540W, 54V 10A Water Proof Power Supply, Telecom Power Supply

China 540W, 54V 10A Water Proof Power Supply, Telecom Power Supply, Find details about China 540W, 54V 10A from 540W, 54V 10A Water Proof Power Supply, Telecom Power Supply

Model NO.
GPAD501M54-1A
Trademark
Goldpower
Specification
288mm)217mm*127mm Weight: 4.65Kg
Origin
China
HS Code
8504401400
Model NO.
GPAD501M54-1A
Trademark
Goldpower
Specification
288mm)217mm*127mm Weight: 4.65Kg
Origin
China
HS Code
8504401400

Chapter 1 Introduction

GPAD501M54-1A is a high-duty power supply with AC/DC single-output. Thanks to the latest circuit design, it is compact and of reliable performance. The whole system is of high regulation and high output efficiency, provided with protection against input over/under-voltage, over-current, short circuit, output over-voltage and over-temperature.
The unit is cooled through natural conduction. The system is designed according to the safety regulations, which strictly conforms to the safety standard of information technology.
Features of GPAD501M54-1A:
Class-D lightning protection; IP65 for outdoor application; Cooling through direct conduction at bottom; Metal enclosure; Stop screws provided for the enclosure and cable connectors; Pole/wall mounting.
 

Chapter 2 Technical Specification

2.1. Ambient Requirements

2.1.1 Operation temperature: -40ºC~+65ºC
2.1.2 Relative humidity: 5~95%
2.1.3 Storage temperature: -40ºC~+85ºC
2.1.4 Altitude: ≤4000m
2.1.5 Atmospheric pressure: 70~106KPa
2.1.6 Cooling: natural cooling
 

2.2. Input Properties

 
ItemUnitMinTypicalMaxTesting Condition
Input Voltage Vac150220285 
Start up VoltageVac150 280 
Input FrequencyHz455065 
Input Power Factor 0.95  220Vac±20% Input, rated output
Input Inrush CurrentA  20Cold start up
 

2.3. Output Electrical Properties

 
ItemUnitMinTypicalMax.Testing Condition
Output voltage Vdc-52-54-58 
Output current A 10  
 Voltage regulation   ±2% 
Load regulation   ±1% 
Line regulation   ±1% 
Ripple + noise mV  200 
Output powerW 540  
Output efficiency%88  220V±20% Input, 50%-100% rated output
Temperature coefficient/ºC  ±0.02% 
Soft start timeS  5From start up with rated input voltage till the output voltage achieves the rating
Operating duration @ power downmS10  220VAC Input,  rated output
Transient response overshoot%VO  ±525%~50%~25% or 50%~75%~50% load variation
 
Recovery time for transient responseus  2000.1A/uS
Overshoot and undershoot @start-up/shutdown%VO  ±5 
 

2.4 Protections

 
ItemUnitYES/NOMinTypicalMax.Recovery Property
Input over-voltageVYES300 320Tested at half load
Auto recoverable
Input over-voltage recovery set pointVYES280 300Tested at half load
Recoverable at ≤290VAC
Input under-voltageVYES110 130Tested at half load
Auto recoverable
Input under-voltage recovery set pointV YES130 150Tested at half load
Recoverable at ≥140VAC
Input over current YES    
-54V Output over-voltage protection set pointVYES585960Auto recovery
Output  current-limitingAYES13 16 
Thermal protectionºCYES75  Auto recovery at ambient temperature less than 70ºC
Short circuit protection YES    Long-term short circuit endurable,  Auto recovery
        
 

2.5. Safety and insulation rating

 
ItemRatingStandard(or Testing condition)
SafetyEN60950, UL1950 complianceEN60950, UL1950
Insulation voltage(output-ground)500Vdc500Vdc/1Min / Leakage current30mA
Insulation voltage (input - ground)2121Vdc2121Vdc/1Min / Leakage current30mA
Insulation voltage (input -output)4242Vdc4242Vdc/1Min / Leakage current30mA
Insulation resistance10MΩRH:90%, DC 500V, the insulation resistance of input to output, input to ground, and output to ground is not less than 10MΩ.
Leakage current≤3.5mA300Vac
 

2.6. EMC

ItemRequirementStandard
CECLASS BEN55022
RECLASS BEN55022
HarmonicsCLASS AIEC 61000-3-2[6]
CSLEVEL 3 IEC61000-4-6
(Criterion A)
RSLEVEL 3IEC61000-4-3
(Criterion A)
ESDAt the tangible part of the enclosure under normal operation.(Power on during test)
Contact discharge: +/-6KV
Air discharge: +/-8KV
 
EN61000-4-2
(Criterion B)
At the tangible part of the enclosure under normal operation.(Power off during test)
Contact discharge: +/-8KV
Air discharge: +/-10KV
 
EN61000-4-2
(Criterion R)
Conductor in signal interface:
Contact discharge: +/-2KV (Power on during test)
EN61000-4-2 (Criterion R)
Voltage fluctuationPst≤1.0 ; P1t≤0.65;dc≤3.3%;dmax≤4%;d(t) exceeds 3.3% with duration of 200ms or lessIEC61000-3-3
EFT/BLEVEL 3IEC61000-4-4
(Criterion B)
SURGELEVEL 4EN61000-4-5
(Criterion B)
DIPDip to 70%UT, 40%UT, 0%UT
Duration: 10ms 100ms,5000ms.
IEC61000-4-11
(Criterion C)
 
   
CECLASS B -6dB MarginEN55022
RECLASS B -6dB MarginEN55022
CSTesting frequency: 0.15MHZ-80MHZ; Testing strength: 10V; AM: 80%AM(1KHZ)IEC61000-4-6
RSTesting frequency: 80MHZ-1000MHZ,1.4GHZ-2GHZ; Testing strength: 10V/m;
AM: 80%AM(1KHZ)
IEC61000-4-6
ESDCriterion B (Discharge the enclosure after the same is equipped.)
Contact discharge: ±6kV
Air discharge: ±8Kv

Criterion B (Discharge the enclosure after the same is equipped.)
North America:
Contact discharge:±8kV
Air discharge: ±15kV
IEC 61000-4-2
 EFT/BLEVEL 3  Class-B  (2KV/5Hz)IEC 61000-4-4
SURGEWire-wire: ±2KV
Wire-Ground: ±4KV (Criterion B)
 
IEC 61000-4-5
DIPDip to 70%UT, Duration: 500ms, 0°,45°,90°,135°,180°,225°,270°,315° Criterion C;IEC61000-4-29

2.7. Other requirements

 
ItemRequirementsProperty
Noise<50dB(A)Pass
MTBF100,000HPass
Lightning proofThe AC input should withstand ±5 times for impact of 5KA, lightning impact current waveform of 8/20us with testing interval of 1 Min. Damage free to the power unit.Pass
VibrationFrequency: 5-9 Hz;
Amplitude: 3.5mm, 9~200 Hz
Acceleration: 1.0m/s2  
Axes: 3 Sweep frequency 5 times per axis (3*50 Min) Damage free to the power unit.
Pass
ShockHalf-sine wave, Acceleration: 250m/S2; Pulse width:6ms; Direction: 6; 500 times per directionPass
IP protectionDustproof to some extend; IP65Pass
OdorNo peculiar smell and deleterious gasPass