Touch screen 128 channels gas alarm controller with RS485 connection and datalogger

Product description

Bus system 128 channels controller is a simple and practical controller that can connect 128 detectors.The system is compatible with all kinds of gas detectors. The 7-inch touch screen shows local time, detection gas, gas concentration , gas concentration unit and whether the current detector is in good condition in real time. When the gas concentration reaches the preset alarm value, it generates sound alarm. The controller can keep 1000 gas alarm records, which is convenient for users to keep track of the detector alarm status at any time.


 

Characteristics & Functions

Advanced microprocessor technology
7 inch touch screen operation
Good stability, high precision
·Universal, RS485 signal input

High brightness touch screen display, with two alarm functions
3 channesl relays and 1 common relay output
Display local time, type of gas detected, gas concentration, current detector status, etc in real time
standard RS485 signal output (optional)



Specificiation

 

Host capacity: can connect more than 50 sensors
Liquid crystal: 800* 480 resolution,7 inch resistance touch screen.
Processor: ARM
Gas detected: EX, CO, O2, N2, CO, H2S, CL2, NH4, SO2, H2, NO2, etc
Display mode: 8 channels are displayed on each page, and the page turning interval can be changed.
Inspection interval: 100mS (continuous channel data acquisition time interval)
Page change interval: 5-20s (adjustable)
Online setting: the alarm parameters of bus transmitter can be set online.
Switching output: 3 channel relays and 1 common relay
Data storage: can save 1000 gas alarm records, can check the alarm records on the controller
Communication interface: 1 RS485 communicates with bus transmitter.RS485 can be connected to the computer, and the computer can monitor all the data of the alarm host in real time.
Communication rate: 9600bps (mandatory).
Transmission distance: the maximum distance between detector and controller is less than 1000 meters, and the maximum distance between computer and host is less than 1000 meters.
Installation: wall mounted
System power supply: AC220V±15%,50Hz±1%
Power supply of transmitter: DC24V
Working temperature: - 20 ºC to 50 ºC
Humidity: no more than 95%RH


Product details

Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and DataloggerTouch Screen 128 Channels Gas Alarm Controller with RS485 Connection and DataloggerTouch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger

Company information
Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger
Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger
Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and DataloggerTouch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger
Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger
FAQ
Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger

Touch Screen 128 Channels Gas Alarm Controller with RS485 Connection and Datalogger