China Ylc2-D50 220/230V 50/60Hz, Find details about China AC Magnetic Contactor, Gmc 220 AC Magnetic Contactor from Ylc2-D50 220/230V 50/60Hz
1. General
1) Application: remote making & breaking circuits; protect circuit
from over-load when assembling with thermal over-load relay;..
frequent start-up and control of AC contactor;
2) Electric ratings: AC50/60Hz, 690V, up to 95A;
3) Utilization category: AC-3, AC-4;
4) Altitude: ≤2000m;
5) Ambient temperature: -5ºC~+40ºC;
6) Mounting category: III;
7) Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;.
8) Standard: IEC/EN 60947-4-1. .IEC/EN 60947-5-1. 9) Control Coil Voltage(AC Coil Operation)
Volts(VAC) | 24 | 36 | 42 | 48 | 110 | 127 | 220 | 230 | 240 | 380 | 415 | 440 | 480 | 500 | 600 | |
Code | 50Hz | B5 | C5 | D5 | E5 | F5 | G5 | M5 | P5 | U5 | Q5 | N5 | R5 | - | S5 | Y5 |
60Hz | B6 | - | D6 | E6 | F6 | G6 | M6 | - | U6 | Q6 | - | R6 | T6 | - | - | |
50/60Hz | B7 | - | D7 | E7 | F7 | - | M7 | P7 | - | Q7 | N7 | R7 | - | - | - |
2.Specifications | ||||||||
Type | Thermal Rated Current (A) | Rated Current AC-3 380V(A) | Control Power AC-3(KW) | Rated Insulation | ||||
220V | 380V | 415V | 660V | Voltage(V) | Aux.Contact | |||
LC1-D09 | 20 | 9 | 2.2 | 4 | 4 | 5.5 | 660 | 3P+1NO+1NC |
LC1-D12 | 20 | 12 | 3 | 5.5 | 5.5 | 7.5 | ||
LC1-D18 | 32 | 18 | 4 | 7.5 | 9 | 9 | ||
LC1-D25 | 40 | 25 | 5.5 | 11 | 11 | 15 | ||
LC1-D32 | 50 | 32 | 7.5 | 15 | 15 | 18.5 | ||
LC1-D40 | 60 | 40 | 11 | 18.5 | 22 | 30 | ||
LC1-D50 | 80 | 50 | 15 | 22 | 25 | 33 | ||
LC1-D65 | 80 | 65 | 18.5 | 30 | 37 | 37 | ||
LC1-D80 | 125 | 80 | 22 | 37 | 45 | 45 | ||
LC1-D95 | 125 | 95 | 25 | 45 | 45 | 45 | ||
LC1-D115 | 200 | 115 | 30 | 55 | 59 | 80 | ||
LC1-D150 | 250 | 150 | 40 | 75 | 80 | 100 |