China Electric Generator Automatic Voltage Regulator Replacement for Alternator Voltage Stabilizer AVR As440 Diesel Genset Spare Parts, Find details about China Replace AVR, Intelligent Regulator from Electric Generator Automatic Voltage Regulator Replacement for Alternator Voltage Stabilizer AVR As440 Diesel Genset Spare Parts
Sensing Input | Voltage | Jumper selectable 100-130 Vac 1 phase 190-264 Vac 1 phase |
Frequency | 50-60 Hz nominal | |
Power input | Voltage | 100-264 V ac 1 phase |
Frequency | 50-60 Hz nominal | |
Output | Voltage | 82 V d.c. @ 200 V a.c. |
Current | Continuous 4A transient 7.5A for 10 secs | |
Resistance | 15 ohms min (10 ohms min when input Volts is less than 175 ac) | |
Regulation | ± 1.0% | |
Thermal drift | 0.03% per deg. C change in AVR ambient | |
Typical system response | AVR response | 20 ms |
Filed current to 90% | 80 ms | |
Machine Volts to 97% | 300 ms | |
External voltage adjustment | ±-10% with 1kohm 1 watt trimmer Increasing resistance lowers voltage. | |
Uuder frequency protection | Set point | 94 -98% Hz |
Unitpower dissipation | 12 watts maximum | |
Build up voltage | 4 Volts @ AVR terminals | |
Analogue voltage | Maximum input | ±5 Vdc |
Sensitivity | 1V for 5% Generator Volts (adjustable) | |
Input resistance | 1k ohm | |
Quadrature droop input | 10 ohms burden | |
Max. sensitivity: 0.07 A for 5% droop 0PF | ||
Max. input: 0.33 A | ||
Over excitation protection | Set point | 65 V dc |
Time delay | 10-15 seconds (fixed) | |
Environmental | Vibration | 20-100 Hz |
100Hz - 2kHz | ||
50mm/sec | Operating temperature | 40degree under zero to 70 degree |
3.3g | Relative humidity 0-70°C | 95% |
Storage temperature | Storage temperature -55 to +80C |