Items | S1100 E | ||||||
Power Supply | Rated voltage, Frequency | Single phase/Three phase 220V 50/60Hz Single-phase 220V 50/60Hz | |||||
Voltage Range | 220V: 170V~240V; 220V: 170V~240V | ||||||
Output | Voltage Range | 220V: 0~220V; 220V: 0~240V | |||||
Frequency Range | 0.10`400.00Hz | ||||||
Control method | V/F control, Space vector control. | ||||||
Indication | Operating status/Alarm definition/interactive guidance: eg, frequency setting, the output frequency/current, DC bus voltage, the temperature and so on. | ||||||
Control Specifications | Output Frequency Range | 0.10Hz~400.00Hz | |||||
Frequency Setting Resolution | Digital input: 0.01Hz, analog input: 0.1% of maximum output frequency | ||||||
Output Frequency Accuracy | 0.01Hz | ||||||
V/F Control | Setting V/F curve to satisfy various load requirements | ||||||
Torque Control | Auto increase: auto raise torque by loading condition; manual increase; enable to set0.0~20.0% of raising torque | ||||||
Multifunctional Input Terminal | Eight multi-function input terminals, realizing functions including fifteen section speed control, program running, four-section acceleration/deceleration speed switch, UP/DOWN function and emergency stop and other functions | ||||||
Multifunctional Output Terminal | 3 multi-function output terminals for displaying of running, zero speed, counter, external abnormity, program operation and other information and warnings | ||||||
Acceleration/deceleration time Setting | 0~-6000s acceleration/deceleration time can be set individually | ||||||
Other Functions | PID Control | Built-in PID control | |||||
RS485 | Standard RS485 communication function(MODBUS) | ||||||
Frequency Setting | Analog input: 0 to 10V, , 0 to 20mA can be selected; Digital input: Input using the setting dial of the operation panel or RS485 or UP/DOWN | ||||||
Multi-speed | Eight multifunction input terminals, 15section speed can be set | ||||||
Automatic voltage regulation | Automatic voltage regulation function can be selected | ||||||
Counter | Built – in 2group of counters | ||||||
Protection/ Warning Function | Overload | 150%, 60 second(Constant torque); 120%. 60 second (variable torque) | |||||
Over Voltage | Over voltage protection can be set | ||||||
Under Voltage | Under voltage protection can be set | ||||||
Other Protections | Overheat, short circuit, over current, and parameter lock and so on | ||||||
Environment | Ambient Temperature | -10 ° C to 40 ° C (non-freezing) | |||||
Ambient Humidity | Max. 95%(non-condensing) | ||||||
Altitude | Lower than 1000m | ||||||
Vibration | Max. 0.5G | ||||||
Structure | Cooling Mode | Forced air cooling | |||||
Protective Structure | IP20 | ||||||
Installation | Mode | Below 90KW: Wall Mounted; 110~200KW: Wall Mounted or in Cabinet; Above 220KW: in Cabinet |