China Inbuilt Water Tank and Water Pump Integrated Industrial Water Chiller, Find details about China Water Chiller, Chiller from Inbuilt Water Tank and Water Pump Integrated Industrial Water Chiller
Industrial Water Cooled Screw Chiller (two compressors) | ||||||||||||
Model ESGW | 050DON | 070DON | 090DON | 120DON | 130DON | 155DON | 180DON | 210DON | 250DON | 265DON | ||
Rated Cooling Capacity | KW | 237 | 316 | 408 | 558 | 609 | 722 | 834 | 984 | 1164 | 1229 | |
USRT | 67.5 | 89.9 | 116.1 | 158.6 | 173.3 | 205.2 | 237.1 | 279.7 | 330.9 | 349.4 | ||
×1000kcal/h | 204.0 | 271.9 | 351.1 | 479.7 | 524.0 | 620.5 | 716.9 | 845.7 | 1000.8 | 1056.5 | ||
Input Power | KW | 46.6 | 61.0 | 75.6 | 103.2 | 113.4 | 126.2 | 147.2 | 176.4 | 204.6 | 216.0 | |
Comp. Input Power×Qty. (KW) | 23.3×2 | 30.5×2 | 37.8×2 | 51.6×2 | 56.7×2 | 63.1×2 | 73.6×2 | 88.2×2 | 102.3×2 | 108.0×2 | ||
Comp. Current (A) | 78.2 | 102.6 | 127.2 | 173.6 | 190.6 | 212.2 | 247.6 | 296.6 | 343.8 | 363 | ||
Refrigerant | R407C | |||||||||||
Power Supply | 3φ-380V-50HZ | |||||||||||
Safety Protection | Phase reversion protection, Phase lack protection, Overload current protection, Discharge air temp. protection, Low & High pressure protection, Low temp. protection, Reserved water flow protection interface. | |||||||||||
Number of Refrigeration Circuit | 2 | |||||||||||
Capacity Control (%) | 0, 33, 50, 66.5, 83, 100 | 0, 25, 37.5, 50, 62.5, 75, 87,5, 100 | ||||||||||
Refrigerant Charge (Kg) | 36 | 50 | 64 | 84 | 92 | 110 | 124 | 150 | 180 | 188 | ||
Condenser | Shell and Tube Type | |||||||||||
Water Side Max Pressure (MPa) | 1 | |||||||||||
Dia. of Pipe to Condenser (inch) | 3" | 3" | 4" | 4" | 5" | 5" | 5" | 5" | 4"×2 | 4"×2 | ||
Cooling Water Flow (m3/h) | 48.8 | 64.9 | 83.2 | 113.7 | 124.3 | 145.8 | 168.7 | 199.5 | 235.3 | 248.4 | ||
Condenser Water Pressure drop (kPa) | 45 | 46 | 46 | 47 | 48 | 49 | 49 | 50 | 49 | 50 | ||
Evaporator | Shell and Tube Type | |||||||||||
Water Side Max Pressure (MPa) | 1 | |||||||||||
Dia.of Pipe to Evaporator (inch) | 3" | 3" | 4" | 5" | 5" | 5" | 5" | 5" | 6" | 6" | ||
Chilled Water Flow (m3/h) | 40.8 | 54.4 | 70.2 | 95.9 | 104.8 | 124.1 | 143.4 | 169.1 | 200.2 | 211.3 | ||
Evaporator Water Pressure drop (kPa) | 31 | 37 | 40 | 42 | 54 | 51 | 44 | 46 | 47 | 47 | ||
Running Noise dB(A) | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | ||
Total weight (Kg) | 1570 | 1810 | 2150 | 2510 | 2820 | 3050 | 3250 | 3560 | 3860 | 4150 | ||
Running Weight (Kg) | 1990 | 2450 | 2880 | 3300 | 3700 | 4050 | 4350 | 4660 | 5060 | 5370 | ||
Dimension L×W×H | Detailed dimensions are according to the actual finished product sizes. |
Industrial Water Cooled Screw Chiller (two compressors) | ||||||||||||
Model ESGW | 290DON | 310DON | 325DON | 380DON | 415DON | 445DON | 500DON | 625DON | 735DON | 820DON | ||
Rated Cooling Capacity | KW | 1360 | 1449 | 1515 | 1763 | 1936 | 2078 | 2318 | 2912 | 3429 | 3827 | |
USRT | 386.6 | 411.9 | 430.9 | 501.3 | 550.4 | 590.7 | 659.2 | 828.0 | 975.0 | 1088.0 | ||
×1000kcal/h | 1169.0 | 1245.7 | 1302.9 | 1516.0 | 1664.6 | 1786.3 | 1993.4 | 2504.0 | 2948.3 | 3290.2 | ||
Input Power | KW | 240.2 | 254.6 | 268.2 | 308.8 | 339.2 | 361.4 | 403.2 | 508.4 | 595.4 | 657.8 | |
Comp. Input Power×Qty. (KW) | 120.1×2 | 127.3×2 | 134.1×2 | 154.4×2 | 169.6×2 | 180.7×2 | 201.6×2 | 254.2×2 | 297.7×2 | 328.9×2 | ||
Comp. Current (A) | 403.6 | 428 | 451 | 519.2 | 570.2 | 607.8 | 677.8 | 854.6 | 1001 | 1105.8 | ||
Refrigerant | R407C | |||||||||||
Power Supply | 3φ-380V-50HZ | |||||||||||
Safety Protection | Phase reversion protection, Phase lack protection, Overload current protection, Discharge air temp. protection, Low & High pressure protection, Low temp. protection, Reserved water flow protection interface. | |||||||||||
Number of Refrigeration Circuit | 2 | |||||||||||
Capacity Control (%) | 0, 25, 37.5, 50, 62.5, 75, 87,5, 100 | |||||||||||
Refrigerant Charge (Kg) | 204 | 220 | 230 | 268 | 296 | 316 | 354 | 436 | 512 | 584 | ||
Condenser | Shell and Tube Type | |||||||||||
Water Side Max Pressure (MPa) | 1 | |||||||||||
Dia. of Pipe to Condenser (inch) | 5"×2 | 5"×2 | 5"×2 | 5"×2 | 5"×2 | 5"×2 | 6"×2 | 6"×2 | 8"×2 | 8"×2 | ||
Cooling Water Flow (m3/h) | 275.1 | 292.9 | 306.7 | 356.3 | 391.2 | 419.4 | 468.0 | 588.2 | 692.1 | 771.2 | ||
Condenser Water Pressure drop (kPa) | 51 | 54 | 58 | 65 | 67 | 74 | 81 | 84 | 88 | 94 | ||
Evaporator | Shell and Tube Type | |||||||||||
Water Side Max Pressure (MPa) | 1 | |||||||||||
Dia.of Pipe to Evaporator (inch) | 6" | 8" | 8" | 8" | 8" | 8" | 8" | 8" | 10" | 10" | ||
Chilled Water Flow (m3/h) | 233.8 | 249.1 | 260.6 | 303.2 | 332.9 | 357.3 | 398.7 | 500.8 | 589.7 | 658.0 | ||
Evaporator Water Pressure drop (kPa) | 53 | 52 | 56 | 60 | 78 | 76 | 73 | 70 | 77 | 84 | ||
Running Noise dB(A) | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | 75.0 | ||
Total weight (Kg) | 4390 | 4800 | 5340 | 5850 | 6310 | 6540 | 6790 | 8200 | 8900 | 9500 | ||
Running Weight (Kg) | 5710 | 6150 | 6390 | 6630 | 6880 | 7220 | 7570 | 9360 | 10200 | 10800 | ||
Dimension L×W×H | Detailed dimensions are according to the actual finished product sizes. |