China Double Conversion Online UPS with Large LCD Display, Find details about China Double Conversion Online UPS, Online UPS from Double Conversion Online UPS with Large LCD Display
MODEL | Q1K | Q1KL | Q2K | Q2KL | Q3K | Q3KL | ||
Rated capacity | 1KVA/800W | 2KVA/1600W | 3KVA/2400W | |||||
Input | Voltage | 115 - 300Vac | ||||||
Frequency | 40-60Hz / 50-70Hz | |||||||
Power factor | 0.99 | |||||||
Output | Voltage | 220/230Vac(1±2%) | ||||||
Frequency | Synchronize with utility power(utility mode); 50 / 60Hz ± 0.2Hz(battery mode) | |||||||
On-load factor | 0.8 | |||||||
Overload rating | 125% overload,1min | |||||||
Battery | Type | Valve-control lead acid maintenance-free battery | ||||||
Back up time | > 11min (half load) | External | > 11min (half load) | External | > 11min (half load) | External | ||
Rated voltage | 36V | 72V | 96V | |||||
Transfer time | 0 | |||||||
Operating environment | Humidity: 20%-90%, Temperature:0oC-40oC | |||||||
Size (WxDxH)mm | 350 x 144 x 229 | 424 x 190 x 328 | 424 x 190 x 328 | |||||
Net Weight(kg) | 11.5 | 5.7 | 22.2 | 10 | 26.3 | 10 |
Queen Star Series Q6K-20Kva | ||||||||
Model | Q6K | Q6KL | Q10K | Q10KL | 31Q10KL | 31Q15KL | 31Q20KL | |
Capacity | 6KVA/4800W | 10KVA/8000W | 15KVA/12KW | 20KVA/16KW | ||||
Input | Nominal Voltage | 220/230/240Vac | 380/400/415Vac | |||||
Voltage Range | 176~276Vac (1P2W+G) | 304~478Vac (3P4W+G) | ||||||
Current | 31A (max) | 50A (max) | 50A (max) | 75A (max) | 100A (max) | |||
Frequency | 46~54Hz/56~64Hz | |||||||
Power Factor | ≥0.99 | |||||||
Output | Voltage | 220/230/240± 2%Vac (1P2W+G) | ||||||
Frequency | 50/60Hz(adjustable) 50/60Hz± 5% (Line mode) 50/60Hz ± 0.05Hz ( Battery mode) | |||||||
Current | 27.3A | 45A | 68A | 91A | ||||
Power Factor | 0.8lag | |||||||
Waveform | Pure Sine Wave | |||||||
Waveform Distortion | Line load <2% | Line load <3% | ||||||
Back-up Time | Full Load | ≥7′ | Depends on external batteries bank's Capacity | ≥5′ | Depends on external batteries bank's Capacity | |||
Half Load | ≥20′ | ≥13′ | ||||||
Battery Nominal Voltage | 192/240Vdc | |||||||
Transfer Time | 0ms | |||||||
Overload Capacity | >105% 1min, >120% 30s transfer to bypass, shut down in 1min | |||||||
Communication | SNMP,RS-232,USB+Intelligent Slot | |||||||
Operating Environment | Temperature | 0C~40ºC | ||||||
Humidity | 15%~90% | |||||||
Dimension | Width (mm) | 260 | 260 | 260 | 260 | 260 | ||
Depth (mm) | 560 | 533 | 560 | 533 | 560 | |||
Height (mm) | 717 | 501 | 717 | 501 | 717 | |||
Net Weight(Kg) | 68 | 18 | 70 | 20 | 28 | 30 | 30 | |
*Specification are subject to change without prior notice |