3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA

China 3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA, Find details about China Online UPS, Power Supply from 3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA

Model NO.
3W3
Standby UPS
Sine Wave Output UPS
Output Capacity
Customization
Equipment Mode
Decentralized
Brand
Reros
OEM/ODM
Yes
Power Factor
0.9
Voltage(V)
380/400/415
Cooling Way
Forced Cooling
Trademark
REROS
Transport Package
Carton
Specification
Size: 470*710*115; Weight: 110/222KG
Origin
China
HS Code
85044020
Model NO.
3W3
Standby UPS
Sine Wave Output UPS
Output Capacity
Customization
Equipment Mode
Decentralized
Brand
Reros
OEM/ODM
Yes
Power Factor
0.9
Voltage(V)
380/400/415
Cooling Way
Forced Cooling
Trademark
REROS
Transport Package
Carton
Specification
Size: 470*710*115; Weight: 110/222KG
Origin
China
HS Code
85044020
Features & Application

3W3 10kVA-80kVA

Product Introduction

3W3 10kVA-80kVA series is based on double conversion on-line intelligent UPS, it adopts advanced power factor correction and superior performance of SPWM inverter control technology, key components in redundancy design, with higher input power factor and lower input current harmonic distortion, a new generation of green power supply device has higher performance and output indicators and many functions of innovation design can satisfy the users' needs, is the ideal solution for power supply for large scene, can eliminate all kinds of power grid problems comprehensively. This product is small volume, weight is light, save space for user and at the same time, its excellent quality provide safe and reliable comprehensive protection for the IT room, data center, industrial automation, precision instruments and etc.
 

Main feature

1.Full DSP control technology
2.Output power factor up to 0.9,IGBT rectifier
3.Intelligent SNMP+USB+EPO (optional)
4.RS232/RS485/dry contact communication port
5.ECO fuction
6.Maintenance switch
7.DC cold start function
8.Intelligent fan speed control



Application

1.Data center 
2.IT room
3.Commercial facility
4.Precision instrument
5.Telecom system
6.Rack device 


Specification
Model3W3RX10K
S/L
3W3IX20K
S/L
3W3IX30K
S/L
3W3IX40K 
S/L
3W3IX60K
L
3W3IX80K
L
Capacity10kVA20kVA30kVA40kVA60kVA80kVA
Input features
Input voltage(Vac)380(-45%~+25%),-45%~-20%
Bypass voltage(V)+15%(+20% optional)/-25%
Frequency(HZ)40-70Hz Automatically select synchronization range according to grid frequency
Phase3φ4W+PE
Power Factor≥0.99
Battery voltage(Vdc)240±192
Quantity of battery(Pcs)16-20 can be adjusted28-32 can be adjusted

Battery type

20*7Ah12V
/External

 

32*9Ah 12V
/External

 

32*12Ah 12V
/External

 

32*12Ah 12V
/External

 
External
Output features
Power factor0.9
Voltage(V)380/400/415±1%
Frequency(HZ)Mains normal,Same as input;Mains abnormal,50±0.2%
Transfer Time(ms)0
Efficiency (AC mode @ full loads)>93%>94%
 
N+X in parallel3pcs8pcs
WaveformLinear Load THD<3%;Non Linear Load THD<5%
Overload capacity125% full load keep 10 mins,150% full load keep 60s
Crest factor>3:1
Others
Manual maintenance bypasswith no transfer time bypass maintenance switch
CommunicationRS232/RS485/dry contact(SNMP/USB are optional)
Noise (dB)<58(within 1 meter)
AlarmBattery low-voltage, mains abnormal, overload, UPS fault, over temperature protection
ProtectionInput over-voltage protection, battery under voltage protection, overload protection, short circuit protection, over temperature protection
Cooling wayForced cooling
Working Temperature(ºC)0~40
Humidity0~95%,no condensing
EMCGB7260.2
Size(D×W×H) (mm)250*592*826/576420*643*956470*710*1150796*500*1200
Weight(KG)109/38183/82222/110226/114160180

Note:
Because the products are continuously improved, please contact the company or dealer to inquiry the latest specification.

3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA3 Phase Power Supply High Frequency Pl2 RM Online UPS for 10-80kVA
FAQ                                                                                                 
1)What is your minimum order quantity?
A: For common specification, there is no minimum order quantity, and one piece could also be supplied. The difference is just the price and schedule. If your request is some special, we need to calculate it accordingly.

2)Is OEM/ODM available?
A: Yes, it is! Our products can be Customized. We have 5 senior engineers in our R&D Dept.

3)What is the Terms of Payment?
A: T/T, L/C, D/P, D/A, Western Union, Paypal and MoneyGram (for Small-amount payment).

4)Can you offer Form A or Form E or C/O?
A: Yes, it's no problem, we could apply it from our local government.

5)What's the warranty condition for your UPS?
A: 1 year warranty after the shipment of boarding date, and 1% single phase of UPS amount by free Spare Parts shipped together with each order shipment;