China CCS, Chademo, Type2 Fast Charging Station EV Charger 80kw, Find details about China EV Charger, Charger from CCS, Chademo, Type2 Fast Charging Station EV Charger 80kw
150kW(CCS2) |
CCS 2 - Dual Connector DC EVSE |
Conductive |
Mode 4 |
Modularity, self-diagnostic features, fault codes and easy serviceability in the field |
Regulated DC EV charging station with combination of CVC or CCC but not simultaneously |
Each output isolated from each other with proper Insulation Input/ Output/ Ground: Supplier to confirm Control Circuit/ Ground: Supplier to confirm |
Class 1 Equipment |
DC EV charging station connected to AC mains |
Communicate by Digital & Analog Signals |
Inter-operable with any EV supporting CCS2 (non- dedicated,can be used by any consumer) |
Yes - Hot Swappable |
Easily Operable by a trained person or end user |
10 °C with respect to Ambient |
Reqd. for Better operation integrated with controller |
Reqd. for system safety integrated with controller |
Reqd. for safety of end user from high power during operation as well better performace of fitted switch gear and components |
3-Phase, 5 Wire AC system (3Ph+N+E) |
3Ø, 415V (+6% and -10%) as per IS 12360 |
50Hz, ±1.5Hz |
Battery backup for minimum 6 hour for control system and billing unit, to enable activities such as billing, to be provided. To get in ideal condition for both EV and EVSE. |
2 ( CCS 2 + CCS 2 ) as per IEC62196 Standard |
Phoenix Contact |
Supplier to provide & confirm |
200 - 1000 VDC as per IEC61851 Standard |
0 - 200 Amp as per IEC61851 Standard |
≥ 95 % at nominal output power |
≥ 0.99 (Full load) |
30mA RCD + 6mA DC Protection.The charger should have an insulation monitoring function. When the charging gun interface is connected, the charger should be responsible for the insulation monitoring inside the charger (including the charging cable) before charging starts. An alarm should be created when the insulation resistance is between 100Ω/V and 1000 Ω/V. When the insulation resistance is ≥100Ω/V, alarm and stop charging |
CCS - IEC 61851-23 / -24, IEC 62196-3, DIN 70121 |
SPD Protection, AC Input Over Voltage, Over current, AC Input under voltage, DC Output Over Voltage, DC Output Under Voltage, Residual current, Short circuit retraction, Earth fault at input and output, Input phase reversal, Battery Anti-reverse, Current Anti-reverse, Emergency shutdown with alarm, Over temperature, Protection against electric shock, Protection against direct contact to live parts, Protection against Earth leakage at car side |
Case 1 : 150 KW Max @ Charging Gun 1 @ Full Load, when only Gun 1 is in use Case 2: 75 KW Max @ Charging Gun 1 & 2 each, when Gun 1 is in use & another user comes to use Gun 2 Case 3 : 150 KW Max @ Charging Gun 2 @ Full Load, while Gun 2 is in use & user complete charging from Gun 1 |
200A@750V 187.5A@800V 176.5@850V 150A@1000V |
200A@375V 150A@500V 100A@750V |
Usuable Requirement as on Date : 120 KW which can be upgradable to 150 KW as an ultimate capacity |