China Low Current 1A 6A 10A Current Transformer for Nigeria Market, Find details about China Electrical Transformer, Current Transformer from Low Current 1A 6A 10A Current Transformer for Nigeria Market
Specification | PN | Ib (In(A)) | Imax (A) | Secondary Current (mA) | Accuracy(class) | Burden Rb(Ω) | |||||
CTS1.5(10)A/5mA 0.02s10Ω | 1.5 | 10 | 5 | 0.02 | 10+10 | ||||||
CTS1.5(10)A/5mA 0.01s10Ω | 1.5 | 10 | 5 | 0.01 | 10+10 | ||||||
Current Ratio ±(%) | |||||||||||
Accuracy | Imax | 0.5Imax | 2In | In | 0.5In | 0.2In | 0.1In | 0.05In | 0.02In | 0.01In | |
0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.02 | 0.04 | |
0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.01 | 0.02 | |
Phase error (′) | |||||||||||
Accuracy | Imax | 0.5Imax | 2In | In | 0.5In | 0.2In | 0.1In | 0.05In | 0.02In | 0.01In | |
0.02 | 0.6 | 0.6 | 0.6 | 0.6 | 0.6 | 0.6 | 0.6 | 0.6 | 0.6 | 1.2 | |
0.01 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.6 |