China Indoor Air Insulated Metal Clad Mv Switchgear, Find details about China Switchgear, Metal Clad Switchgear from Indoor Air Insulated Metal Clad Mv Switchgear
Indoor metal-clad withdrawable or without drawable switchgear (hereinafter short as switchgear) is a complete power distribution device for 3.6~33kV, 3 phase AC 50/60Hz, single-bus and single-bus sectionalized system.
It is mainly used for power transmission of middle/small generators in power plants; Power receiving, transmission for substations in power distribution and power system of factories, mines and enterprises, and starting of large high-voltage motor, etc., so as to control, protect and monitor the system.
The switchgear meets IEC298, GB3906-91. In addition to be used with domestic VS1 vacuum circuit breaker, it can also be used with VD4 from ABB, 3AH5 from Siemens domestic ZN65A, and VB2 from GE, etc., it is truly a power distribution device with good performance.
It can also be fitted with isolation truck, PT truck, fuses truck and so on.
In order to meet the requirement for wall mounting and front-end maintenance, the switchgear is equipped with a special current transformer, so that the operator can maintain and inspect it in front of the cubicle.
Standards and Specifications
- IEC60694 The commo n technical requirements of high voltage switchgear and controlgear
- IEC62271-200 A.C. metal enclosed switchgear and controlgear at the rated voltage of 1kV~52k V
- IEC62271-100 High voltage switchgear and controlgear-Part 100:Hi gh voltage A.C. circuit breaker
- GB3906 3.6~ 40.5kV alternating current metal enclosed switchgea r and controlgear
- GB1984 High voltage alternating current circuit breaker
- GB/T11022 The commo n technical requirements of high voltage switchgear and controlgear
- DL/T404 3.6~ 40.5kV alternating current metal enclosed switchgea r and controlgear
Service Environment
a) Ambient temperature: Maximum temperature: +40ºC Minimum temperature: -25ºC
b) Ambient humidity: Daily average RH no more than 95%; Monthly average RH no more than 90%
c) Altitude no higher than 2500m;
d) The air around without any pollution of duty, smoke, ercode or flammable air, steam or salty fog;
Main technical specifications
KYN61-40.5
No. | Item | Unit | Parameters | ||
1 | Rated Voltage | KV | 36 | 40.5 | |
2 | Rated Frequency | Hz | 50/60 | ||
3 | Rated Current | A | 630 1250 1600 2000 2500 3150 | ||
4 | Branch busbar rated current | A | 630 1250 1600 2000 2500 3150 | ||
5 | Main busbar rated current | A | 630 1250 1600 2000 2500 3150 | ||
6 | 1min power frequency withstand voltage | KV | 70 | 95 | |
7 | Lightening impulse withstand voltage | kV | 170 | 185 | |
8 | Rated Short-time Withstand Current (4s) | kA | 20/25/31.5/40 | ||
9 | Rated Short Circuit Breaking Current(Peak) | kA | 40/50/63/80/100 | ||
10 | Protection type | IP4X for housing | |||
11 | Rated voltage for control Circuit | V | DC110, DC220, AC220 |
No. | Item | Unit | Parameter | ||
1 | Rated voltage | KV | 3.6KV, 7.2KV, 12KV, 24KV | ||
2 | Rated frequency | Hz | 50/60 | ||
3 | Rated current | A | 630; 1250; 1600; 2000; 2500; 3150; 4000 | ||
4 | Branch busbar Rated current | A | 630; 1250; 1600; 2000; 2500; 3150; 4000 | ||
5 | Main busbar Rated current | A | 630; 1250; 1600; 2000; 2500; 3150; 4000 | ||
6 | 1 min Power frequency withstand coltage | Wet | KV | 28 | 50/60 |
Dry | KV | 34 | 60/65 | ||
7 | Lighting impulse withstand voltage | KV | 75 | 95/125 | |
8 | Rated short circuit breaking current(peak) | KA | 40/50/63/80/100 | ||
9 | Short time withstand current | KA | 20/25/31.5/40 | ||
10 | Protection type | IP4X for housing |
Mainly Structure
Basic components
a) Busbar compartment
b) Circuit breaker compartment
c) Cable compartment
d) Low-voltage compartment
1 - main device: circuit breaker, contactor,
2 - current transformers,
3 - earthing switch,
4 - voltage transformers,
5 - support-bushing insulators,
6 - bushing insulators
7 - surge arresters,
8 - support insulators (reactance),
9 - main busbars.
10 - connecting (distribution) busbars,
11 - earth-fault current transformer,
12 - earthing conductor,
13 - metal movable particions,
14 - cable ducts (optionally),
15 - vent flaps.