China 0.6/1kv Four Core Aluminium XLPE Insulated PVC Jacket Underground Power Cables Electrical Wire Coaxial Cable, Find details about China Electric Wire, Electrical from 0.6/1kv Four Core Aluminium XLPE Insulated PVC Jacket Underground Power Cables Electrical Wire Coaxial Cable
In dry, humid and wet locations, cable ducts, outdoors, underground and in Water.
1 ..... solid or stranded bare copper wire
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering
4 ..... concentric conductor of copper wires and copper tape applied helically
5 ..... outer sheath of polyvinylchloride (PVC), black
DIN VDE 0276-627
HD 627 S1:1996 part 1 4H1, 4H2.7H
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)
AWG | NO. OF CORES X NOMINAL CROSS SECTIONAL AREA # X MM² | STRANDED CONDUCTOR TYPE | NOMINAL OVERALL DIAMETER MM | NOMINAL COPPER WEIGHT KG/KM | NOMINAL CABLE WEIGHT KG/KM |
---|---|---|---|---|---|
8 | 2 x 10.0 | re / 10.0 | 19 | 312 | 650 |
6 | 2 x 16.0 | re / 16.0 | 21.5 | 489 | 850 |
4 | 2 x 25.0 | rm / 25.0 | 24.5 | 763 | 1210 |
8 | 3 x 10.0 | re / 10.0 | 19.5 | 408 | 730 |
6 | 3 x 16.0 | re / 16.0 | 22 | 643 | 1000 |
4 | 3 x 25.0 | rm / 16.0 | 26 | 902 | 1550 |
4 | 3 x 25.0 | rm / 25.0 | 26 | 1003 | 1600 |
2 | 3 x 35.0 | sm / 35.0 | 27.5 | 1402 | 1850 |
2 | 3 x 35.0 | sm / 16.0 | 27 | 1190 | 1750 |
1 | 3 x 50.0 | sm / 50.0 | 29.5 | 2000 | 2450 |
1 | 3 x 50.0 | sm / 25.0 | 29 | 1723 | 2250 |
2/0 | 3 x 70.0 | sm / 70.0 | 34 | 2796 | 3350 |
2/0 | 3 x 70.0 | sm / 35.0 | 33 | 2410 | 2950 |
3/0 | 3 x 95.0 | sm / 95.0 | 38.5 | 3791 | 4550 |
3/0 | 3 x 95.0 | sm / 50.0 | 38 | 3296 | 4100 |
4/0 | 3 x 120.0 | sm / 70.0 | 41 | 4236 | 5050 |
4/0 | 3 x 120.0 | sm / 120.0 | 42 | 4786 | 5550 |
300mcm | 3 x 150.0 | sm / 70.0 | 45 | 5100 | 6000 |
300mcm | 3 x 150.0 | sm / 150.0 | 46 | 5970 | 6900 |
350mcm | 3 x 185.0 | sm / 95.0 | 50 | 6383 | 7550 |
350mcm | 3 x 185.0 | sm / 185.0 | 51 | 7363 | 8500 |
500mcm | 3 x 240.0 | sm / 120.0 | 57 | 8242 | 9950 |
8 | 4 x 10.0 | re / 10.0 | 20.5 | 504 | 890 |
6 | 4 x 16.0 | re / 16.0 | 23.5 | 796 | 1250 |
4 | 4 x 25.0 | rm / 16.0 | 28 | 1142 | 1800 |
2 | 4 x 35.0 | sm / 16.0 | 29 | 1526 | 2050 |
1 | 4 x 50.0 | sm / 25.0 | 33 | 2203 | 2700 |
2/0 | 4 x 70.0 | sm / 35.0 | 37 | 3082 | 3750 |
3/0 | 4 x 95.0 | sm / 50.0 | 43.5 | 4208 | 5000 |
4/0 | 4 x 120.0 | sm / 70.0 | 47 | 5388 | 6350 |
300mcm | 4 x 150.0 | sm / 70.0 | 51 | 6540 | 7650 |
350mcm | 4 x 185.0 | sm / 95.0 | 56 | 8159 | 9350 |
500mcm | 4 x 240.0 | sm / 120.0 | 62.5 | 10546 | 11600 |
Nominal voltage Uo/U | [V] | 600 / 1000 volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | one time / fixed | x diameter | 12 |
in motion | x diameter | 15 | |
Flammability | standard | EN 60332-1-2 |