Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier

China Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier, Find details about China Transformer Test Bench, Transformer Test Bench Manufaturer from Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier

Model NO.
HZBZ-IV
Accuracy Grade
1
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Oil Cylinder Position
Under
Test Report
Yes
Measurement Accuracy
± (0.2%+2)
Work Power
110V-400V Adjustable
Work Temperature
-10°c~ 50°c
Environment Humidity
≤85%Rh
Power Frequency
50±1Hz
Sharpness of Separation
1
Trademark
HuaZheng
Transport Package
Wooden Box with Foam Inside
Specification
CE/ISO/IEC
Origin
Hebei, China
HS Code
9030332000
Model NO.
HZBZ-IV
Accuracy Grade
1
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Oil Cylinder Position
Under
Test Report
Yes
Measurement Accuracy
± (0.2%+2)
Work Power
110V-400V Adjustable
Work Temperature
-10°c~ 50°c
Environment Humidity
≤85%Rh
Power Frequency
50±1Hz
Sharpness of Separation
1
Trademark
HuaZheng
Transport Package
Wooden Box with Foam Inside
Specification
CE/ISO/IEC
Origin
Hebei, China
HS Code
9030332000
Power/Distribution Transformer Test Set Up | Transformer Test Bay Equipment Supplier
 

I.Automatic Transformer Test Bench Test ability:

1)Can meet the capacity of 63000KvA, 110Kv and below the oil-immersed transformer (including S9 S11 S13 and amorphous alloy transformer);

2) It can meet the capacity of 31500KvA, 35Kv and below dry-type transformers;

3) Mine explosion-proof transformers that can meet capacity of 6300KvA, 10Kv and below;

4) Special transformer (need to inform detailed capacity and voltage level when ordering).

 Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier
 

II.Automatic Transformer Test Bench Test item:

1) transformer winding resistance test

2) Transformer voltage ratio measurement and connection group number test

3) transformer no-load current (%) and no-load loss test

4) Transformer short circuit impedance (%) and load loss test

5) Transformer power frequency applied pressure test

6) Transformer induced withstand voltage test

 

III.Automatic Transformer Test Bench Extensible test project:

1) Transformer partial discharge test

2) No-load harmonic test (0-31th harmonic)

3) Withstand voltage test of transformer oil (0-80Kv)

4) Transformer temperature rise test (can automatically draw temperature rise curve)

5) Insulation resistance test (absorption ratio and polarization index)

6) Transformer anti-interference dielectric loss test

7) Lightning impact test.

 

 

IV.Automatic Transformer Test Bench Technical Parameters:

NO.EquipmentModelQuantity
1,HZBZ-IV Master station for transformer test bench
01Master station for transformer test bench HZBZ-IV1
02 industrial control machineIPC-610L1
 Display  screenSamsung stereo screen 27 inches1
 PrinterHP1
03 transformer test system software V1.01
2,Test instrument
01Turn ratio testerHZ-7001
02power analyzerHZ-3001
03Dual channel DC resistance tester HZ-2001
04Insulation resistance testercommon 3125A1
05Transformer dielectric loss tester HZ-60001
06Temperature inspector 8 temperature passageway1
3, High and low voltage control cabinet (containment structure, it can be hoisted as a whole, convenient and quick, internal wiring completed at once, saving installation and commissioning time).
01Instrument integration unit one set 1
02PLC control deviceSIEMENS S7-2001
03Test project distribution device400A1
04High voltage current metering device 1
 High voltage precision current Mutual inductor400-200-100-50-20-10-5A/5A
Voltage level:22/√3KV
Precision grade:0.1
3
05High voltage voltage metering devices 1
 High voltage precision voltage Mutual inductor(22.0-11.0-6.6-3.3)/√3/0.1KV
Voltage level:22/√3KV
Precision grade:0.1
3
4, Equipment
01Three-phase induction voltage regulator 250KVA(10-650V)1
02Intermediate transformer250KVA1
03Frequency doubling generator 10KV1
5,Test transformer console
01High voltage test transformer 50KVA/100KV1
02Test transformer console50KVA(Including electric regulator)1
03Protection resistance100KV1
 AccessoriesSpecial high voltage discharge rod  
 High voltage test line  
 Grounding wire and plug  
6, Other
01Cable and wire Regulator input: 150mm23*10M
Regulator output: 95mm23*10M
Intermediate input: 95mm23*10M
Intermediate variable output: 25mm23*10M (high voltage line)
Multiplier unit input: 25mm23*10M
Excitation regulation: 16mm23*10M
Multiplier unit output: 16mm23*10M
Test transformer input: 25mm22*10M
Test line: 50mm23*10M (high voltage line)
1
 lightning impulse test system
01Lightning impulse test system450KV/20KJ(including 300KV chopper device)1
Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier
Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier


V.Company Information

HuaZheng Electric Manufacturing (Baoding) Co.,Ltd is the supplier of the State Grid in China.It means we are the supplier of the Chinese Government.And our products spread throughout the whole China.
What's more, our customers come from different countries like America, England, Bulgaria, Brazil, Chile, Malysia, Vietnam and so on.

Our main products are Insulation Oil Tester, Cable Fault Locator, Power Quality Analyzer, High Voltage Generator, High Voltage Capacitor, Testing Transformer and so on.
Huazheng IEC60076 Electric Testing Equipment Transformer Turns Ratio


VI.Customer Visit
Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier


VII.Exhibition
Power/Distribution Transformer Test Set up Transformer Test Bay Equipment Supplier



VIII.Similar Recommendation
 