3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter

China 3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter, Find details about China 3 Phase Power Meter, Modbus TCP Power Meter from 3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter

Model NO.
APM800
Measured Signal
Pulse Peak
Type
Power Meter
Certification
CE
Customized
Customized
Acurracy
0.5s Class
Input Current
5A or 1A by Cts
Input Voltage
AC 100V/110V/400V/690V
Power Range
0-999999.99kwh
Frequency
45-65Hz
Communication
RS485 Modbus RTU
Optional Communication
Modbus TCP Ethernet or Profibus-Dp
Certificate
CE
Warranty
2 Years
Trademark
ACREL
Transport Package
Paper Carton
Specification
96*96mm
Origin
Jiangsu, China
HS Code
9028301400
Model NO.
APM800
Measured Signal
Pulse Peak
Type
Power Meter
Certification
CE
Customized
Customized
Acurracy
0.5s Class
Input Current
5A or 1A by Cts
Input Voltage
AC 100V/110V/400V/690V
Power Range
0-999999.99kwh
Frequency
45-65Hz
Communication
RS485 Modbus RTU
Optional Communication
Modbus TCP Ethernet or Profibus-Dp
Certificate
CE
Warranty
2 Years
Trademark
ACREL
Transport Package
Paper Carton
Specification
96*96mm
Origin
Jiangsu, China
HS Code
9028301400
Product Description

0.5s accuracy 3 phase ethernet modbus tcp power quality analysis energy meter

 multifunction energy analyzer CE approval APM series is a high performance panel meter, used not only in the electricity transmission and power

distribution system, but also in the power consumption measurement and analysis in high voltage smart power grid up to 690V or PT connection.

It supports 1p2w, 3p4w and 3p3w supplies, including voltage, frequency, current, power and active and reactive energy, imported or exported,

Harmonic, Power factor, Max. Demand etc. Energy is measured in terms of kWh, kVArh and kVAh. Maximum demand current can be measured

over preset periods of up to 30minutes.

Built-in interfaces RS485 Modbus RTU and Optional Ethernet TCP/IP or profibus-DP communication. Digital input and outputs are provided for

external signal counting and external device control.  66 alarm types can be set,each type can record up to 16 alarm records.

 

Functions and parameters

Main Functions of APM800 high performance power meter 

  • Accuracy: Voltage,current and power:class 0.5s  Active power:class 0.5s
     

  • Rated voltage:AC 3*57.7/100V,AC 3*63.5/110V,AC 3*230/400V or AC 3*400/690V
     

  • Rated current:AC 5A or 1A by CTs,support 2.5mm2 line access
     

  • THD & 63st Harmonic analysis with bar chart display
     

  • 66 alarm types and external (SOE) each has 16 SOE,support SD card extend  record
     

  • 2 DI +2 DO (standard)
     

  • RS485 Modbus-RTU
     

  • Optional functions:
     

    Multi-tariff energy(F)

    8DI+2DO(MD82)

    TF card(MLOG)

    8AI+4AO(MA84)

    Ethernet(MCE)

    Profibus-DP(MCP)

Data sheet
Technical data
Input Grid net1p2w, 3p4w or 3p3w
Frequency45~65HZ
Voltagerated valueAC100V 110V 400V 690V
power consumption<0.5VA(every channel)
Currentrated valueAC 1A,5A,4mm2 wire can be connected
power consumption<0.5VA(every channel)
Accuracy0.5s
Digital inputdry contact input,inner power supply
Relay outputcontact type:main body normal open,module changeover contact;   contact capacity:AC250V/3A DC30V/3A                                                        
Impulse outputoutput type optcoupler impulse
Analog outputDC 0~20mA,4~20mA,0~5V,1~5V 
Analog inputDC 0~20mA,4~20mA,0~5V,1~5V 
CommunicationRS485 Modbus RS485 RTU communication and DLT645 protocol;                                                                   
RS232/Profibus-DP protocol; 
RJ45(Ethernet)/Modbus-TCP,http and DHCP protocol...
Power supplyAC85V~265VDC 100V~350V or AC100~415VDC 125V~500V
Basic functions
three phase(I,U,kW,kvar,kWh,kvarh,Hz,cosφ),zero-sequence current In;
Four quadrant electric energy;real-time and max demand;last month and this month extreme value;
voltage unbanlanceness degree ;load current columnar display;
66 alarm types and external (SOE) each has 16 SOE,support SD card extend  record;
2-63st harmonics;2DI+2DO RS485/Modbus;LCD display
Optional Function
1Multi-tariff(F)
28DI+2DO(MD82)
3TF card(MLOG)
48AI+4AO(MA84)
5second channel RS485(MCM)
6Ethernet(MCE)
Remark:APM800 standard model is with 1*RS485 

Dimensions and Wirings

3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter
About ACREL

ACREL is a professional manufacturer with over 18 years experience in energy meters
3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter3 Phase Ethernet Modbus TCP Power Quality Analysis Energy Meter
3 Phase Ethernet Modbus TCP Power Quality Analysis Energy MeterFAQ


Q:Where is your company located?
 
A:Our headquarter is in Shanghai, our factory locates in Jiangyin,Jiangsu Province,China.It takes about 1 hour by car from Shanghai Hongqiao International Airport to our factory. As it is low labor cost here in Jiangsu,we can offer a better price with high quality.

 
A:Our headquarter is in Shanghai, our factory locates in Jiangyin,Jiangsu Province,China.It takes about 1 hour by car from Shanghai Hongqiao International Airport to our factory. As it is low labor cost here in Jiangsu,we can offer a better price with high quality.
 
Q:What's your lead time?
 
A:Sample time 1-3days,mass production 10~20days for order more than 500pcs
 
Q:Payment terms?
 
A:Usually,TT,credit card,western union,in cash and so on.You can also choose to pay 30% as deposit and the balance before shipment or against copy of B/L if the order is large.
 
Q:Can other logo be put on your products(ODM)?

A:Yes,but MOQ for ODM will be at least 5pcs.We also need you provide logo Ai Format or EPS.