China Honny Power More Than 25 Years Experience Generador, Find details about China Generador, Honny Power from Honny Power More Than 25 Years Experience Generador
Genset Model | HGM500E | |
Genset Prime Output | kW/kVA | 360/450 |
Genset Standby Output | kW/kVA | 400/500 |
Rating Power Factor | 0.8 | |
Rating Speed | rpm | 1500 |
Rating Frequency | Hz | 50 |
Rating Voltage | V | 400 |
Engine Model | PTAA13E-G5 | |
Displacement | l | 12.8 |
Configuration | 6 in line | |
Genset Size-Open Type (LxWxH) | mm | 3300x1150x1600 |
Genset Weight | kg | 2900 |
Engine Model | PTAA13E-G5 | |
Engine Standby Output (LTP) | kW | 450 |
Engine Prime Output (PRP) | kW | 408 |
Engine Continuous Power (COP) | kW | 320 |
Typical Alternator Efficiency | 94.1% | |
Speed droop (static) elect. Gov. | 0-5% | |
Governing standards to ISO 8528 | G3 | |
Max. step load acceptance, 1st step(% PRP) | 55% | |
Engine Data in General | ||
Aspiration Type | Turbocharger, air- air aftercooler | |
Injection Type | Common rail | |
Configuration | In line | |
No. of Cylinders | 6 | |
Displacement | l | 12.8 |
Bore | mm | 128 |
Stroke | mm | 166 |
Compression Ratio | 15.5:1 | |
Piston Speed | m/s | 8.3 |
Rotation Direction (from flywheel) | Counter Clockwise | |
Number of Flywheel Teeth | 160 | |
Flywheel House Size | SAE1-14 | |
Lubrication System | ||
Lube Oil Specification | AFI-CG4 | |
Oil Capacity | l | 40 |
Max. Permissible Oil Temperature | °C | 110 |
Oil Pressure Warning | kPa | 200 |
Oil Pressure Shutdown | kPa | 160 |
Oil Consumption (as % of fuel consumption ) | % | ≤0.5 |
Cooling System | ||
Coolant Capacity for Engine | l | 18 |
Max. Permissible Temperature | °C | 90 |
Max. Coolant Warning Temperature | °C | 95 |
Max. Coolant Shutdown Temperature | °C | 105 |
Thermostat Open Temperature | °C | 71 |
Radiator Cooling Flow | m³/min | 410 |
Flow of Coolant pump | m³/h | 19.7 |
Heat dissipation (engine radiator) | kW | 258 |
Heat dissipation (convection) | kW | 39 |
Fuel System | ||
Governor Type | Common Rail | |
Fuel Consumption at 25% of genset prime output | l/h | 27 |
Fuel Consumption at 50% of genset prime output | l/h | 50 |
Fuel Consumption at 75% of genset prime output | l/h | 73 |
Fuel Consumption at 100% of genset prime output | l/h | 97 |
Lowest Fuel Consumption Ratio | g/kW.hr | 199 |
Intake & Exhaust System (On Standby Output) | ||
Combustion Air Consumption | m³/min | 34 |
Max. Intake Restriction | KPa | 5 |
Exhaust Temperature (Before Turbo) | °C | 645 |
Exhaust Temperature (After Turbo) | °C | 520 |
Max. Exhaust Back Pressure | Kpa | 5 |
Exhaust Gas Flow | m³/min | 40.4 |
Turbo Bellows Diameter | mm | DN100-150 |
Exhaust Flange Diameter | mm | DN150 |
Electrical System | ||
Charging Alternator Voltage | V | 28 |
Charging Alternator Capacity | A | 35 |
Starting Voltage | V | 24 |
Starting Motor Capacity | kW | 1*6.6 |
Minimum Battery Capacity | Ah | 2*150 |
Emission Data | ||
CO | g/kW.h | 2.587 |
HC | g/kW.h | 0.130 |
NOX | g/kW.h | 3.518 |
PM | g/kW.h | 0.185 |
Generator-Googol Power | ||
Generator Model | GP450-4P | |
Capacity @ 0.8PF, H Rise Class | kW | 360 |
Efficiency @ 0.8PF | % | 94.1 |
Duty | S1 | |
Bearing | Single | |
Insulation | H | |
Rise Temperature | H | |
Enclosure | IP23 | |
Over speed | rpm | 2250 |
Excitation System | AVR | |
AVR Model | SX440 | |
Poles | 4 |