China 6kv Kbsg Series Dry Type Mining Explosion Isolation Dry Type Transformer (A), Find details about China Explosion-Proof Transformer, Mine Transformer from 6kv Kbsg Series Dry Type Mining Explosion Isolation Dry Type Transformer (A)
Technical Data of 6kV KBSG Series Dry Type Mining Explosion Isolation Dry Type Transformer | ||||||||||||
Loss (kW) | Weight (kg) | (mm) | Gauge(mm) | |||||||||
Rated Capacity | Voltage Group(kV) | Connection Method | (145) | No-load current | Impedance | (L) | (W) | (H) | ||||
(kVA) | HV | LV | No-load | Load | % | % | Machine | Dimension | ||||
50 | 6± 5% | 0.693/0.4 1.2/0.693 1.2 3.45 | Yy0 (d11) | 350 | 550 | 2.5 | 4 | 1350 | 2250 | 950 | 1160 | 600 |
100 | 520 | 920 | 2.5 | 4 | 1600 | 2500 | 950 | 1430 | ||||
200 | 820 | 1550 | 2 | 4 | 2050 | 2640 | 950 | 1445 | 600 900 | |||
250 | 950 | 1800 | 2 | 4 | 2300 | 2750 | 965 | 1530 | ||||
315 | 1100 | 2150 | 1.8 | 4 | 2500 | 2830 | 975 | 1540 | ||||
400 | 1300 | 2600 | 1.8 | 4 | 2650 | 2830 | 995 | 1550 | ||||
500 | 1500 | 3100 | 1.5 | 4 | 3100 | 2850 | 1050 | 1570 | ||||
630 | 1800 | 3680 | 1 | 4 | 4310 | 3020 | 1080 | 1450 | ||||
800 | Yy0 (d11) Dyn11 | 2050 | 4500 | 1 | 4 | 4650 | 3020 | 1080 | 1510 | |||
1000 | 2350 | 5400 | 1 | 4 | 5150 | 3030 | 1130 | 1540 | ||||
1250 | 2750 | 6500 | 0.8 | 4 | 5900 | 3120 | 1160 | 1610 | ||||
1600 | 3350 | 8000 | 0.6 | 4 | 7250 | 3120 | 1200 | 1750 | ||||
2000 | 3800 | 8500 | 0.6 | 4.5 | 10820 | 3225 | 1220 | 1790 | ||||
2500 | 4500 | 10600 | 0.6 | 5 | 13850 | 3580 | 1230 | 1850 | ||||
3150 | 5300 | 12500 | 0.6 | 5.5 | 18250 | 3820 | 1260 | 1890 | ||||
4000 | 6100 | 14000 | 0.6 | 6 | 20810 | 3930 | 1400 | 1920 | ||||
(Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz. The above data provides a reference only, movable transformer sustation the basis switch of the shape size of transformer substation different but different. |