China High Quality 240V AC to DC 75W Access Home Control Power Supply 24V DIN Rail Mount Power Supply, Find details about China Power Supply, Swtching Power Supply from High Quality 240V AC to DC 75W Access Home Control Power Supply 24V DIN Rail Mount Power Supply
SPECIFICATIONS | |||
OUTPUT | |||
Model | DR-75-12 | DR-75-24 | DR-75-48 |
DC Voltage | 12V | 24V | 48V |
Rated Current | 6.3A | 3.2A | 1.6A |
Current Range | 0-6.3A | 0-3.2A | 0-1.6A |
Rated Power | 75.6W | 76.8W | 76.8W |
Ripple & Noise | 100mVp-p | 150mVp-p | 240mVp-p |
Voltage Adj. Range | 12-14V | 24-28V | 48-53V |
Voltage Tolerance | ±2% | ±1% | ±1% |
Line regulation | ±1% | ±1% | ±1% |
Load regulation | ±1% | ±1% | ±1% |
Setup, Rise Time | 1000ms,60ms/230VAC 1800ms,60ms/115VAC at full load | ||
Hold Up Time | 60ms/230VAC 12ms/115VAC at full load | ||
INPUT | |||
Voltage Range | 85~264VAC 47~63 Hz; 120~370VDC | ||
AC Current | 1.6A/115V 0.96A/230V | ||
Efficiency | 76% | 80% | 81% |
Inrush Current | Cold start 20A/115VAC 40A/230VAC | ||
Leakage Current | <1mA/240VAC | ||
PROTECTION | |||
Over Load | 105%~150% rated output power | ||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | |||
Over Voltage | 15-16.5V | 29-34V | 58-65V |
Protection type: Shut down o/p voltage, re-power on to recover | |||
Over Temp. | 85ºC±5ºC (TSW1) detect on heat sink of power transistor | ||
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down | |||
ENVIRONMENT | |||
Working Temp., Humidity | -10ºC~+60ºC; 20%~90% RH non-condensing | ||
Storage Temp., Humidity | -20ºC~+85ºC; 10%~95%RH | ||
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes | ||
SAFETY | |||
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | ||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/25ºC/70%RH | ||
STANDARD | |||
Safety Standard | Design refer to UL508,TUV EN60950-1 | ||
EMC Standard | EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2, heavy industry level, criteria A | ||
OTHERS | |||
Dimension | 55.5*125.2*100mm(L*W*H) | ||
Weight | 0.6Kg | ||
Packing | 20pcs/13Kg/1.29CUFT | ||
NOTE | |||
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |