Electromagnetic Flow Meter

China Electromagnetic Flow Meter, Find details about China Flow Meter, Electromagnetic Flow Meter from Electromagnetic Flow Meter

Model NO.
Flow Meter PCL
Protection
IP65, IP67, IP68
Ambient Temp.
-25ºC-60ºC
Repetition
≤±0.1%/, ±0.25%
Analog Output Error
≤±0.02mA
Measuring Range Velocity
≤20m/S
Electrical Connection
M20×1.5 Seal, G1/2, NPT1/2
Output
Standard 4-20mA, Pulse, RS485, Hart, Profibus-PA
Trademark
WTsensor
Origin
China
Model NO.
Flow Meter PCL
Protection
IP65, IP67, IP68
Ambient Temp.
-25ºC-60ºC
Repetition
≤±0.1%/, ±0.25%
Analog Output Error
≤±0.02mA
Measuring Range Velocity
≤20m/S
Electrical Connection
M20×1.5 Seal, G1/2, NPT1/2
Output
Standard 4-20mA, Pulse, RS485, Hart, Profibus-PA
Trademark
WTsensor
Origin
China
Introduction
PCL series electromagnetic flowmeters, composed of sensor and converter, work based on Faraday's law of electromagnetic induction. It is used to measure electrical conductivity of liquid or solid. Generally, the electrical conductivity should be over 5uS/cm (electrical conductivity of tap water, raw water is about 100-500uS/cm. It can also be used to measure various mediums like acid, alkali, saline solution, paper pulp, ore pulp and so on, but these mediums cannot contain a lot of magnetic materials and bubbles.

Working principle
The principle of the sensor is based on Faraday's law of electromagnetic induction. It is installed a pair of detection electrodes on the pipe wall, where the measurement pipe axis and magnetic field lines are vertical. When the conductive liquid moves along the measurement pipe axis, the conductive liquid cuts magnetic field lines and produces induced electromotive force, which can be measured by the two electrodes on the meter pipe. The result can be calculated by the formula:

Electromagnetic Flow Meter

When measuring flow, fluid flows through magnetic field which is perpendicular to the direction of the flow. Then the flow of conductive fluid induces electromotive force proportional to the average velocity. Therefore, the detected fluid requires to be higher than the minimum of electrical conductivity. Its induced voltage signal is detected through two electrodes and sent to a converter through the cable. After signal processing and related operations, PCL electromagnetic flowmeter will display total flow and instantaneous flow in converter display.
 
Specifications
 
Electromagnetic Flow Meter
Dimension
 

Electromagnetic Flow Meter

Electromagnetic Flow Meter
 
Diameter (mm)Dimension (mm)
LWH
1516095127
2016095137
25160115147
32160115155
40195150165
50195165187
65195185202
80195200223
100245220249
125245250278
150295285303
200345340358
250395395418
300500445468
350500505560
400600640614
450600670656
500600670710
600600780810
700700895995
80080010151115
90090011151215
1000100012301350
1200120014051505
(Data table for reference only)
 
Lining material selection
 

Lining material should be chosen according to the erosion, abrasion and temperature of measuring medium. The applicability of common lining materials are as follows.
 
Lining MaterialMain PropertiesScope of Application
CR
  1. Oil proof, solvent resistance, and resist the erosion of common medium such as acid, alkali, salt, etc.
  1. 0ºC-80ºC non-strong acid, non-strong alkali and non-strong oxidized medium
  2. Be able to measure sewage and mud
IR
  1. Good abrasive resistance, corrosion resistance, insulativity, cold resistance
  2. Low oil proof, aging resistance, oxidative resistance
  1. -10ºC-70ºC non-strong acid, non-strong alkali and non-strong oxidized medium; suitable for drinking water
PU
  1. Very good abrasive resistance and flexibility
  2. Low acid and alkali resistance
  1. -25ºC-60ºC
  2. Ore pulp, coal slurry and mud with neutral strong abrasive resistance
PFA
  1. Good hydrophobicity, non-viscousness and thermostability
  2. Great corrosion resistance, can resist strong acid, strong alkali, organic solvent and all saline solution
  3. Good negative pressure resistance, which can be increased by adding metal net inside
  4. Low abrasion resistance
  1. -25ºC-140ºC non-strong abrasion resistance medium
  2. Healthcare medium
PTFE
  1. Have the most stable chemical properties in plastics, and can resist boiling hydrochloric acid, sulfuric acid, nitric acid, aqua regia, strong alkali and all kinds of organic solvents, but cannot resist the corrosion of chlorine trifluoride, high temperature nitrogen trifluoride, liquid fluorine, liquid oxygen and ozone
  2. Low abrasion resistance
  3. Low negative pressure resistance
  1. -25ºC-140ºC
  2. Strong corrosion medium such as strong acid and alkali
  3. Healthcare medium
FEP(F46)
  1. Hydrophobic and non-viscous
  2. Corrosion resistance is inferior to PFA
  3. Negative pressure resistance can be increased by adding metal net inside.
  4. Low abrasion resistance
  1. -25ºC-100ºC non-strong abrasion resistance medium
  2. Healthcare medium
 
Electrode material selection
 

Electrode material should be selected according to the corrosion resistance of the measuring medium.
 
Electrode MaterialMain Properties
316LMeasure the medium such as water, sewage or inorganic acid, organic acid with slight corrosion.
HCResist the corrosion of oxidizing acid, such as nitric acid and mixed medium of chromic acid and sulfuric acid, and oxidative hydrochloric acid, such as Fe+++, Cu++ and some other oxidants, such as sub-argon salt solution higher than normal temperature and oily water.
TiResist the corrosion of salt water, various oxides, hypochlorite, oxidizing acid (including fuming sulfuric acid, nitric acid), organic acid, alkali and so on. It is not resistant to the corrosion of pure reductive acids such as sulfuric acid and hydrochloric acid, but if oxidizing agents are contained in acid, the corrosion is greatly reduced.
TaHave good corrosion resistance similar to glass. Resist the corrosion of almost all chemical medium, except hydrofluoric acid, fuming sulfuric acid and alkali. Sodium hydroxide and other alkaline solutions are not applicable.
Pt-IrHave good corrosion resistance of all acid, and can resist the corrosion of alkali and all salt.
 
Ground ring selection
 

The inductive signal voltage of electromagnetic flowmeter is low, so it is easy to be affected by outside noise or other electromagnetic signals. The function of ground ring is to form a space to shield outside interference so as to increase the accuracy by grounding the body of flowmeter. (The ground ring is required when you use non-metal pipe.) Installation methods in different conditions are as follows.Electromagnetic Flow Meter
How to order
 

Model: PCL
Electromagnetic Flow Meter