China Megatro 161kv Transmission Power Tower Bb1, Find details about China 161kv DC Strain Electrical Pylons, 161kv DC Angle Electrical Power Tower from Megatro 161kv Transmission Power Tower Bb1
1 | Line details - Circuit (DC) & KV. | DC, 161 KV | |
2 | Number of phases. | 3 | |
3 | Tower details | Wind span | Weight Span |
Intermediate Angle tower | 450m | 800m | |
Nominal height (m) | 39.9m | ||
4 | Conductors Type ( ACSR/BB1AC/etc) | TERN conductors (2 x 430mm2)) | |
Conductor - Single/twin/quad/hexa | Double | ||
5 | Earth-wire | 6NO. ×48 Core OPGW | |
6 | Wind speed | 95 to 120 km/h | |
7 | Insulators. | 161 KV ball and socket type toughened glass insulators with anchor type | |
8 | Factor of safety. | 1.8 | |
9 | Environmental condition of area (Temp). | Minimum +10oC average +28oC maximum +45oC | |
10 | rainfall | -Annual maximum 1400 mm - Annual minimum 600 mm - Annual mean 1100 mm -Annual mean raindays 78 | |
11 | Angle of Deviation | 20 | |
12 | Tower Height. | 56.1 Mtr. (Subject to approval ) | |
13 | Design Code | The design shall be in accordance with the ASCE standards on design of latticed steel transmission structures ANSI/ASCE 10-97, 1997. In addition due consideration shall be given to ACSE 74, which provides guidelines for the structural loadings of transmission lines. | |
14 | Type of Soil (Normal / Black cotton) | Wet soil |
ITEM | TYPE OF SOIL | Excavation m3 | CONCRETE fc=225 kg/cm2 m3 | REINFORCING STEEL kg | BASE BxBxh cmxcmxcm | COLUMN bxb cmxcm | DEPTH cm |
FOUNDATION TOWER BB1 | |||||||
2.1 | Foundation in Poor Soil | 38.88 | 7.38 | 665.00 | 360x360x50 | 60x60 | 300 |
2.2 | Foundation in Good Soil | 28.67 | 5.95 | 535.00 | 320x320x50 | 60x60 | 280 |
2.3 | Foundation in Unfractured Rock | 23.55 | 5.77 | 520.00 | 320x320x50 | 60x60 | 230 |
2.4 | Foundation in Wet Soil | 122.00 | 17.63 | 1590.00 | 520x520x60 | 60x60 | 450 |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8230-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |