AC Current Sensor 85mv BNC Flexible Rogowski Coil with Power Meter

China AC Current Sensor 85mv BNC Flexible Rogowski Coil with Power Meter, Find details about China Rogowski Coil, Flexible Current Senor from AC Current Sensor 85mv BNC Flexible Rogowski Coil with Power Meter

Model NO.
Y-FCT
IP Rating
IP67
Certification
CE
Customized
Customized
Current Range(RMS)
0-100ka AC
Output Signal(Di/Dt)
85mv/Ka@50Hz,100mv/Ka@50Hz
Accuracy(Typ.)
Calibrated <0.5% (Central Position, 25ºC)
Linearity (10% to 100% of Range)
±0.2% of Reading
Bandwidth (-3dB)
1Hz to 100kHz
Internal Resistance
80 ± 10% Ohms/400mm
Conductor Position Sensitivity
±1% of Reading
Output Sensitivity Tolerance
±2%
Thicker Flexible Rogowski Coil
Thicker Flexible Rogowski Coil
Trademark
Meatrol
Transport Package
Poly Bag for Rogowski Coil, Carton for Poly Bag
Specification
CE
Origin
Shanghai
HS Code
8504311000
Model NO.
Y-FCT
IP Rating
IP67
Certification
CE
Customized
Customized
Current Range(RMS)
0-100ka AC
Output Signal(Di/Dt)
85mv/Ka@50Hz,100mv/Ka@50Hz
Accuracy(Typ.)
Calibrated <0.5% (Central Position, 25ºC)
Linearity (10% to 100% of Range)
±0.2% of Reading
Bandwidth (-3dB)
1Hz to 100kHz
Internal Resistance
80 ± 10% Ohms/400mm
Conductor Position Sensitivity
±1% of Reading
Output Sensitivity Tolerance
±2%
Thicker Flexible Rogowski Coil
Thicker Flexible Rogowski Coil
Trademark
Meatrol
Transport Package
Poly Bag for Rogowski Coil, Carton for Poly Bag
Specification
CE
Origin
Shanghai
HS Code
8504311000
AC Current Sensor 85mv BNC Flexible Rogowski Coil with Power MeterY-FCT
Ø8 Flexible Rogowski coil
  1. High linearity from 1A to 100kA
  2. Wide dynamic range
  3. Very useful with large size or awkward shaped conductors or in places with limited access
  4. No danger from open-circuited secondary
  5. Not damaged by large overloads
  6. Non-intrusive, no power drawn from the main
  1. Measurement uniformity at any position of the conductor inside the coil
  2. Excellent degree of rejection to the external current conductor
Feature
Y-FCT is a flexible current transducer based on Rogowski principle, particularly suitable for measurement in combination with portable devices. Y-FCT coils are available in different sizes and can be supplied according to customer's design, therefore they can be used in all those applications, in which traditional transducers are not fitting due to its size and/or weight.
Due to its specific features, flexible Rogowski coil is an extremely confortable solution for current measurement and can be used in a number of cases where traditional current transducer is not the adequate solution.
Y-FCT coil is provided with a shield against the influence of external magnetic fields, therefore it grants a stable measurement from low currents to hundreds of kA. The Rogowski coils must be connected to an electronic integrator for 90° phase shift compensation and frequency equalization. Our DIN-RAIL and panel meters can interface Rogowski coils directly without the need of the external integrators. This is an advantage because there is no external boxes or any power supply with consequent ease of use. The particular features of the Rogowski coils combined with the extremely flexible input programming of our portable meters, allow to carry out measurement by all applications.

What is a Rogowski coil?
Rogowski coils have been used for the detection and measurement of electric currents for decades. They are based on a simple principle: an "air-cored" coil is placed around the conductor in a toroidal fashion and the magnetic field produced by the current induces a voltage in the coil. The voltage output is proportional to the rate of change of current. This voltage is integrated, thus producing an output proportional to the current.
By using precision winding techniques, especially developed for the purpose, the coils are manufactured so that their output is not influenced by the position of the conductor within the toroid, and to reject interference from external magnetic fields caused, for example, from nearby conductors.Basically, a Rogowski coil current measuring system consists of a combination of a coil and conditioning electronics.Rogowski coil current transducers are used for the AC measurement.
They can be used in similar circumstances to current transformers but for many applications they have considerable advantages:
Wide dynamic range.
High linearity.
Very useful with large size or awkward shaped conductors or in places with limited access. Thanks to the structure without hard core, the coil can be easily manufactured according to the application or to the available space.
Unlike traditional current transducers, there is no danger from open-circuited secondaries.
They cannot be damaged by large overloads.
They are non-intrusive. They draw no power from the main circuit carrying the current to be measured.
They are also light weighted and in some applications are light enough to be suspended on the conductor being measured.

The transducer does not measure direct currents but, unlike a current transformer, it can carry out accurate measurements of AC component even if there is a large superimposed DC component, since there is no iron core causing saturation. This feature is particularly useful for measuring ripple currents for example in battery charging systems.


Specification
 
MODELY-FCT-200Y-FCT-350Y-FCT-510Y-FCT-800
Coil length200mm350mm510mm800mm
Window size50mm100mm150mm240mm
Reference
Rated current
600A1000A3000A6000A
Coil Resistance 140 (+/-10) Ω210 (+/-10) Ω290 (+/-10) Ω430 (+/-10) Ω
Weight140g150g160g180g
RatioCalibrated85mV/kA@50Hz50mV/kA@50Hz
Uncalibrated110mV/kA@50Hz
Read AccuracyCalibrated <0.5% (central position, 25ºC)
     Uncalibrated < 5% tolerance (central position, 25ºC)
Maximum current measurable 100kA
Coil Resistance from 100 to 250 Ω
Coil Section8mm
Lead length2meter
TemperatureUncalibrated  200ppm/C
Calibrated  300ppm/C
Position Error±1% maximum
Output on 0A (zero drift)0.05mV
Phase error≤0.5°
Linearity±0.2% of reading
Bandwidth1Hz to 100kHz(-3dB)
Operating temperature-30ºC to 80ºC
Storage temperature-40ºC to 90ºC
Other requirements, please contact us to OEM.


Materials 
 
Coil & cableThermoplastic rubber
flame retardant UL 94 V-0 rated
CouplingsPA6 UL 94 V-O rated
Color(coil)Black, Yellow, Red, Green, Blue
Shielded100% coil, 100% output cable

Safety
 
Certifications CE marked
Complies with
LVD EN 61010-1:2010
EMC EN 61326-1:2013
IP68
Voltage insulationCoil: 3000V
Signal cable:1000V
Safety1000V CATIII ,600V CATIV


AC Current Sensor 85mv BNC Flexible Rogowski Coil with Power Meter



Dimensions tolerance:
A,B,C,F:±5mm, D:±0.2mm,E:±10mm
Dimensions(mm)Y-FCT-200Y-FCT-350Y-FCT-510Y-FCT-800
A.Windows size A50105155245
B.Windows size B60100150240
C.Coil O.D.66121171261
D.Coil section8
E.Lead Cable Total Length2000
F:Coil length200350510800

Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions,please read these instructions thoroughly!Safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within the limits of the technical specifications.

Caution!Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into operation by qualified personnel that have received an appropriate training,The corresponding national regulations shall be observed during installation and operation of the transducer and any electrical conductor.The transducer shall be used in electric/electronic equipment the respect to applicable standards and safety requirements and in accordance with all the related systems and components manufacturers' operating instructions.

Caution!Risk of electrical shock
When operating the transducer,certain parts of the module may carry hazardous live voltage(e.g.primary conductor).The user shall ensure to take all measures necessary to protect against electrical shock.The transducer is a build-in device containing conducting parts that shall not be accessible after installation.A protective enclosure or additional insulation barrier may be necessary.Installation and maintenance shall be done with the main power supply disconnected except if there are no hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed.

Safe and trouble-free operation of this transducer can only be guaranteed if transport,storage and installation are carried out correctly and operation and maintenance are carried out with care.

WARING!
Do not stress the coil by applying any kind of mechanical force(ie.twisting,puncturing,excessive pressure,tight bending,etc.) which will dramatically degrade the device's accuracy.