Specification:Conventional Fire Alarm Control Panel Alarm SystemMain power: AC220V± 15%,50Hz/ AC110V± 15%,60Hz
Battery: DC 24V (2 x 12V 3.3Ah)
Zone and sounder end of line resistors: 3.9KΩ,1W
Zone monitoring current:<4.5mA
Zone alarm current:>20mA
Zone short current:>110mA
Zone voltage: 24V±2V
Sounder alarm output: 3 x 300mA (max)/24VDC
Auxiliary Supply: 300mA/24V
Dimensions: 290 x 87.5 x 211.5mm
One set of fault relay contacts: Rated at 0.5A SELV
Humidity: ≤95%RH
Number of zones: 1,2,4
weight: 2100g (without battery)
Features:• The CF800X panel is available on 1,2,4 zones.
• Each zone has a maximum capacity of 50 devices.
• It has 3 groups of sounders output circuits each capable of supplying 300mA.
• It has a 24V/300mA auxiliary supply.
• It has a set of fault relay contacts,rated at 0.5A SELV.
• It has the ability to disable any zone,any group of sounder.
• The panel will send a fault signal when there is zone short/open or sounder short/open.
• It has the ability to disconnect the zones and sounders automatically when there is zone short or sounder short.
After the short is clear, the zones and sounders will recover.
• It has the sounder start/stop and delay facility (the delay time is 30-120 seconds in 30 seconds increments).
• It has the "rst "re alarm and subsequent "re alarm functions.
The indicator of the "rst "re zone is #ashing and the subsequent"re zone is lit.
• It has the mains-lost silence function.After con"gure the mains lostsilence function,the panel will not send the main power lost fault signal. Related Products