Heat Recovery Outside Chilled Water Cooling Ahu Package Unit

China Heat Recovery Outside Chilled Water Cooling Ahu Package Unit, Find details about China Ahu, Air Handling Unit from Heat Recovery Outside Chilled Water Cooling Ahu Package Unit

Mounting
Floor Standing
Lifetime
15~20 years
Certification
RoHS, ISO, CE, CCC
Condition
New
Cooling Capacity
7-1000kw
Heating Capacity
7-1000kw
Fluid
Chilled Water, Refrigerant Gas
Refrigerant
R22/R407c/R410A/R134A
Chilled Water
7-12degree
Compressor Brand
Copeland/Panasonic/Daikin etc
Condenser
Copper Tube Aluminum Fin
Evaporator
Copper Tube Aluminum Fin
Tube Diameter
7.94mm/9.52mm/12.7mm/15.88mm
Fan
Axial Fan
Voltage
380V/3p/50Hz
Additional Function
Fresh Air Dehumidification Humidification
Trademark
Shenglin
Transport Package
Wrap Film or Customized
Specification
CE, ISO
Origin
Shanghai, China(Mainland)
HS Code
8415909000
Mounting
Floor Standing
Lifetime
15~20 years
Certification
RoHS, ISO, CE, CCC
Condition
New
Cooling Capacity
7-1000kw
Heating Capacity
7-1000kw
Fluid
Chilled Water, Refrigerant Gas
Refrigerant
R22/R407c/R410A/R134A
Chilled Water
7-12degree
Compressor Brand
Copeland/Panasonic/Daikin etc
Condenser
Copper Tube Aluminum Fin
Evaporator
Copper Tube Aluminum Fin
Tube Diameter
7.94mm/9.52mm/12.7mm/15.88mm
Fan
Axial Fan
Voltage
380V/3p/50Hz
Additional Function
Fresh Air Dehumidification Humidification
Trademark
Shenglin
Transport Package
Wrap Film or Customized
Specification
CE, ISO
Origin
Shanghai, China(Mainland)
HS Code
8415909000
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit

Feature:

1, Complying with above China Standard, which is from ARI standard. ISO9001 and ISO14001 qualified.
2, Choose best materials, main components are from China top brand or imported.
3, The modular casing design, easy interchanging each other. easy install,easy transport,easy maintaince.
4, Unique no-cold-bridge design, improve the insulation and air tightness, total air leak rate ≤2.5%;
5, With dynamic balanced double inlet Centrifugal fan, with good air dynamic features, and accurate working, high efficiency, low vibration, low noise etc.
6, High efficient heat exchanger coil, ensure to provide the enough cooling capacity to the unit. And also high efficient breakwater panel is provided if required, water flow in coil ≤3×10-4kg/kg
7, Strong structure, good looking and permanent color.
8, Reasonable inside structure, with the suitable space for maintenance and cleaning.
9, Casing sheet: Provide double-skin construction constructing Sandwich type comprising 0.5mm thick galvanized internal and external skins and with 30mm thick polystyrene insulation of minimum 45kg/m3 density. Good airproof material is use between the casing and the frame to reduce the rate of the air leak.
The combined air handling untis are modular designed ,each modular can be used independently and can also work together and company with fan coil units to add refresh air. Not only reduce operation costs and energy saving, but also optimize air quality and create a congnitive indoor space to meet the human health requirements


Technical Data
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Air cooled direct expansion type air handling unit
unit characteristicsModel: GT-ZKW-()DX203040506580100
Cooling capacityKW10.115.320.325.532.338.652.0
Heating capacityKW10.315.720.826.133.539.553.2
Supply air volumeM³/h20003000400050006500800010000
Margin blast pressurePa200250300300400400500
Power3N-380V-50Hz
 
 
 
 
 
 
 
 
Indoor unit
BlowerTypeHigh efficient centrifugal fan
KW0.550.751.52.23.03.05.5
Chilled water coil
(option)
TypeHigh efficient copper tube aluminum fin
Water flow
(m³/h)
1.72.63.54.45.66.68.9
Segment length
(mm)
300300300300300300300
HeaterTypeStainless steel tubular electric heater/ Steam heat coil/ Hot water heat coil
KW691218242430
segment length
(mm)
300300300300400400400
HumidifierTypeElectrode type/ Steam/ Electrothermic type/ Wet film
KW345881212
segment length
(mm)
400400400400400400400
Air filterTypePrimary filter G4( Middle filter F8 &Nanocrystalline carbon filter)
NoisedB(A)60606162636365
SizeL (mm)1800200020002100210022002400
W (mm)730103010301030114013401340
H (mm)78878811151115111511151420
WeightKG140180320400580660800
Outdoor unitModel: GT-WL-10152025354055
Compressor ATypeHermetic Scroll ( Fixed frequency system)
Quantity1111122
Input power AKW3.44.86.38.09.812.716.1
Compressor BTypeHermetic Scroll( Frequency conversion system)
Quantity1111122
Input power BKW3.34.66.27.79.712.615.6
RefrigerantTypeR22/R407C/R410A
ModeThermal expansion valve/ Electronic expansion valve
NoisedB(A)63636464656576
SizeL (mm)85085098098098018801880
W (mm)850850980980980980980
H (mm)1080108010801080123410801080
WeightKG130135150180220280320
Connection Pipe diameterliquid pipe(mm)12.7
(9.52)
12.7
(9.52)
12.7
(12.7)
15.88
(12.7)
15.88
(12.7)
15.88*2
(12.7*2)
15.88*2
(12.7*2)
gas pipe(mm)15.88
(12.7)
19.05
(15.88)
19.05
(15.88)
28.6
(22.23)
15.88
(12.7)
22.23*2
(19.05*2)
28.6*2
(22.23*2)

Note:
Cooling condition: indoor dry bulb/wet bulb 27/19 ºC;Outdoor dry bulb/wet bulb 35/24 ºC;
Heating condition: indoor dry bulb/wet bulb 20/- ºC;Outdoor dry bulb/wet bulb 7/6 ºC;
Air volume, pressure, power in the table is standard parameters. It can be separately designed according to customer's requirements;
Chilled water coil as optional parts, according to the customer site requirements configured to double cold source unit;
Heater, humidifier, heat recovery device as optional parts, according to the customer requirements configured to the specific form
Unit standard USES G4 level filters, according to the customer requirements configured to the other forms;
Unit length does not include the function section. Such as heating section humidification secition. Specific details please consult us;
Air cooled split type air conditioning unit without refrigerant leaving the factory, refrigerant models need to indicated in the order;
Noise data is measured 2 m in the front of the unit , 1.2 m high, when cooling under the standard air volume; 
Inside of bracket is R410A refrigerant type connection pipe diameter, the connection copper pipe between the indoor and outdoor unit should within 35 meters.


Chilled water type air handling unit

Model GT-ZKW-20406080100150200250300
Air volume(m³/h)20004000600080001000015000200002500030000
Outlet air pressure(pa)300300400500500600750750750
Supply fan capacity(kw)1.11.52.245.511151518.5
Cooling4 RowsReturn air(kw)12.223.935.9486090120150179
water flow(m³/h)2.24.26.18.210.515.320.423.828.2
all fresh air(kw)2243.86290112156210265310
water flow(m³/h)3.87.71115.519.227.336.545.855
pipe diameter (DN)253240404050656580
6 RowsReturn air(kw)1730.145.26075113151188210
water flow(m³/h)2.85.37.710.513.619.225.530.236
all fresh air(kw)30.55888118150200288355420
water flow(m³/h)5.11015.220.226.235.5497072.5
pipe diameter (DN)323240405065658080
8 RowsReturn air(kw)18.335.2537090132176220264
water flow(m³/h)3.26.28.912.216.222.230.237.244.2
all fresh air(kw)34.870101138178245332410500
water flow(m³/h)5.81217.523.530.842.557.17185
pipe diameter (DN)323240405065658080
Heating2 RowsReturn air(kw)20426084108150200250300
water flow(m³/h)0.81.92.63.74.66.58.71113
all fresh air(kw)18385470100125180210280
water flow(m³/h)0.81.72.43.24.55.57.81012
pipe diameter (DN)253240404040505065
4 RowsReturn air(kw)285680110140200250320380
water flow(m³/h)1.22.43.54.86.391113.518.2
all fresh air(kw)326290125150220300380450
water flow(m³/h)1.52.73.85.46.89.513.516.219.5
pipe diameter (DN)323240404050506565
Function section
outside dimension
Mixing sectionLength(mm)500500500550600800800800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Pre-filter sectionLength(mm)100100100100100100100100100
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Medium efficiency filter sectionLength(mm)500500500500500500500500500
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Cooling coil sectionLength(mm)60060070070070080080010001000
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Heating sectionLength(mm)300300300400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Humidifying sectionLength(mm)400400400400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Fan sectionLength(mm)50050090040011001400160017001850
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Current balance sectionLength(mm)400400500900500600600600700
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Sound deadening sectionLength(mm)800800800500800100010001000100
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Air outlet sectionLength(mm)400400400800500600600800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200

Note:
Cooling condition: supply water/return water 7/12 ºC, indoor dry bulb/wet bulb 27/19ºC , fresh air dry bulb/wet bulb 35/28ºC ;
Heating condition: supply water/return water 60/50ºC, indoor dry bulb/wet bulb 20/-ºC,outdoor air dry bulb/wet bulb 7/6ºC;
Air volume, pressure, power in the table is standard parameters. It can be separately designed according to customer's requirements;
Heater, humidifier, heat recovery device as optional parts, according to the customer requirements configured to the specific form;
Unit standard USES G4 level filters, according to the customer requirements configured to the other forms;
Unit length is decided for the number of function section. Specific details please consult us;


Application

The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.

Air handling unit drawing

General comfortable occasion air handling unit
Configuration of basic function, early efficient filter and hot coil in air handling units (choose wet membrane humidification), it has the simple and highly controllable size characteristics of the function.
Suitable for general building room comfort air conditioning process.


Heat Recovery Outside Chilled Water Cooling Ahu Package Unit

Air handling units for all fresh air occasion
Configuration of basic function, primary filter or medium efficiency air filter, cooling coil ( enough margin, meet the needs of extreme conditions), it use steam, hot water heating, or natural gas direct combustion heating section
( high thermal efficiency, low running cost); it also need to set the reheat, can choose the cooling reheat to control humidity and enhance the energy level, or set up the electric heater, to realize thermal compensation again after the summer dehumidification. It mainly meet the aerospace, automotive, instruments and meters, precision machining and other special industry requirements for air quality.

Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Air handling units for general technology purification occasion
The configuration of the function section are: mixed section, cooling section, fan section, primary efficiency filter (G4) section, medium efficiency filter (F8) section. At the same time,it equipped with electric heating, electric humidification, muffler to satisfy high cleanliness, constant temperature and humidity,low noise control cleanliness project. Such as: inspection and quarantine laboratory, electronics factory workshop, biological engineering R&D center, food processing, precision machinery, pharmaceutical processing and storage area and other places which have strict requirements for temperature and humidity, cleanliness.

Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Air handling units with heat recovery device
Can configured with wheel heat recovery device, hot and cold air passes through hot wheel, heat and moisture exchange is carried out by the difference of temperature and steam pressure between fresh air and exhaust air, effective recovery of sensible heat and latent heat in exhaust air, achieve the purpose of energy conservation.Honeycomb structure with aluminum foil carrier and high efficient moisture absorbing coating for heat storage core body of heat exchanger, excellent characteristics of heat storage, moisture absorption and heat transfer, efficiency is higher than 75%.

Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit
Heat Recovery Outside Chilled Water Cooling Ahu Package Unit