8.13 | b) A través de la distancia de seccionamiento | kV | 375 | 750 | |||||
8.14 | Rated voltage supported at the industrial frequency (Ud) | kV | 72.5 | 145 | |||||
8.15 | a) On land and between poles | kV | 140 | 275 | |||||
8.16 | b) Through the sectioning distance | kV | 160 | 315 | |||||
8.17 | Current characteristics | ||||||||
8.18 | Rated current in continuous service (In) | A | 3150 | 3150 | |||||
8.19 | Rated short-time cutter (Ikh) | kA | 40 | 40 | |||||
8.20 | Duration of the short-circuit assigned (t) | s | 4 | 4 | |||||
8.21 | Peak value of the permissible current (Ip) | kAp | 100 | 100 | |||||
8.22 | Bus transfer current | 2500 | 2500 | ||||||
8.23 | Nominal transfer current of bars | A | 1600 | 1600 | |||||
8.24 | Nominal transfer voltage of bars | V | 30 | 30 | |||||
8.25 | Mechanical operations of the disconnector | 2000 | 2000 | ||||||
8.26 | Class of earthing disconnector | ||||||||
8.27 | Control device | ||||||||
8.28 | a) Operation | yes | yes | ||||||
8.29 | b) Type of operating mechanism | Electric mechanism | Electric mechanism | ||||||
8.30 | c) Manual | yes | yes | ||||||
8.31 | d) Electric (local and remote) | yes | yes | ||||||
8.32 | e) REMOTE-DISCONNECTED-LOCAL selector | yes | yes | ||||||
8.33 | Auxiliary voltage for closing and opening control | ||||||||
8.34 | a) Substation named "CALLALI" | Vcc | 110 | 110 | |||||
8.35 | Auxiliary voltage operating mechanism | ||||||||
8.36 | a) Substation named "CALLALI" | V | 110 | 110 | |||||
8.37 | Number of reserve auxiliary contacts | ||||||||
8.38 | a) Opening of the end of career | 8 | 8 | ||||||
8.39 | b) End of career closing | 8 | 8 | ||||||
8.40 | c) On the move | yes | yes | ||||||
8.41 | Degree of protection of the operating mechanism in accordance with IEC 60947 - 1 | yes | yes | ||||||
9 | CURRENT TRANSFORMER IN BUSHING FOR MEASUREMENT AND PROTECTION | ||||||||
9.01 | Rules | IEC 60044 | IEC 60044 | ||||||
9.02 | Type of installation | Exterior | Exterior | ||||||
9.03 | Kind | Toriodal | Toriodal | ||||||
9.04 | Voltage characteristics | ||||||||
9.05 | System Voltage | kV | 66 | 132 | |||||
9.06 | Nominal voltage of the equipment | kV | 72.5 | 145 | |||||
9.07 | Rated voltage supported at industrial frequency (Ud) | kV | 140 | 275 | |||||
9.08 | Assigned voltage supported to the interior lightning impulse (Up) of the Hybrid Bay | kV | 325 | 650 | |||||
9.09 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
9.10 | Current characteristics | ||||||||
9.11 | Primary current assigned (Ion) | A | 300-600 | 300-600 | |||||
9.12 | Rated secondary current (Isn) | A | 5 | 5 | |||||
9.13 | Rated thermal short-circuit current (Ith) | kA | 40 | 40 | |||||
9.14 | Measure | 0,2 | 0,2 | ||||||
9.15 | Conventional protection | 5P | 5P | ||||||
9.16 | Characteristics cores | ELECTROMAGNETIC | ELECTROMAGNETIC | ||||||
9.17 | a) Allocated transformation ratio | A | 650 | 650 | |||||
9.18 | b) Relationship for which the specification must comply | A | 300-600/5 | 300-600/5 | |||||
9.19 | c) Precision class | 0,2 | 0,2 | ||||||
9.20 | d) Precision loading | VA | 15 | 15 | |||||
9.23 | a) Allocated transformation ratio | A | 300-600/5 | 300-600/5 | |||||
9.24 | b) Relationship for which the specification must comply | A | 300-600/5 | 300-600/5 | |||||
9.25 | c) Precision class | VA | 20 | 20 | |||||
9.26 | d) Precision loading | 5P | 5P | ||||||
9.27 | e) Precision limit factor | 20 | 20 |
| |||||||||
M00 72.5KV/145KV PASS PLUG AND SWITCH SYSEM | |||||||||
ITEM | DESCRIPTION | UNIT | 72.5KV | 145KV | |||||
1 | GENERAL SERVICE CONDITIONS | ||||||||
1.01 | Installation type | Indoor/Outdoor | Indoor/Outdoor | ||||||
1.02 | Altitude above sea level | ≤1000M ,Adjuatable to 5000m | ≤1000M,adjustable to 5000m | ||||||
1.03 | Standard | IEC 62271 | IEC62271 | ||||||
1.04 | Extinction medium | SF6 | SF6 | ||||||
1.05 | Maximum ambient air temperature | °C | (+40ºC) | (+40ºC) | |||||
1.06 | Minimum ambient air temperature | °C | (-30ºC) | (-30ºC) | |||||
1.07 | Relative humidity | % | ≤100% day average ,≤95% month average | ≤100% day average ,≤95% month average | |||||
1.08 | Wind pressure (wind speed not more than 34m/s) | Pa | 700 | 700 | |||||
1.09 | Solar radiation according to IEC 894 | W/m2 | <1000 | <1000 | |||||
1.10 | Seismic acceleration according to IEC 1166 | g | >0.5 horizontal,>0.25 vertical | >0.5 horizontal,>0.25 vertical | |||||
1.11 | Degree of protection according to IEC 60529 | IP class | 44 | 44 | |||||
1.12 | Pollution level according to IEC 60815 | IV | IV | ||||||
1.13 | Anti-corrosion of tank | Yes | Yes | ||||||
1.14 | Ice Thickness | mm | 10 | 10 | |||||
2 | Weight of Equipment | ||||||||
2.01 | SBB Module | Kg | 2330 | 2620 | |||||
2.02 | SBB Support frame | Kg | 150 | 150 | |||||
2.03 | SBB Conntrol Panel | Kg | 80 | 80 | |||||
2.04 | SBB SF6 Gas | Kg | 40 | 50 | |||||
2.05 | Total weight of SBB PASS | Kg | 2600 | 2900 | |||||
3 | Surface Finishing | ||||||||
3.01 | Support structure(Hot-dip galvanised according to DIN50976) | um | 85 | 85 | |||||
3.02 | Surface painting | NO | NO | ||||||
4 | Electrical Data | ||||||||
4.01 | Number of poles | 2 | 2 | ||||||
4.02 | Number of phases | 3 | 3 | ||||||
4.03 | Type of execution | Outdoor | Outdoor | ||||||
4.04 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
4.05 | Voltage Characteristics | ||||||||
Nominal voltage of the system | kV | 66 | 132 | ||||||
Maximum equipment voltage | kV | 72.5 | 145 | ||||||
4.06 | Level of insulation | ||||||||
Rated voltage supported at industrial frequency (Ud)(1min) | kV | ||||||||
To ground | kV | 140 | 275 | ||||||
Across the isolating distance | kV | 160 | 315 | ||||||
Assigned voltage supported to the lightning impulse (peak) | |||||||||
to ground | kV | 325 | 650 | ||||||
across the isolating distance | kV | 375 | 750 | ||||||
5 | Bushing | ||||||||
5.01 | BIL exterior of Bushing | kV | 375 | 750 | |||||
5.02 | Interior BIL of Bushing | kV | 325 | 650 | |||||
5.03 | Bushing Materual | Porcelain/Composite | Porcelain/Composite | ||||||
5.04 | Rated voltage | kV | 72.5 | 145 | |||||
5.05 | Rated Current | A | 3150 | 3150 | |||||
5.06 | Rated power frequency withstadn voltage | kV | 140 | 275 | |||||
5.07 | Rated light impulse withstand voltage | kV | 325 | 650 | |||||
5.08 | Maximum dynamic current | kAp | 100 | 100 | |||||
5.09 | Duration of the short-circuit assigned (tk) | s | 4 | 4 | |||||
5.10 | Patial discharge level 46kV | pC | at 46kv ≤5 | at 58kv≤5 | |||||
5.11 | Radi inerference Voltage level | Uv | ≤2500 | ≤2500 | |||||
5.12 | Power frequency withstand voltage (15min) at 100Kpa /20ºC | 46 | 58 | ||||||
5.13 | Arcing distance | mm | 800 | 1452 | |||||
5.14 | Creepage distance | mm | 2250 | 4500 | |||||
5.15 | Forces that act on the concrete bases during the operation | ||||||||
5.16 | a) Vertical | N | 1250 | 1250 | |||||
5.17 | b) Horizontal | N | 750 | 750 | |||||
5.18 | c) transversal | N | 1000 | 1000 | |||||
6 | DIMENSIONS | ||||||||
6.01 | A) hIGH | mm | 3700 | 4500 | |||||
6.02 | b) Wide | mm | 2400 | 4100 | |||||
6.03 | c) Length | mm | 2700 | 2700 | |||||
7 | CIRCUIT BREAKER | ||||||||
7.01 | Standard | IEC 52271-100 | IEC 52271-100 | ||||||
7.02 | Type | three-phase | three-phase | ||||||
7.03 | Extinction medium | Gas | SF6 | SF6 | |||||
7.04 | Number of poles | 3 | 3 | ||||||
7.05 | Number of cameras per pole | 1 | 1 | ||||||
7.06 | Type of installation | Outdoor Hybrid bay | Outdoor Hybrid bay | ||||||
7.07 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
7.08 | Tension characteristics | ||||||||
7.09 | System Voltage | kV | 66 | 132 | |||||
7.10 | Nominal voltage of the equipment | kV | 72.5 | 145 | |||||
7.11 | Rated voltage supported at industrial frequency (Ud) phase-phase, phase-earth and through open switch | kV | 140 | 315 | |||||
7.12 | Assigned voltage supported to the impulse type ray (Up) phase-ground, between phases and through open switch | 325 | 650 | ||||||
7.13 | BIL interior (inner) | kV | 325 | 650 | |||||
7.14 | Current characteristics | ||||||||
7.15 | Rated current in continuous service (Ir) | A | 3150 | 3150 | |||||
7.16 | Rated short-circuit current (Ics) | kA | 40 | 40 | |||||
7.17 | Short circuit current assigned (Ip) | kAp | 100 | 100 | |||||
7.18 | First pole factor | 1.5 | 1.5 | ||||||
7.19 | Rated short-circuit duration (tk) | s | 3 | 3 | |||||
7.20 | Assigned sequence of maneuvers O-0, 3s-CO-3min-CO | yes | yes | ||||||
7.21 | Number of mechanical operations | TIMES | 6000 | 6000 | |||||
7.22 | Pole discrepancy logic | yes | yes | ||||||
7.23 | Anti-pumping device | yes | yes | ||||||
7.24 | CHARACTERISIC FOR TERMINAL FAULT (ACCORD TO IEC62271-100) | ||||||||
7.25 | Short circuit breaking current | KA | 40 | 40 | |||||
7.26 | Short circuit making current | KA | 100 | 100 | |||||
7.27 | Recovery voltage | KV | 63 | 86 | |||||
7.28 | TRV Peak value | KV | 124 | 171 | |||||
7.29 | Rate of rise of recovery voltage (RRRV) | KV/US | 1.47 | 2 | |||||
7.30 | OPENING TIME (AT RATED VOLTAGE) | 32 | 32 | ||||||
7.31 | CLOSING TIME(AT RATED VOLTAGE) | 85 | 85 | ||||||
7.32 | MINIMUM ARCING TIME | MS | 7 | 7 | |||||
7.33 | MINIMUM CLEARING ARCING TIME | MS | 50 | 50 | |||||
7.34 | MAXIMUM BREAK TIME | 60 | 60 | ||||||
7.35 | PEAK CURRENT VALUE RATED TO PEAK VALUE FOR SYMMETRICAL SHORT CIRCUIT CURRENT | PU | 1.21 | 1.21 | |||||
7.36 | DURATION OF MAJOR LOOP | MS | 11.5 | 11.5 | |||||
7.37 | CHARACTERISTIC FOR SHORT LINE FUALT (L90 DUTY CYCLS TO IEC62271-100) | ||||||||
7.38 | Short line fault current | 36 | 36 | ||||||
7.39 | TIME DELAY | 2 | 2 | ||||||
7.40 | TRV SIURCE CHARACTERISTICS | ||||||||
7.41 | TRV PEAK VALUE Uc | 144 | 144 | ||||||
7.42 | Time to reach peak t3 | ||||||||
7.43 | Rated of rise of recovery voltage (RRRV) | 2 | 2 | ||||||
7.44 | CHARACTERITIC FOR OUR OF PHASE MAKING AND BREAKING ACCORDING TO IEC62271-100 | ||||||||
7.45 | Out of phase breaking current | 10 | 10 | ||||||
7.46 | out of phase voltage factor | 2.5 | 2.5 | ||||||
7.47 | CHARACTERISTIC FOR CAPACITIVE CURRENT SWITCHING (LC1 LC2 ACCORDING TO 62271-100) | ||||||||
7.48 | RATED LINE CHARGING BREAKING CURRENT | A | 50 | 50 | |||||
7.49 | RATED CABLE CHARGING BREAKING CURRENT | A | 160 | 160 | |||||
7.50 | VOLTAGE FACTOR K | PU | 2 | 2 | |||||
7.51 | Auxiliary voltage for heating and lighting | V | 220 | 220 | |||||
7.52 | Number of reserve auxiliary contacts | ||||||||
7.53 | a) Opening | 10 | 10 | ||||||
7.54 | b) Closing | 10 | 10 | ||||||
7.55 | Closing and opening devices | ||||||||
7.56 | a) Supply DC voltage assigned (Ua) | Vcc | 110 | 110 | |||||
7.57 | b) Number of opening coils per mechanism | 2 | 2 | ||||||
7.58 | c) Number of closing coils per mechanism | 1 | 1 | ||||||
7.59 | d) Consumption of the closing coil | W | 253 | 253 | |||||
7.60 | e) Consumption of the opening coil | W | 297 | 297 | |||||
7.61 | f) Opening coil voltage range | % | 60-120 | 60-120 | |||||
7.62 | g) Voltage margin of closing coil | % | 85-110 | 85-110 | |||||
7.63 | Operation counter by mechanism | yes | yes | ||||||
7.64 | Data of the operation mechanism | ||||||||
7.65 | a) Type | SPRING | SPRING | ||||||
7.66 | b) Consumption for closing | W | 3000 | 3000 | |||||
7.67 | c) Consumption for opening | W | 1700 | 1700 | |||||
7.68 | d) Voltage margin for normal operation of the mechanism | V | 26.4 | 26.4 | |||||
7.69 | e) Degree of protection in accordance with IEC 60947 - 1 | yes | yes | ||||||
7.70 | f) REMOTE-DISCONNECTED-LOCAL switch | yes | yes | ||||||
7.71 | Alarms and indicators | ||||||||
7.72 | a) Low gas pressure (two states) | yes | yes | ||||||
7.73 | b) Fault in the control device | yes | yes | ||||||
7.74 | c) Pole discordance | yes | yes | ||||||
7.75 | d) Position local / remote status control box | yes | yes | ||||||
7.76 | e) Spring distension | yes | yes | ||||||
7.77 | f) Terminal monitoring trip coils | yes | yes | ||||||
7.78 | Mechanism engine data | ||||||||
7.79 | a) Type | Electric | Electric | ||||||
7.80 | b) Tension | Vcc | 110 | 110 | |||||
7.81 | c) Power | W | 400 | 400 | |||||
7.82 | d) Operation counter yes / no | yes | yes | ||||||
7.83 | e) Excessive operation indication yes / no | no | no | ||||||
7.84 | f) Operating voltage margin | % | 10 | 10 | |||||
7.85 | Nominal motor current | A | 3,5 +/- 1,5 | 3,5 +/- 1,5 | |||||
7.86 | Inrush current | A | 10 +/- 1,5 | 10 +/- 1,5 | |||||
8 | DISCONNECTOR | ||||||||
8.01 | Model | yes | yes | ||||||
8.02 | Standarda | IEC 62271-102 | IEC 62271-102 | ||||||
8.03 | Type of installation | Outdoor | Outdoor | ||||||
8.04 | Type of operation | three phase | three phase | ||||||
8.05 | Number of combined switches | 1 | 1 | ||||||
8.06 | Type of connection disconnector construction | Compressed air | Compressed air | ||||||
8.07 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
8.08 | Tension characteristics | Single pressure | Single pressure | ||||||
8.09 | System Voltage | kV | 66 | 132 | |||||
8.10 | Rated voltage of the equipment | kV | 72.5 | 145 | |||||
8.11 | Assigned voltage supported to the lightning impulse (Up), inside the Hybrid Bay | ||||||||
8.12 | a) On land and between poles | kV | 325 | 650 | |||||
8.13 | b) A través de la distancia de seccionamiento | kV | 375 | 750 | |||||
8.14 | Rated voltage supported at the industrial frequency (Ud) | kV | 72.5 | 145 | |||||
8.15 | a) On land and between poles | kV | 140 | 275 | |||||
8.16 | b) Through the sectioning distance | kV | 160 | 315 | |||||
8.17 | Current characteristics | ||||||||
8.18 | Rated current in continuous service (In) | A | 3150 | 3150 | |||||
8.19 | Rated short-time cutter (Ikh) | kA | 40 | 40 | |||||
8.20 | Duration of the short-circuit assigned (t) | s | 4 | 4 | |||||
8.21 | Peak value of the permissible current (Ip) | kAp | 100 | 100 | |||||
8.22 | Bus transfer current | 2500 | 2500 | ||||||
8.23 | Nominal transfer current of bars | A | 1600 | 1600 | |||||
8.24 | Nominal transfer voltage of bars | V | 30 | 30 | |||||
8.25 | Mechanical operations of the disconnector | 2000 | 2000 | ||||||
8.26 | Class of earthing disconnector | ||||||||
8.27 | Control device | ||||||||
8.28 | a) Operation | yes | yes | ||||||
8.29 | b) Type of operating mechanism | Electric mechanism | Electric mechanism | ||||||
8.30 | c) Manual | yes | yes | ||||||
8.31 | d) Electric (local and remote) | yes | yes | ||||||
8.32 | e) REMOTE-DISCONNECTED-LOCAL selector | yes | yes | ||||||
8.33 | Auxiliary voltage for closing and opening control | ||||||||
8.34 | a) Substation named "CALLALI" | Vcc | 110 | 110 | |||||
8.35 | Auxiliary voltage operating mechanism | ||||||||
8.36 | a) Substation named "CALLALI" | V | 110 | 110 | |||||
8.37 | Number of reserve auxiliary contacts | ||||||||
8.38 | a) Opening of the end of career | 8 | 8 | ||||||
8.39 | b) End of career closing | 8 | 8 | ||||||
8.40 | c) On the move | yes | yes | ||||||
8.41 | Degree of protection of the operating mechanism in accordance with IEC 60947 - 1 | yes | yes | ||||||
9 | CURRENT TRANSFORMER IN BUSHING FOR MEASUREMENT AND PROTECTION | ||||||||
9.01 | Rules | IEC 60044 | IEC 60044 | ||||||
9.02 | Type of installation | Exterior | Exterior | ||||||
9.03 | Kind | Toriodal | Toriodal | ||||||
9.04 | Voltage characteristics | ||||||||
9.05 | System Voltage | kV | 66 | 132 | |||||
9.06 | Nominal voltage of the equipment | kV | 72.5 | 145 | |||||
9.07 | Rated voltage supported at industrial frequency (Ud) | kV | 140 | 275 | |||||
9.08 | Assigned voltage supported to the interior lightning impulse (Up) of the Hybrid Bay | kV | 325 | 650 | |||||
9.09 | Assigned frequency (fr) | Hz | 50/60 | 50/60 | |||||
9.10 | Current characteristics | ||||||||
9.11 | Primary current assigned (Ion) | A | 300-600 | 300-600 | |||||
9.12 | Rated secondary current (Isn) | A | 5 | 5 | |||||
9.13 | Rated thermal short-circuit current (Ith) | kA | 40 | 40 | |||||
9.14 | Measure | 0,2 | 0,2 | ||||||
9.15 | Conventional protection | 5P | 5P | ||||||
9.16 | Characteristics cores | ELECTROMAGNETIC | ELECTROMAGNETIC | ||||||
9.17 | a) Allocated transformation ratio | A | 650 | 650 | |||||
9.18 | b) Relationship for which the specification must comply | A | 300-600/5 | 300-600/5 | |||||
9.19 | c) Precision class | 0,2 | 0,2 | ||||||
9.20 | d) Precision loading | VA | 15 | 15 | |||||
9.23 | a) Allocated transformation ratio | A | 300-600/5 | 300-600/5 | |||||
9.24 | b) Relationship for which the specification must comply | A | 300-600/5 | 300-600/5 | |||||
9.25 | c) Precision class | VA | 20 | 20 | |||||
9.26 | d) Precision loading | 5P | 5P | ||||||
9.27 | e) Precision limit factor | 20 | 20 |