China RS485 Electric Current Clamp Rogowski Coil Current Transducer S9.42 Waterproof Flexible CT, Find details about China Rogowski Coil Integrator Current Sensor, Integrator Rogowski Coil Current Transformer from RS485 Electric Current Clamp Rogowski Coil Current Transducer S9.42 Waterproof Flexible CT
Model | S9.42 | |
Output | RS485 interface | |
Amplitude accuracy | ±0.5% rdg.±0.2%f.s. (45Hz~66Hz, Coil vertical center position) | |
Linearity | ±0.2% (10%~100% F.S.) | |
Bandwidth | 30Hz~5kHz | |
Temperature drift | 50ppm/ºC | |
Weight | ≤150g | |
Size | 114mm*42mm*29mm | |
Material | PC | |
Power supply | 5VDC,12VDC,24VDC | |
Power consumption | ≤0.5W | |
Working temperature | -20ºC~70ºC | |
Storage temperature | -30ºC~90ºC | |
Relative humidity | Maximum 80%, no condensation | |
Protection level | IP66 | |
Wiring definition | Red | Power + |
Blue | Power - | |
Green | RS485 port A | |
Yellow | RS485 port B | |
For other requirements, please contact us for customization |
Parameter | Effective value | Default value |
Baud rate | -1200 -2400 -4800 -9600 -19200 | 9600 |
Parity check | - Odd - Even -None | None |
Data bits | 8 | 8 |
Stop bit | 1 | 1 |
Address | 1-247 | 1 |
Slave address | Function code | Command data | CRC check |
8-Bits | 8-Bits | N×8-Bits | 16-Bits |
Coil Model | Coil diameter (mm) | Output ratio and tolerance | Signal cable length |
Code:Y-FCT | Code:200(Typical rated 500A) Code:350(Typical rated 1500A) Code:510(Typical rated 3kA) Code:800(Typical rated 10kA) Y-FCT code is length. | Code:110 110mV/kA@50Hz±5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | Code:-2m Code:-5m Code:-10m Code:-20m |
Code:NRC | Code:100(Typical rated 1kA) Code:150(Typical rated 3kA) Code:200(Typical rated 6kA) | ||
Code:MRC | Code:16(Typical rated 100A) Code:24(Typical rated 300A) Code:36(Typical rated 600A) | Code:60 60mV/kA@50Hz±5% Code:50 50mV/kA@50Hz±0.5% | |
Code:SRC | Code:50 Code:100 Code:150 | Code:360 360mV/kA@50Hz±5% Code:333 333mV/kA@50Hz±0.5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | |
Other requirement could be OEM |
Integrator | Output form | Output value | Rated current | Power supply |
Code:D1 (DIN-RAIL integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -5(5V) | Code: -600A Code: -1kA Code: -3kA Code: -6kA | Code: -12(12V DC) Code: -24(24V DC) |
Code: .3(4-20mA output) | N/A | |||
Code:S9 (mini integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -3(3V) | Code: -12(6-12V DC) Code: -24(24V DC) | |
Code:S1 (high accuracy integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -5(5V) Code: -10(10V) | Code: -12(4-12V DC) Code: -24(24V DC) | |
Code: .3(4-20mA output) | N/A | |||
Code:ATP-01 (1A output three phase integrator) | N/A(0-1A) | N/A | Code: -12(12V DC) Code: -24(24V DC) | |
Code:A01 (1A output integrator) | N/A(0-1A) | N/A | N/A(85-265V AC DC) | |
Code:A05 (5A output integrator) | N/A(0-5A) | N/A | N/A(85-265V AC DC) | |
Code:HF (high frequency integrator) | N/A(0-10VAC peak) | N/A | Code: -1kA(1kA/1V) Code: -10kA(10kA/1V) | N/A(4-12V DC) |
Other requirement could be OEM |