China Yangtze Power Deep Cycle 6V 180ah Batteries, Find details about China 6V 180ah Batteries, Battery 6V 200ah from Yangtze Power Deep Cycle 6V 180ah Batteries
1. Functional Parameter | 5. Environment Temperature | ||
Nominal Voltage | 6V | Discharge Temperature | -20~60ºC |
Nominal Capacity (10 hour rate) | 180Ah | Charge Temperature | 0~50ºC |
Number of Cells | 3cells | Storage Temperature | -20~60ºC |
2. Rated Capacity at 25ºC (77° F) | 6. Inner Resistance & Max . Discharge Current | ||
20 hour rate (0.1C, 10.8V) | 180Ah | Fully Charged battery at 25ºC (77° F) | 3.4mΩ |
10 hour rate (0.25C, 10.8V) | 160Ah | Max. Discharge Current | 1500A (5s) |
1 hour rate (0.55C, 10.5V) | 100.9Ah | Short Circuit Current | 5000A |
3. Capacity affected by Temperature (10 hour rate) | 7. Self-discharge at 25ºC (77° F) | ||
40ºC (104° F) | 103% | Capacity after 3 month storage | 92% |
25ºC (77° F) | 100% | Capacity after 6 month storage | 84% |
0ºC (32° F) | 85% | Capacity after 9 month storage | 73% |
-15ºC (5° F) | 65% | Capacity after 12 month storage | 65% |
4. Dimension and Weight | 8. Constant voltage charging at 25ºC (77° F) | ||
Length | 306mm | Cyclic use | 7.2~7.45V |
Width | 168mm | Maximum charging current | 25A |
Height | 220mm | Temperature compensation | -30mV/ºC |
Total Height | 222mm | Float use | 6.8~6.9V |
Reference Weight | 27.5kg | Temperature compensation | -20mV/ºC |