Single Stage RO Reverse Osmosis Controller, pH Orp Controller

China Single Stage RO Reverse Osmosis Controller, pH Orp Controller, Find details about China RO Controller, RO Meter Controller from Single Stage RO Reverse Osmosis Controller, pH Orp Controller

Model NO.
ROC-8221A/CCT-8320, PH-3520/PH-3500
Product Water Conductivity Range
2~200us/Cm
Communication
RS485 (Modbus Protocol)
Protection Level
IP65 (with Back Cover)
Installation
Panel Mounted, Fast Installation
pH
0.00~14.00 pH
Orp
-2000mv~+2000mv
Temp
0.0-99.9 C (Temperature Compensation: Ntc10K)
Buffer Solution
9.18; 6.86; 4.01; 10.00; 7.00; 4.
Trademark
ShowRange
Transport Package
Carton
Specification
130mm*180mm*60mm (H*W*D)
Origin
China
HS Code
9025800000
Model NO.
ROC-8221A/CCT-8320, PH-3520/PH-3500
Product Water Conductivity Range
2~200us/Cm
Communication
RS485 (Modbus Protocol)
Protection Level
IP65 (with Back Cover)
Installation
Panel Mounted, Fast Installation
pH
0.00~14.00 pH
Orp
-2000mv~+2000mv
Temp
0.0-99.9 C (Temperature Compensation: Ntc10K)
Buffer Solution
9.18; 6.86; 4.01; 10.00; 7.00; 4.
Trademark
ShowRange
Transport Package
Carton
Specification
130mm*180mm*60mm (H*W*D)
Origin
China
HS Code
9025800000
ROC-8221A/CCT-8320 Single Stage Double Channels RO Controller
Specification:
ModelROC-8221A/CCT-8320
Signal detection(seven channels)Dry contact inputRaw water tank level:double channelsLow level
High level
Pure water tank level:double channelsLow level
High level
Low pressure protection
High pressure protection
Pretreatment backwash signal
Control port (five channels)Dry contact output 
  Raw water pump
 
SPST-NO; 
Load capacity
: 
AC 220V/3A Max
; 
AC 110V/5A Max

DC 24V/3A Max
lnlet valve
High pressure pump
Flush vavle
Conductivity voerlimit drainge valve
Measure detection pointsRaw water conductivity, product water conductivity, raw water Temp.
Measurement rangeRaw water conductivityMeasurement range5~4000μS /cm
Conductivity Cell constant1.0cm-1
Product water conductivityMeasurement range2~200μS /cm
Conductivity Cell constant1.0cm-1
Medium Temp.0~50ºC
Accuracy1.5%(FS)
CommunicationRS485 communication (Modbus protocol)
Work EnvironmentTemp: 0~50ºC relative humidity:</=85%RH (none condensation)
Storage EnvironmentTemp-20~60ºC;relative humidity</=85%RH (none condensation)
Power supplyDC24V+/-4 V
Protection levelIP65 (with back cover)
Dimensions130mm*180mm*60mm (H*W*D)
Hole size122mm*172mm (H*W)
InstallationPanel mounted,fast installation


PH-3520/PH-3500 pH/ORP Controller
Technical Features:
Measurement Range:
PH: 0.00-14.00
ORP: (-2000-+2000)Mv
Temp.: (0.0-99.9) ºC (Temperature compensation: NTC10K)
Resolution:
Ph: 0.01
ORP: 1mV
Temp.: 0.1ºC
Accuracy:
Ph: 0.1 level

ORP: +/-5Mv (electronic unit)
Temp.: +/-5ºC
Buffer solution: 9.18; 6.86; 4.01; 10.00; 7.00; 4.00
Temp. compensation: (0-50) ºC, (with 25ºC as standard under normal medium), manual and automatic temperature compensation for selection.
Analog output: Single channel isolated (4-20)mA output instrument/transmitter mode for selection.
Control output: double relay output (ON/OFF)
Consumption: <3W
Working environment: Temp. (0-50) ºC; Humidity: </=85%RH (none condensation)
Storage environment: Temp. (-20-60) ºC; Humidity: </=85%RH (none condensation)
Dimension: 96mm*96mm*105mm (H*W*D)
Hole size: 91mm*91mm (H*W)
Installation: Panel mounted, fast installation
Application:
Widely used for online monitoring in environmental water treatment , chemical treatment, circulating cooling water, aquaculture.
Order direction
Basic order units:
PH-3520 pH/ORP Controller: double relay output (ON/OFF)
PH-3500 pH/ORP Controller: power supply DC 24V
Probe length: 10M.
Probe Overall connection: 3/4 inch outer thread.

Remark:
See sensor selection part for correctly choosing sensor and accessories