China Vcb & Controller Outdoor High Voltage Vacuum Circuit Breaker, Find details about China PVB, Outdoors from Vcb & Controller Outdoor High Voltage Vacuum Circuit Breaker
WSD-ZW32-24D Outdoor AC high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is a rated voltage of 24 KV, 50 HZ three-phase AC outdoor distribution equipment.The utility model has the advantages of stable and reliable interruption performance, no danger of combustion and explosion, maintenance-free, small size, light weight and long service life.It is mainly used for breaking and closing the load current, overload current and short circuit current in power system.It is suitable for protection and control in power distribution systems of substations and industrial and mining enterprises, and more suitable for rural power grids and frequently operated places.
This product meets GB1984-2003 "High Voltage AC Circuit Breakers" and DL/T402-2007 "Technical Conditions for Order of High Voltage AC Circuit Breakers" and DL/T403-2000 "Technical Conditions for Order of 12 kV~40.5 kV High Voltage Vacuum Circuit Breakers" and other technical standards.
Serial number | Name | Units | Data | |
1 | Rated voltage | kV | 24 | |
2 | Rated current | A | 630 1250 | |
3 | Rated short circuit breaking current | kV | 20 25 | |
4 | Rated short circuit switching current (peak value) | 50 63 | ||
5 | Rated peak tolerable current | 50 63 | ||
6 | icw | 20 25 | ||
7 | Rated short duration | S | 4 | |
8 | 1 min power frequency Withstand voltage | (wet) alternating, ground-to-ground/fracture | kV | 50/65 |
9 | (dry) alternating, ground-to-ground/fracture | 65/79 | ||
10 | Rated operation sequence | Score - 0.3s - Score - 180s - Score | ||
11 | Lightning Shock Tolerance Voltage (Peak) Interphase, Ground to Ground/Fracture | kV | 125/145 | |
12 | Mechanical life | number of times | 10000 | |
13 | Accumulated Allowable Wear Thickness of Dynamic and Static Contacts | mm | 3 | |
14 | Rated Current of Overcurrent Releaser | A | 5 | |
15 | Current Ratio of Current Transformer | 200/5,400/5,600/5,1250/5 | ||
16 | Contact opening | mm | 9±1 | |
17 | Contact overrun | 2±0.5 | ||
18 | Average Switching Speed | m/s | 1.0±0.2 | |
19 | Average closing speed | 0.6±0.3 | ||
20 | Opening time | ms | 23~45 | |
21 | Closing time | 25~45 | ||
22 | Closing bounce time | ≤2 | ||
23 | Synchronization of three-phase dividing and closing | ≤2 | ||
24 | DC Resistance in Each Phase Loop | μΩ | ≤80 | |
Actual scene shooting
1. When ordering, the model, name, quantity and rated value of the product should be specified.
2. Type of switching mechanism (spring or permanent magnet)
3. The user should propose the installation method and select the corresponding fasteners.
4. Users should choose the appropriate functional configuration according to the use requirements.