China Aw-Cfp2166 Asenware Conventional Fire Alarm Control Panel En54, Find details about China Fire Alarm System, Control Panel from Aw-Cfp2166 Asenware Conventional Fire Alarm Control Panel En54
ITEM | 1Zone panel | 2Zone panel | 4-8Zone panel | 4-32 Zone panel |
Mains supply voltage | 110VAC or 240VAC | |||
Internal power supply | 27.2VDC | |||
Total output current limited | 500mA @ 240VAC | 500mA @ 240VAC | 3A @ 240VAC | 3A @ 240VAC |
Main supply monitor for fault | Yes | |||
Battery protection for low voltage | Yes | |||
Number of circuit | 1 | 2 | 4-16 | 4-32 |
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Line fault monitor for detector | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,grey, red, gold) |