China Multifunction Evi Split DC Inverter Heat Pump, Find details about China DC Inverter Heat Pump, DC Inverter Evi Heat Pump from Multifunction Evi Split DC Inverter Heat Pump
Air Source Heat Pump Unit( EVI DC Inverter Split Type ) (Heating&Cooling) | ||||||
Model | ESSA-05LHP | ESSA-05LHP | ESSA-10LHP | ESSA-10LHP | ||
3ES | 5ES | 6ES | 8ES | |||
Working mode | Heating&Cooling | |||||
Working environment temperature range | -25ºC~43ºC | |||||
Power supply | 220-240V/1PH/50HZ | 220-240V/1PH/50HZ | 220-240V/1PH/50HZ | 380-420V/3PH/50HZ | ||
Heating | Air DB/WB: 7ºC/6ºC, water In/outlet: 30ºC/35ºC | Heating capacity (kW) | 9.7 | 16.4 | 19.0 | 24.8 |
Min.~Max.(kW) | 3~9.7 | 5~16.4 | 5~19 | 6~24.8 | ||
Input power(kW) | 2.2 | 3.68 | 4.35 | 5.7 | ||
Current(A) | 10.5 | 16 | 19 | 9 | ||
COP(W/W) | 4.41 | 4.46 | 4.37 | 4.35 | ||
Air DB/WB: 2ºC/1ºC, water In/outlet: 30ºC/35ºC | Heating capacity (kW) | 8.0 | 13.0 | 16.0 | 20.0 | |
Min.~Max.(kW) | 3~8 | 5~13 | 5~16 | 6~20 | ||
Input power(kW) | 2.32 | 3.62 | 4.65 | 5.6 | ||
Current(A) | 11.0 | 16.8 | 19.8 | 9.7 | ||
COP(W/W) | 3.45 | 3.59 | 3.44 | 3.57 | ||
Cooling | Air DB/WB: 35ºC/24ºC, water In/outlet: 12ºC/7ºC | Cooling capacity (kW) | 7.3 | 12.3 | 14.2 | 17.5 |
Min.~Max.(kW) | 3.1~7.3 | 5.4~12.3 | 6.3~14.2 | 7.4~17.5 | ||
Input power (kW) | 2.8 | 4.6 | 5.5 | 6.3 | ||
EER | 2.61 | 2.67 | 2.58 | 2.78 |