China H-Class SHS Epoxy Prepreg for Dry Type Transformer, Find details about China Class H SHS for Dry Transformers, Class H SHS Prepreg from H-Class SHS Epoxy Prepreg for Dry Type Transformer
No. | Performance | Unit | Requirements | |||||||||
1 | Nominal thickness | mm | 0.13 | 0.15 | 0.18 | 0.20 | 0.25 | 0.30 | ||||
2 | Deviation of thickness | mm | ±0.02 | ±0.02 | ±0.03 | ±0.03 | ±0.035 | ±0.035 | ||||
3 | Deviation of width | mm | ≤60:±0.2 >60≤1000:±0.8 >1000:±1.0 | |||||||||
4 | Tensile strength Lengthways no bending | N/10mm | ≥40 | ≥50 | ≥70 | ≥70 | ≥80 | ≥100 | ||||
5 | Volatile content | % | ≤1.5 | |||||||||
6 | Soluble resin content | g/ | 30±10 | 35±10 | ≥45 | |||||||
7 | Breakdown voltage | kV | ≥4.5 | ≥5 | ≥6 | ≥6 | ≥8 | ≥9 | ||||
8 | Tensile shear strength | MPa | ≥3.0 | |||||||||
9 | Temperature exponent | - | ≥180 | |||||||||
Remark: Other specification of products or users have special requirements, supply can be negotiated according to the user's needs. Supply width: 10mm~1280mm; |
Curing temperature | Time |
80ºC→120ºC/120ºC | 0.5h/1h~2h |
120ºC→160ºC/160ºC | 0.5h~1h/4h~8h |
160ºC→120ºC/120ºC | 1h/1h~2h |
120ºC→80ºC/80ºC | 0.5h/1h |
Remarks: Due to diversity of production and application of each transformer plant, the above data can be adjusted according to the actual situation of the manufacturer and the size of the workpiece. |