China Iuniswitch Air Insulation Ring Main Unit, Find details about China Sf6 Indoor Load Break Switch, Ring Main Unit from Iuniswitch Air Insulation Ring Main Unit
Rated voltage Ur | kV | 12 | 24 | |
BIL | common value | kV | 75 | 125 |
across the isolating distance | 85 | 145 | ||
AC withstand voltage | common value | kV | 28 1) | 50 |
across the isolating distance | 32 1) | 60 | ||
Rated frequency | Hz | 50/60 | 50/60 | |
Rated current | busbar | A | 630/1250 | 630/1250 |
feeder | A | 630/800/1250 4) | 630/1250 4) | |
Rated short-time withstand current | main circuit | kA | 25 | 20 |
earthing circuit | kA | 25 | 20 | |
Rated peak withstand current | kA | 65 | 50 | |
Rated duration of short circuit | s | 1 | 1 | |
Arc-fault current, 1s | kA | 20 | 20 | |
Degree of protection, enclosure | IP2XC | IP2XC | ||
Degree of protection, partitions | IP2X | IP2X | ||
Ambient temperature | maximum value | [ºC] | 40 | 40 |
maximum value of 24 h-mean | +35 | 35 | ||
minimum value | -53) | -53) | ||
Altitude above sea level | [m] | <1000 2) | <1000 2) |