China Eltek Power System Rack Flatpack S 24V/3X2kw, Find details about China DC Power System, Eltek from Eltek Power System Rack Flatpack S 24V/3X2kw
With its flexible alarm and monitoring options combined with bulk output, this 3U system is a superb building block for various industrial applications.
Key features
• The Flatpack S 3U 3x2kW rack has 3 separate DC systems consisting of 2 redundant rectifiers and 1 controller. For flexibility two of these systems can be paralleled to create a system with 4 rectifiers for greater out power or increased redundancy. All rectifiers have separate AC feeding allowing for redundant AC sources for each output.
• A relay output DC okay signal is available for each pair of rectifiers. For increased monitoring and control one Smartpack S controller can be plugged in for each rectifier pair and output.
• In addition to more warning and alarm relay outputs, it provides setup, status and logs through the display or the Ethernet port.
Applications
Offshore, Marine and Process Industry
Applications in these markets demand state of the art, reliable and safe DC power systems. Flatpack S delivers an industry leading power density in its segment, many safety functions, wide operating temperature range and superb reliability in its small housing.
The AC input filters assures compliance to DnV Rules for Classifications of ships, High Speed & Light Craft and DnV Offshore standards.
Product features and advantages
Flatpack S rectifiers
The Flatpack S family will include models covering most applications in terms of output voltage and power, efficiency and special requirements. All rectifiers have intelligent self- protective features like reduced output power at high temperatures or low mains.
Models with increased output overvoltage protection are also available. The Flatpack S 24/1000 SIL3 OVP, has SIL3 on output voltage exceeding 30V. It is capable of handling double fail and has a proof test interval exceeding 15 years.
DC System.
The Flatpack S 3U 3x2kW rack has 3 separate DC systems consisting of 2 redundant rectifiers and 1 controller. For flexibility two of these systems can be paralleled to create a system with 4 rectifiers for greater out power or increased redundancy. All rectifiers have separate AC feeding allowing for redundant AC sources for each output.
A relay output DC okay signal is available for each pair of rectifiers. For increased monitoring and control one Smartpack S controller can be plugged in for each rectifier pair and output. In additions to more warning and alarm relay outputs, it provides setup, status and logs through the display or the Ethernet port.
Flatpack S 3U DC system
Individual feed | Single Phase for each rectifier |
Voltage | 230 VAC/DC nominal, max 300 VAC/DC* |
Maximum Current | 5.9 Arms for each feed* |
Connection | x 2.5mm2 for each rectifier; L + N x M6 cable lug rear; PE |
* For details see datasheet for the applicable rectifier. | |
DC OUTPUT | |
Voltage | 24 Vdc* |
Maximum Current | 3 x 83 A system * |
Connection | 6 x 16/25mm2 (3 x VDC+ and 3 x VDC-) Can be paralleled by links. |
* For details see datasheet for the applicable rectifier. | |
OTHER SPECIFICATIONS | |
# rectifiers | 2 positions for each output (4 if paralleled) |
# controller | 1 positions for each output |
Isolation | 3.0 kVAC - input to output 1.5 kVAC - input to earth 0.5 kVDC - output to earth |
Operating temp. | -40 to +85°C (-40 to +185°F) * |
Storage temp. | -40 to +85°C (-40 to+185°F) |
Mounting | Rear mounted onto a 19" frame or mounting plate (default) Front flush mounted onto a 19" frame (optional, p/n 278626) |
MTBF | > 500, 000 hours Telcordia SR-332 Issue 1, method III (a) (Tambient: 45°C) |
IEC Prot. Cl. | IP20 |
Dimensions | Height: 132.5 mm (3U) Width: 482.6 mm (to fit into 19,,mounting) Depth: 300 mm including rear mounting brackets, 252 mm without brackets. 300 mm depth required in enclosed cabinets for air flow |
Weight | CS0603.000:7.8 kg (17.2 lbs) excluding modules CS0603.001:6.0 kg (13.2 lbs) excluding modules |
* see rectifier datasheet for details on temperature derating | |
CONTROL, MONITORING AND ALARMS | |
Without controller
Connection | Series connected rectifier alarm for each rectifier pair 2 x 1.5mm2; COM, NC (To be loaded with maximum 30V and 100mA) Battery current sense Battery and load fuse sense 2 LVDs 10 x 1.5mm2 |
Temp, input and alarm output connections on controller | |
See rectifier datasheet for details; see Smartpack S datasheet for details | |
APPLICABLE STANDARDS | |
Electrical safety | IEC 60950-l/-3rdedition
UL60950-l/-3rd edition |
EMC | ETSI EN 300 386 V.l.4.1 EN 61000-6-1 (immunity, light industry) EN 61000-6-2 (immunity, industry) EN 61000-6-3 (emission, light industry) EN 61000-6-4 (emission, industry) FCC Part 15 Subpart 109 |
Mains Harmonics | EN 61000-3-2 |
Marine | DNV-OS-D202, Ch.2 Sec. 4 (DNV 2.4) o Temperature CL B o Humidity CL B Vibration CL A EMC CL B*) |
Environment | ETSI EN 300 019-2-1 Class 1.2 ETSI EN 300 019-2-2 Class 2.3 ETSI EN 300 019-2-3 Class 3.2 ETSI EN 300 132-2 RoHS compliant |
*)ClassAforCA0603.001 |