China UL1185 Spiral Single Core Shielded PVC Jacket Wire, Find details about China Solid Conductor, Stranded Conductor from UL1185 Spiral Single Core Shielded PVC Jacket Wire
APPLIANCE WIRING MATERIAL | |||||
Subj.758 | Issued:1959-05-01 | ||||
Revised:2011-10-24 | |||||
Style 1185 | Single conductor using extruded non-integral jacket. | ||||
Rating | 80 deg C, 300 Vac, Horizontal flame. | ||||
Conductor | 30 AWG - 4/0 AWG, solid or stranded. | ||||
Insulation | PVC | ||||
Conductor | Minimum average | Minimum thickness at any | |||
size | thickness | point | |||
30-16 AWG | 15 mils | 13 mils | |||
15-10 AWG | 30 mils | 27 mils | |||
9-8 AWG | 45 mils | 40 mils | |||
7-2 AWG | 60 mils | 54 mils | |||
1-4/0 AWG | 80 mils | 72 mils | |||
Assembly | Insulated conductor, optional shield, required | ||||
jacket, optional shield, optional jacket. | |||||
Shield | Optional. | ||||
Jacket | Extruded PVC. | ||||
Conductor | Minimum average | Minimum thickness at any | |||
size | thickness | point | |||
30-16 AWG | 15 mils | 12 mils | |||
15-2 AWG | 30 mils | 24 mils | |||
1-4/0 AWG | 45 mils | 36 mils | |||
30-16 AWG | or lacquered braid | ||||
Outer Shield | Optional. | ||||
Optional. Extruded PVC, 15 mils minimum average | |||||
Outer Jacket | thickness, 12 mils minimum thickness at any point. | ||||
Standard | Appliance Wiring Material UL 758. | ||||