China Metal Enclosed Medium Voltage Electric Switchgear, Find details about China Ring Main Unit, Load Break Switch from Metal Enclosed Medium Voltage Electric Switchgear
Rated voltage | kV | 12 | 24 | ||
BIL | common value | kV | 75 | 125 | |
across the isolating distance | 85 | 145 | |||
AC withstand voltage | common value | kV | 28 1) | 50 | |
across the isolating distance | 32 1) | 60 | |||
Rated frequency | Hz | 50/60 | 50/60 | ||
Rated current | busbar | A | 630/1250 | 630/1250 | |
feeder | A | 630/800/12504) | 630/1250 4) | ||
Rated short-time withstand current | main circuit | kA | 25 | 20 | |
earthing circuit | kA | 25 | 20 | ||
Rated peak withstand current | kA | 65 | 50 | ||
Rated duration of short circuit | s | 1 | 1 | ||
Arc-fault current, 1s | kA | 20 | 20 | ||
Degree of protection, enclosure | IP2XC | IP2XC | |||
Degree of protection, partitions | IP2X | IP2X | |||
Ambient temperature | maximum value | [ºC] | 40 | 40 | |
maximum value of 24 h-mean | +35 | 35 | |||
minimum value | -5 3) | -5 3) | |||
Altitude above sea level | [m] | <1000 2) | <1000 2) | ||