China 60kv Automatic Insulation Oil Bdv Tester Transformer Oil Breakdown Voltage Test Kit Oil Testing & Measuring Equipments, Find details about China Transformer Oil Breakdown Tester, Transformer Oil Bdv Tester from 60kv Automatic Insulation Oil Bdv Tester Transformer Oil Breakdown Voltage Test Kit Oil Testing & Measuring Equipments
Test voltage: | AC 0~60kV (100kV/80kV at option) |
Voltage boosting rate: | 2.0 kV/s,3.0 kV/s(selectable) |
Error 0.2kV/s | |
Power distortion: | <1% |
Electrodes Gap: | 2.5mm |
Volume: | 410×390×380mm |
Weight: | 26kg |
Environmental temperature: | 0-35ºC |
Relative humidity: | ≤75%RH |
Working power | AC 220V ± 20% |
Power Frequency | 50 Hz ± 5 Hz |
Power consumption: | 300VA |
Standing time | The default value is 15 min, and the optional range is 1-15 min (increment step is 1 min). |
Interval time | The default value is 5 min, and the optional range is 1-10 min (increment step is 1 min). |
Stirring time: | The default value is 10 s, the optional range is 5-90 s (increment step is 5 s) |
Boosting voltage: | The default value is 60 kV, and the optional range is 10-60 kV (increment step is 10kV). |
Testing time: | The default value is 6 times, and the optional range is 1-6 times (increment step is 1 time) |