China 21/30 Engine Driven Generator, Find details about China Generator, Engine from 21/30 Engine Driven Generator
Main Specification:
Generator Model | 600GF | 800GF | 1000GF | 1250GF | 1350GF |
Rated Electrical Power (kW) | 600 | 800 | 1000 | 1250 | 1350 |
Engine Model | N6210ZD4 | N6210ZD18 | N8210ZD | N8210ZD4 | N8210ZD24 |
Bore x Stroke (mm) | 210x300 | ||||
Engine Type | 4-Stroke, Inline, Direct Injection,Tubocharged, Intercooled | ||||
Engine Capacity (kW) | 662 | 882 | 1103 | 1471 | 1471 |
Engine Rev. (rpm) | 50Hz@750 | 50Hz@1000 | 50Hz@1000 | 50Hz@1000 | 50Hz@1000 |
60Hz@720 | 60Hz@900 | 60Hz@900 | 60Hz@900 | 60Hz@900 | |
Fuel Consumption (L/h) | 154.3 | 207.6 | 261.9 | 327.4 | 353.6 |
Note: All engine rating data based on ISO 3046/1;
Reference conditions: Ambient temperature 25ºC, Total Barometric Pressure 100kPa, Relative humidity 30%, Intercooler coolant inlet temperature 25 ºC;
Fuel characteristics: Related density: 0.84±0.005, Lower heat value:42700kj/kg, Consumption tolerance: +5%;
Power: An overload of 10% is permitted for one hour in every twelve hours of operation.
Characteristics:
Meet with: ISO8528, IEC60034, ISO3046;
Marine medium speed engine driven, modular construction, HFO burning;
Brushless self excited alternator with AVR;
Application: Marine AUX,Land (EPS) power,Containerized power.
Low noise, long TBO, low operating cost.
Electrical Performance
Voltage | Voltage no load adjustment range | % | 95~105 |
Voltage fluctuation rate | % | ±1 | |
Stable voltage regulating rate | % | ±2.5 | |
Transient voltage regulating rate | % | ±20~-15 | |
Stabilizing time | s | 1 | |
Alternator Excitation method |
| Brushless AVR | |
Frequency | Stable frequency (rev.) regulating rate | % | 5 |
Frequency (rev.) fluctuation rate | % | ±0.5 | |
Transient frequency regulating rate | % | ±10 | |
Stabilizing time | s | < 5 | |
Frequency regulating method |
| Auto / Manual |
Protection | Over speed | 115% Nr A, T, S | Reverse P. | -9.6% Pn A, T |
LO. P | 0.25MPa A, 0.15MPa T,S | Over current | 130% In A, T | |
FW T. | 90ºC A, 95ºC T,S | Over voltage | 120% V A, T | |
LO. T | 90ºC A | Over load | 110% In A |