Ndu3 -35 SPD Surge Protector Devicethree Phase Lightning Protection

China Ndu3-35 SPD Surge Protector Devicethree Phase Lightning Protection, Find details about China Surge Protector Device, SPD from Ndu3-35 SPD Surge Protector Devicethree Phase Lightning Protection

Model NO.
NDU3-35-2P
Fuse or Switch
Less Than 100A
Poles
2p
Operating Environment
-40c~+85c
Trademark
LOVADON
Transport Package
Standard Export Packing or Packing as Your Require
Specification
normal
Origin
China
HS Code
8536300000
Model NO.
NDU3-35-2P
Fuse or Switch
Less Than 100A
Poles
2p
Operating Environment
-40c~+85c
Trademark
LOVADON
Transport Package
Standard Export Packing or Packing as Your Require
Specification
normal
Origin
China
HS Code
8536300000
Product Description
The NDU3-35 switch modular high-performance SPD is based on IEC standard design, with high lightning flow capacity, suitable for lightning high-risk areas of the first level of lightning protection power supply system                                                    
"Products using modular design, good sealing, standard 35 off electrical rail installation, wiring is very convenient, simple maintenance and so on. The products are widely used in microwave communication station 7 station. Telecom room, industrial factories and mines. Financial. Securities and other power systems. Important and vulnerable to lightning.""Flow capacity of large, fast response Residual pressure is very low, no continued flow Pluggable structure with LED degradation indicator" "Flow capacity is large, fast response Residual pressure is very low, no continued flow"                                                    

Technical Parameters         
                        Model 
Technical Parameters
NDU3-15NDU3-25NDU3-35NDU3-50
Rated Operating Voltage Uc(V~)220V380V
Maximum Continuous Operating Voltage Uc( V~) 275V320V
Protection Level Up(V-)kV≤1.8≤2.0≤2.2≤2.5
Nominal Discharge Curreni limp( 10/350чs)kA 15253550
Response Time ns<100
Tesl StandardGB18802,IEC61643-1
L/N(mm2)The Cross Section of L/N Line16
PE(mm2) The Cross Section of PE Line25
Fuse or Switch(A)≥100A
Operating EnvironmentºC-40ºC~+85ºC
Relative Ilumidity (25ºC)≤95%
Installation Standard Rail 35mm
Material of Outer CoveringFiber glass reinforced plastic
 
Ndu3-35 SPD Surge Protector Devicethree Phase Lightning Protection